background image

5285473-UIM-E-1217

10

Johnson Controls Unitary Products

GAS CONNECTION

The gas supply line should be routed through the 1-5/8” hole located on
the right side of the unit. See Figure 3 for the location. The unit is sup-
plied with a rubber grommet that fits in this hole and is used to seal
around the gas pipe. THIS GROMMET MUST BE INSTALLED IN
ORDER TO PREVENT LEAKAGE OF AIR AND WATER INTO THE
HEATING/CONTROLS COMPARTMENT.

Gas piping requirements:

1.

Install a drip leg and a ground joint union in the gas piping.

2.

Install a manual shut-off valve outside of the unit if required by local
codes.

3.

Use wrought iron or steel pipe for all gas lines. Apply pipe thread
sealant sparingly to male threads only.

4.

Clean all piping of dirt and scale by hammering on the outside of
the pipe and blowing out the loose dirt and scale. Before initial start-
up, be sure that all of the gas lines external to the unit have been
purged of air.

5.

Ensure that the gas supply is a separate line and is installed in
accordance with all applicable safety codes. After the gas connec-
tions have been completed, open the main shut-off valve admitting
normal gas pressure to the gas valve. Check all joints for leaks with
soap solution or other material suitable for the purpose. NEVER
USE AN OPEN FLAME to check for leaks.

6.

Pressure tests in excess of 1/2 psi (3.48 kPa): During the gas sup-
ply piping system pressure test, ensure that the unit and its equip-
ment shutoff valve is disconnected from the gas supply system. 

7.

Pressure tests equal to or less than 1/2 psig (3.48 kPa): During the
gas supply piping system pressure test, verify that the unit is iso-
lated from the gas supply piping system by closing its individual
manual shut-off valve.

FLUE VENT AND AIR INTAKE HOOD

The flue vent hood and air intake hoods are shipped loose. These hoods
must be installed to assure proper unit operation. The hoods must be fas-
tened to the outside of the side gas control/electrical compartment with
the screws provided. See Figure 8.

Table 7: 

Natural Gas Pipe Sizing Chart

1

1. Maximum capacity of pipe in cubic feet of gas per hour (based upon a pres-

sure drop of 0.3 inch water column and 0.6 specific gravity gas).

Length

In Feet

Nominal Inches Iron Pipe Size

1/2”

3/4”

1”

1-1/4”

10

132

278

520

1,050

20

92

190

350

730

30

73

152

285

590

40

63

130

245

500

50

56

115

215

440

60

50

105

195

400

70

46

96

180

370

80

43

90

170

350

90

40

84

160

320

100

38

79

150

305

Table 8: 

Propane (LP) Gas Pipe Sizing Chart

1

1. Maximum capacity of pipe in thousands of BTU per hour (based upon a 

pressure drop of 0.5 inch water column).

Length

In Feet

Nominal Inches Iron Pipe Size

1/2”

3/4”

1”

1-1/4”

10

275

567

1071

2,205

20

189

393

732

1496

30

152

315

590

1212

40

129

267

504

1039

50

114

237

448

913

60

103

217

409

834

70

96

196

378

771

80

89

185

346

724

90

83

173

322

677

100

78

162

307

630

 CAUTION

If flexible stainless steel tubing is allowed by the authority having
jurisdiction, wrought iron or steel pipe must be installed at the gas
valve and extend a minimum of two (2) inches outside of the unit cas-
ing.

 WARNING

Natural gas may contain some propane. Propane being an excellent
solvent, will quickly dissolve white lead or most standard commercial
compounds. Therefore, a special pipe thread sealant must be
applied when wrought iron or steel pipe is used. Shellac base com-
pounds such as gaskoloc or stalastic, and compounds such as Rec-
torseal # 5, Clyde’s or John Crane may be used.

!

!

 WARNING

FIRE OR EXPLOSION HAZARD
Failure to follow the safety warning exactly could result in serious
injury, death or property damage.
Never test for gas leaks with an open flame. Use a commercially
available soap solution made specifically for the detection of leaks to
check all connections. A fire or explosion may result causing property
damage, personal injury or loss of life.

 WARNING

Flue hood surfaces may be hot.

 FIGURE 8:  

Flue Vent Outlet Air Hood

 CAUTION

The flue exhaust hood must be properly installed within the recom-
mended clearances. Further communications and action must be
given to the home or building owner(s) to eliminate any unauthorized
human contact around this area during the heating cycle. Flue hood
surfaces and the immediate area reach high temperatures during the
heating cycle.

!

!

AIR INTAKE HOOD

AIR INTAKE SCREEN

EXHAUST HOOD

A0284-001

!

Summary of Contents for PCG6B42

Page 1: ...Feet Per Hour 20 SECTION I GENERAL INFORMATION These are electric cooling gas heating units designed for outdoor instal lation Only gas piping electric power and duct connections are required for ins...

Page 2: ...ation in this manual is not followed exactly a fire or explosion may result causing property damage personal injury or loss of life Do not store or use gasoline or other flammable vapors and liquids i...

Page 3: ...stallation only 2 Condenser coils must have an unlimited supply of air Where a choice of location is possible position the unit on either north or east side of building 3 Suitable for mounting on roof...

Page 4: ...the spreader bars exceed the largest dimension across the unit Units may be moved or lifted with a forklift Slotted openings in the base rails are provided for this purpose WARNING Do not permit over...

Page 5: ...rances1 2 Direction Distance in Direction Distance in Top3 36 Power Entry Right Side 36 Side Opposite Ducts 36 Left Side 24 Duct Panel 0 Bottom4 1 NOTES 1 A 1 clearance must be provided between any co...

Page 6: ...is required Filters must always be used and must be kept clean When filters become dirt laden insufficient air is delivered by the blower the unit efficiency is decreased operating costs are increased...

Page 7: ...uld be field provided for the unit If any of the wire supplied with the unit must be replaced replacement wire must be of the type shown on the wiring diagram Electrical service must be sized properly...

Page 8: ...stages 2 2 2 2 2 2 2 2 2 2 Temperature Rise Range High Fire F 40 70 40 70 40 70 40 70 Temperature Rise Range Low Fire F 25 55 25 55 25 55 25 55 Max Static Pressure w c 0 5 0 5 0 5 0 5 Max Outlet Air T...

Page 9: ...value should be checked with the local gas utility Direct Drive Indoor Fan Data Fan Size Inch 11 x 10 11 x 10 11 x 10 11 x 10 Type Centrifugal Centrifugal Centrifugal Centrifugal Motor HP each 1 2 3...

Page 10: ...imum capacity of pipe in cubic feet of gas per hour based upon a pres sure drop of 0 3 inch water column and 0 6 specific gravity gas Length In Feet Nominal Inches Iron Pipe Size 1 2 3 4 1 1 1 4 10 13...

Page 11: ...nches WC 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 0 SCFM SCFM SCFM SCFM SCFM SCFM SCFM SCFM SCFM SCFM 36065 High Cool A 1371 1354 1303 1257 1209 1148 1084 1008 934 878 B 1293 1246 1206 1152 1098 1028 938...

Page 12: ...1645 1612 1572 1520 1477 1419 1384 1327 B 1506 1468 1441 1404 1358 1302 1259 1203 1159 1101 C 1322 1278 1238 1191 1138 1077 1030 975 920 859 D 1251 1205 1157 1107 1051 987 938 884 824 761 Low Heat A 1...

Page 13: ...0 872 810 High Heat A 2114 2046 1974 1914 1874 1815 1745 1696 1645 1582 B 1982 1930 1887 1844 1806 1752 1697 1643 1604 1545 C 1785 1746 1720 1687 1647 1596 1551 1494 1459 1402 D 1614 1578 1554 1520 14...

Page 14: ...0 1232 1181 1135 C 1410 1361 1307 1255 1204 1155 1100 1044 992 938 D 1323 1270 1213 1156 1104 1052 993 933 880 821 Low Heat A 1594 1553 1507 1462 1415 1369 1321 1274 1223 1178 B 1323 1270 1213 1156 11...

Page 15: ...oved the control de energizes the inducer without post purge and returns to standby If the pressure switch does not close within 5 seconds of inducer ener gizing the control board flashes 3 on the LED...

Page 16: ...trol faults reset after 60 minutes or power interruption Cooling operations are available during a heating lockout High Temperature Limit Switch Any time the high temperature limit switch is open less...

Page 17: ...door blower runs at the HIGH COOL speed based on the COOL jumper setting If a call for HEAT occurs W1 or W1 W2 the circulating blower runs at the heat speed based on the HEAT jumper setting When the t...

Page 18: ...t operate follow the instructions To Turn Off Gas To Appliance and call service technician or gas supplier To Turn Off Gas To Unit 1 Set the thermostat to the OFF position 2 Turn off all electric powe...

Page 19: ...the high fire manifold pressure or the low fire manifold pressure 1 Refer to Figure 10 for location of pressure regulator adjustment cap and adjustment screws on main gas valve 2 Turn gas and electric...

Page 20: ...d on the 1 cubic foot dial to make a revolution with just a 100 000 BTUH furnace running Using this information locate 38 seconds in the first column of Table 17 Read across to the column headed 1 Cub...

Page 21: ...ten as necessary to keep the coil clean If water is used to clean the coil be sure that the power to the unit is shut off prior to cleaning TROUBLESHOOTING FIGURE 12 Measuring External Static Pressure...

Page 22: ...ONAL FAULT CODES NORMAL OPERATION GREEN HEARTBEAT Normal Operation Standby mode AMBER HEARTBEAT Call for furnace heat active RAPID GREEN FLASHES Control in Factory Test mode 4 AMBER FLASHES No G from...

Page 23: ...PLACED WITH TYPE 105 C 600 VOLT WIRE OR EQUIVALENT AND CLEARLY RENUMBERED FOR IDENTIFICATION VERIFY PROPER OPERATION AFTER SERVICING 3 FACTORY WIRED FOR 230 VOLT THREE PHASE SUPPLY POWER FOR 208 VOLT...

Page 24: ...Manifold sets must be at least 700 psig high side and 180 psig low side with 550 psig retard All hoses must have a service pressure rating of 800 psig Leak detectors must be designed to detect HFC re...

Page 25: ...L2 to L3 L1 to L3 Total amperes L1 L2 L3 Compressor amperes L1 L2 L3 Measured voltage R and C outdoor unit control board Electrical Connections Inspection Check all that apply Equipment Data Addition...

Page 26: ...cle Test Operate the unit through continuous fan cycles from the thermostat noting and correcting any problems Operate the unit through cooling cycles from the thermostat noting and correcting any pro...

Reviews: