5167821-YTG-J-0518
Johnson Controls Ducted Systems
27
115°F
125°F
1250
77
45.1
3.8
-
27.0
17.6
-
-
-
40.1
4.3
-
26.3
16.1
-
-
-
72
42.6
3.7
-
30.5
23.2
16.0
-
-
38.7
4.2
-
29.0
21.6
14.3
-
-
67
40.2
3.7
-
34.0
28.8
22.0
15.2
-
37.4
4.1
-
31.7
27.2
20.3
13.3
-
62
40.0
3.7
-
36.7
34.4
28.1
21.7
15.3
37.4
4.2
-
34.5
32.8
26.2
19.6
13.0
1500
77
45.1
3.8
-
26.6
15.4
-
-
-
40.3
4.3
-
25.4
13.4
-
-
-
72
43.1
3.7
-
31.1
23.2
15.4
-
-
39.2
4.2
-
29.2
21.3
13.5
-
-
67
41.1
3.7
-
35.6
31.1
23.2
15.3
-
38.1
4.1
-
33.1
29.3
21.3
13.3
-
62
41.0
3.7
-
39.5
39.0
31.0
23.0
15.0
38.2
4.2
-
37.0
37.0
29.1
21.1
13.0
57
40.9
3.7
-
39.9
39.9
38.8
30.8
22.7
38.4
4.2
-
37.2
37.2
37.0
28.8
20.6
1750
77
45.1
3.7
39.4
26.3
13.1
-
-
-
40.5
4.2
38.1
24.4
10.7
-
-
-
72
43.6
3.7
40.2
31.7
23.3
14.8
-
-
39.7
4.2
37.9
29.5
21.0
12.6
-
-
67
42.0
3.7
41.0
37.2
33.4
24.4
15.4
-
38.8
4.1
37.7
34.5
31.3
22.3
13.3
-
62
42.0
3.7
41.0
41.0
41.0
34.0
24.4
14.8
39.1
4.1
37.9
37.9
37.9
32.1
22.5
12.9
57
42.1
3.7
41.1
41.1
41.1
41.1
33.4
23.3
39.3
4.2
38.1
38.1
38.1
38.1
31.6
21.5
2000
77
45.1
3.7
41.0
25.9
10.9
-
-
-
40.8
4.2
38.9
23.5
8.1
-
-
-
72
44.0
3.7
41.4
32.4
23.3
14.2
-
-
40.3
4.2
38.7
29.7
20.7
11.8
-
-
67
42.9
3.6
41.9
38.8
35.7
25.6
15.4
-
39.6
4.1
38.4
35.9
33.4
23.4
13.4
-
62
43.0
3.7
42.1
42.1
42.1
36.9
25.8
14.6
39.9
4.1
38.8
38.8
38.8
35.0
23.9
12.8
57
43.2
3.7
42.2
42.2
42.2
42.2
36.1
23.8
40.3
4.1
39.1
39.1
39.1
39.1
34.5
22.3
2250
72
44.5
3.7
42.7
33.0
23.3
13.6
-
-
40.8
4.1
39.4
29.9
20.4
10.9
-
-
67
43.8
3.6
42.8
40.4
38.0
26.8
15.5
-
40.3
4.1
39.2
37.3
35.4
24.4
13.4
-
62
44.0
3.6
43.1
43.1
43.1
39.9
27.1
14.3
40.8
4.1
39.6
39.6
39.6
37.9
25.3
12.8
57
44.3
3.6
43.3
43.3
43.3
43.3
38.7
24.4
41.2
4.1
40.1
40.1
40.1
40.1
37.3
23.2
2500
72
45.0
3.6
-
33.6
23.3
13.0
-
-
41.3
4.1
-
-
-
-
-
-
67
44.6
3.6
-
42.0
40.3
27.9
15.6
-
41.0
4.1
-
-
-
-
-
-
62
45.0
3.6
-
44.1
44.1
42.9
28.5
14.1
41.6
4.1
-
-
-
-
-
-
57
45.4
3.6
-
44.5
44.5
44.5
41.3
24.9
42.2
4.1
-
-
-
-
-
-
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
ZT061 Low Speed Compressor (5.0 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F)
Return Dry Bulb (°F)
90
85
80
75
70
65
90
85
80
75
70
65