5285473-UIM-E-1217

Johnson Controls Unitary Products

9

COMPRESSORS

The compressor used in this product is specifically designed to operate
with R-410A refrigerant and cannot be interchanged. Compressors
used in PCG6 models contain two internal bypass ports which enable
the compressor to operate at 67% part load capacity.

Check compressor rotation. If the scroll is misphased, change the
incoming line connection phasing to obtain the proper rotation.

The compressor uses polyolester (POE oil), Mobile 3MA POE. This oil
is extremely hydroscopic, meaning it absorbs water readily. POE oil can
absorb 15 times as much water as other oils designed for HCFC and
CFC refrigerants. If refrigerant circuit is opened, take all necessary pre-
cautions to avoid exposure of the oil to the atmosphere.

POE (polyolester) compressor lubricants are known to cause long term
damage to some synthetic roofing materials.

Procedures which risk oil leakage include, but are not limited to, com-
pressor replacement, repairing refrigerant leaks, replacing refrigerant
components such as filter drier, pressure switch, metering device or
coil.

Units are shipped with compressor mountings which are factory-
adjusted and ready for operation.

GAS HEAT

These two stage gas-fired heat sections have direct spark ignition.

GAS PIPING

Proper sizing of gas piping depends on the cubic feet per hour of gas
flow required, specific gravity of the gas and the length of run. National
Fuel Gas Code Z223.1 or CSA B149.1 should be followed in all cases
unless superseded by local codes or gas company requirements. Refer
to Tables 7 and 8.

The BTU content of the gas may differ with locality. The value should be
checked with the local gas utility.

Direct Drive Indoor Fan Data

Fan Size (Inch)

11 x 10

11 x 10

11 x 10

11 x 10

Type

Centrifugal

Centrifugal

Centrifugal

Centrifugal

Motor HP each

 1/2

3/4

 3/4

 3/4

1

RPM

1200 Max

1200 Max

1200 Max

1200 Max

Frame size

48

48

48

48

Filters

Filter Size

B

B

B

B

Quantity - Size

Field-supplied external filters must be sized so as not to exceed 300 fpm air velocity through dis-
posable filters. For internal filter use, a filter rack kit is available. Consult the instructions supplied 
with that kit for replacement filter sizes. Filter sizes: A=20x20, B=20x30.

Table 6: 

Physical Data (Continued)

MODELS:

PCG6B36

PCG6B42

PCG6B48

PCG6B60

NOMINAL TONNAGE:

3.0

3.5

4.0

5.0

 CAUTION

This system uses R-410A refrigerant which operates at higher pres-
sures than R-22. No other refrigerant may be used in this system.

 CAUTION

Scroll compressors require proper rotation to operate properly. Fail-
ure to check and correct rotation may result in property damage.

NOTICE

Three-phase, scroll compressors operate in only one direction. If the
scroll is drawing low amperage, has similar suction and discharge
pressures, or is producing a high noise level, the scroll is misphased. 

 CAUTION

Do not leave the system open to the atmosphere. Unit damage could
occur due to moisture being absorbed by the POE oil in the system.
This type of oil is highly susceptible to moisture absorption

!

!

!

 CAUTION

Exposure, even if immediately cleaned up, may cause embrittlement
(leading to cracking) to occur in one year or more. When performing
any service that may risk exposure of compressor oil to the roof, take
precautions to protect roofing.

 CAUTION

Do not loosen compressor mounting bolts.

NOTICE

There may be a local gas utility requirement specifying a minimum
diameter for gas piping. All units require a 1/2 inch pipe connection at
the gas valve.

!

!

Summary of Contents for PCG6B42

Page 1: ...Feet Per Hour 20 SECTION I GENERAL INFORMATION These are electric cooling gas heating units designed for outdoor instal lation Only gas piping electric power and duct connections are required for ins...

Page 2: ...ation in this manual is not followed exactly a fire or explosion may result causing property damage personal injury or loss of life Do not store or use gasoline or other flammable vapors and liquids i...

Page 3: ...stallation only 2 Condenser coils must have an unlimited supply of air Where a choice of location is possible position the unit on either north or east side of building 3 Suitable for mounting on roof...

Page 4: ...the spreader bars exceed the largest dimension across the unit Units may be moved or lifted with a forklift Slotted openings in the base rails are provided for this purpose WARNING Do not permit over...

Page 5: ...rances1 2 Direction Distance in Direction Distance in Top3 36 Power Entry Right Side 36 Side Opposite Ducts 36 Left Side 24 Duct Panel 0 Bottom4 1 NOTES 1 A 1 clearance must be provided between any co...

Page 6: ...is required Filters must always be used and must be kept clean When filters become dirt laden insufficient air is delivered by the blower the unit efficiency is decreased operating costs are increased...

Page 7: ...uld be field provided for the unit If any of the wire supplied with the unit must be replaced replacement wire must be of the type shown on the wiring diagram Electrical service must be sized properly...

Page 8: ...stages 2 2 2 2 2 2 2 2 2 2 Temperature Rise Range High Fire F 40 70 40 70 40 70 40 70 Temperature Rise Range Low Fire F 25 55 25 55 25 55 25 55 Max Static Pressure w c 0 5 0 5 0 5 0 5 Max Outlet Air T...

Page 9: ...value should be checked with the local gas utility Direct Drive Indoor Fan Data Fan Size Inch 11 x 10 11 x 10 11 x 10 11 x 10 Type Centrifugal Centrifugal Centrifugal Centrifugal Motor HP each 1 2 3...

Page 10: ...imum capacity of pipe in cubic feet of gas per hour based upon a pres sure drop of 0 3 inch water column and 0 6 specific gravity gas Length In Feet Nominal Inches Iron Pipe Size 1 2 3 4 1 1 1 4 10 13...

Page 11: ...nches WC 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 0 SCFM SCFM SCFM SCFM SCFM SCFM SCFM SCFM SCFM SCFM 36065 High Cool A 1371 1354 1303 1257 1209 1148 1084 1008 934 878 B 1293 1246 1206 1152 1098 1028 938...

Page 12: ...1645 1612 1572 1520 1477 1419 1384 1327 B 1506 1468 1441 1404 1358 1302 1259 1203 1159 1101 C 1322 1278 1238 1191 1138 1077 1030 975 920 859 D 1251 1205 1157 1107 1051 987 938 884 824 761 Low Heat A 1...

Page 13: ...0 872 810 High Heat A 2114 2046 1974 1914 1874 1815 1745 1696 1645 1582 B 1982 1930 1887 1844 1806 1752 1697 1643 1604 1545 C 1785 1746 1720 1687 1647 1596 1551 1494 1459 1402 D 1614 1578 1554 1520 14...

Page 14: ...0 1232 1181 1135 C 1410 1361 1307 1255 1204 1155 1100 1044 992 938 D 1323 1270 1213 1156 1104 1052 993 933 880 821 Low Heat A 1594 1553 1507 1462 1415 1369 1321 1274 1223 1178 B 1323 1270 1213 1156 11...

Page 15: ...oved the control de energizes the inducer without post purge and returns to standby If the pressure switch does not close within 5 seconds of inducer ener gizing the control board flashes 3 on the LED...

Page 16: ...trol faults reset after 60 minutes or power interruption Cooling operations are available during a heating lockout High Temperature Limit Switch Any time the high temperature limit switch is open less...

Page 17: ...door blower runs at the HIGH COOL speed based on the COOL jumper setting If a call for HEAT occurs W1 or W1 W2 the circulating blower runs at the heat speed based on the HEAT jumper setting When the t...

Page 18: ...t operate follow the instructions To Turn Off Gas To Appliance and call service technician or gas supplier To Turn Off Gas To Unit 1 Set the thermostat to the OFF position 2 Turn off all electric powe...

Page 19: ...the high fire manifold pressure or the low fire manifold pressure 1 Refer to Figure 10 for location of pressure regulator adjustment cap and adjustment screws on main gas valve 2 Turn gas and electric...

Page 20: ...d on the 1 cubic foot dial to make a revolution with just a 100 000 BTUH furnace running Using this information locate 38 seconds in the first column of Table 17 Read across to the column headed 1 Cub...

Page 21: ...ten as necessary to keep the coil clean If water is used to clean the coil be sure that the power to the unit is shut off prior to cleaning TROUBLESHOOTING FIGURE 12 Measuring External Static Pressure...

Page 22: ...ONAL FAULT CODES NORMAL OPERATION GREEN HEARTBEAT Normal Operation Standby mode AMBER HEARTBEAT Call for furnace heat active RAPID GREEN FLASHES Control in Factory Test mode 4 AMBER FLASHES No G from...

Page 23: ...PLACED WITH TYPE 105 C 600 VOLT WIRE OR EQUIVALENT AND CLEARLY RENUMBERED FOR IDENTIFICATION VERIFY PROPER OPERATION AFTER SERVICING 3 FACTORY WIRED FOR 230 VOLT THREE PHASE SUPPLY POWER FOR 208 VOLT...

Page 24: ...Manifold sets must be at least 700 psig high side and 180 psig low side with 550 psig retard All hoses must have a service pressure rating of 800 psig Leak detectors must be designed to detect HFC re...

Page 25: ...L2 to L3 L1 to L3 Total amperes L1 L2 L3 Compressor amperes L1 L2 L3 Measured voltage R and C outdoor unit control board Electrical Connections Inspection Check all that apply Equipment Data Addition...

Page 26: ...cle Test Operate the unit through continuous fan cycles from the thermostat noting and correcting any problems Operate the unit through cooling cycles from the thermostat noting and correcting any pro...