background image

D

L

L

H

NOTE

Unit size

g/m

07

15

09

15

12

15

18

40

25

40

35

40

40

40

45

60

55

60

65

60

Insulation

Heat pump

Liquid

Cooling

Cooling

(suction)

Heat pump

(discharge)

Heat

pump

Liquid

GAS

Cooling

(suction)

Cooling

Low pressure High pressure

Manifold

Gas valve

Liquid valve

Pressure tap

Outdoor unit

Gas line Indoor unit

Liquid line

R22 / R407C

Where  the  difference  in  elevation  between  the  indoor  unit

and  the  outdoor  unit  is  greater  than  5  meters,  install  an

oil trap every 5 meters.
The  suction  line  must  have  a  2%  gradient  up  to  the

compressor on horizontal sections.
Where  piping  lengths  are  unusually  long  and  include  a

large  number  of  oil  traps,  it  may  be  necessary  to  adjust

the compressor oil charge.

Refrigerant charge to be added per extra meter

of piping length when more than 7.5 m.

Refrigerant piping connections

(FLARE connections)

To  avoid  alteration  of  unit  capacities,  check  that  piping

lengths  and  changes  in  elevation  are  kept  to  a  strict

minimum.
Before connecting the refrigerant lines, follow the procedures

below (if pre-charged connection lines are not supplied):
– Select  copper  pipe  diameters  according  to  the  size  of

unit to be installed.

– Install  the  refrigeration  lines,  checking  that  no  foreign

bodies get inside the piping.

– Install the flare connectors and flare the ends of the pipes.

Heat pump

(discharge)

– Evacuate the piping. This operation, which should last at

least 15 minutes or even longer if there are large piping

lengths and changes in elevation, should be followed by a

leak test.

– To this effect, when the piping has been evacuated, close

the pressure gauge tap, note the value on the gauge, then

wait for 15 minutes. If the needle moves, there is a leak in

the  system.  Make  the  necessary  adjustments  or  repairs

and repeat this procedure until the needle no longer moves.

– Open the service valves and top up the refrigerant charge

if necessary.

Minimum thickness 6 mm

REFRIGERANT CIRCUIT CONNECTIONS

PIPE LENGTHS

 Maximum piping lengths

MOC-MOH

D (m)

L (m)

H (m)

07

12
15
10

09

12
15
10

12

15
18
12

18

15
18
12

25

22
25
20

35

22
25
20

40

26
30
24

45

26
30
24

55

26
30
24

65

26
30
24

Make piping runs as short as possible and avoid all unnecessary

changes in direction or elevation.
To prevent heat loss, the two lines must be insulated

separately.
Use  an  appropriate  bending  tool  to  form  curves  and  avoid

flattening the refrigerant tubes.
Fix piping with pipe clamps and check that any eventual pipe

vibrations cannot be transmitted to the building structure.
Use refrigeration quality piping only with an operating pressure

rating of at least 30 bars. Never use ordinary <<plumbing>>

quality piping : you MUST use special deoxidized, dehydrated,

refrigerant quality copper piping.

Summary of Contents for MOC09

Page 1: ...line protection The unit must be grounded Installation and maintenance of this air conditioning system should only be carried out by trained and qualified personnel Regular maintenance operations suc...

Page 2: ...1 590 820 280 56 58 5 8 3 8 1 2 55 12 34 61 1650 1600 1 696 850 285 65 67 5 8 3 8 25 3 3 53 6 77 48 1 35 5 8 3 8 3 5 71 9 10 53 3 6 79 11 72 62 3000 3000 1 1142 850 285 87 88 3 4 3 8 45 3800 3800 1 11...

Page 3: ...00 800 200 400 100 300 800 200 400 100 300 800 40 45 55 65 07 12 400 200 100 210 600 To prevent ice build up beneath the unit during winter operation it may be necessary to increase the dimension of C...

Page 4: ...sunlight especially if it is a cooling only model since direct sunlight will increase condensing pressure and reduce unit efficiency Install units facing North whenever possible In particularly windy...

Page 5: ...all the flare connectors and flare the ends of the pipes Heat pump discharge Evacuate the piping This operation which should last at least 15 minutes or even longer if there are large piping lengths a...

Page 6: ...860 0 856 0 852 0 849 0 845 0 842 0 838 0 835 0 831 0 828 0 824 Pipe Length L H 0 m H 3 m H 5 m H 10 m H 20 m H 25 m H 30 m Pipe Length L H 0 m H 3 m H 5 m H 10 m H 20 m H 25 m H 30 m 0 974 0 973 0 97...

Page 7: ...olating valves have been fully opened That the refrigerant charge has been topped up if necessary Start the units and check operation in both the cooling and the heating mode Unit base plate Compresso...

Page 8: ...e Flare with Schrader COOLING CIRCUIT PRESSURE TAP LOCATION PRESSURE TAP Outdoor unit C a u t i o n Risk of electric shock A fan speed controller is provided as standard on full featured condensing un...

Page 9: ...me characteristic sounds that differentiate if from those normally associated with reciprocating type compressors These sounds described below are characteristics and do not affect reliability or indi...

Page 10: ...y check that motors are operating properly Check wire gauges etc Replace it Remedy Cause Symptoms Remedy Ice build up indoor coil Faulty installation Compressor noisy Thermostat Safety device Excessiv...

Page 11: ...ting valve with pressure tap 7 HP pressure switch Interseason start up safety 8 4 way cycle changeover valve 9 Anti slugging receiver 10 Restrictor Unit Capacity Total cooling capacity can be determin...

Page 12: ...d gas isolation are secured in the OFF position The supply cables and gas pipework may then be disconnected and removed For points of connection refer to unit installation instructions 2 Remove all re...

Reviews: