PHASE ROTATION

Scroll  compressors  designed  to  operate  only  in  one  direction.  If  opposite  direction  is  required,  swamp  any  two

phases at the main terminal block. Reciprocating compressors are able to run in either direction without any loss of

performance or reliability.

Special Note for units fitted with Scroll Compressors

Phase sequencing: the Scroll compressor is designed to operate with motor running in only direction. Mis-wiring of

phase power (phase reversal) will cause the compressor to operate in the wrong direction. The Scroll compressor

will run without damaging itself if phasing is improper, but it will not pump refrigerant and will draw minimal current.

In such a case, the internal winding line break will ultimately shut off the compressor. Depending upon the conditions

it could take up to 30 minutes to trip the internal winding protection. The compressor will be noisy, vibrate excessively

and the oil sump will become warm to hot when running backwards.
Because of the scroll compressor design and its capability to accommodate liquid slugging, both oil and refrigerant,

without causing compressor damage, there are some characteristic sounds that differentiate if from those normally

associated with reciprocating type compressors.

These sounds described below, are characteristics and do not affect reliability or indicate that the compressor is

defective.

Cautions

1. Three phase scrolls will only pump when running in right direction.

2. Verify rotation on initial start up by checking pressure.

3. To correct improper motor rotation, switch any two supply lines.

At Start-up:

Under conditions of low refrigerant flows (low suction pressures) such as start-up, a rating sound may emanate from

the compressor.

This is more like to be heard under conditions such as low ambient starts where it takes time to build sufficient head

pressure to allow the thermal expansion valve to flow sufficient refrigerant to increase the suction pressure. This

sound should diminish and disappear as the suction pressure increases.

At Shutdown:

The gas within the scroll expands and causes momentary reverse rotation until the discharge check valve seats.

This results in a “flutter” type noise.

Refrigerant Flooding:

If the compressor experience severe liquid slugging during the operation the compressor will make a loud rattling

sound.

This is normal because of the separation of the scrolls that allow the liquid refrigerant to pass through the compressor

without damaging it.

Summary of Contents for MOC09

Page 1: ...line protection The unit must be grounded Installation and maintenance of this air conditioning system should only be carried out by trained and qualified personnel Regular maintenance operations suc...

Page 2: ...1 590 820 280 56 58 5 8 3 8 1 2 55 12 34 61 1650 1600 1 696 850 285 65 67 5 8 3 8 25 3 3 53 6 77 48 1 35 5 8 3 8 3 5 71 9 10 53 3 6 79 11 72 62 3000 3000 1 1142 850 285 87 88 3 4 3 8 45 3800 3800 1 11...

Page 3: ...00 800 200 400 100 300 800 200 400 100 300 800 40 45 55 65 07 12 400 200 100 210 600 To prevent ice build up beneath the unit during winter operation it may be necessary to increase the dimension of C...

Page 4: ...sunlight especially if it is a cooling only model since direct sunlight will increase condensing pressure and reduce unit efficiency Install units facing North whenever possible In particularly windy...

Page 5: ...all the flare connectors and flare the ends of the pipes Heat pump discharge Evacuate the piping This operation which should last at least 15 minutes or even longer if there are large piping lengths a...

Page 6: ...860 0 856 0 852 0 849 0 845 0 842 0 838 0 835 0 831 0 828 0 824 Pipe Length L H 0 m H 3 m H 5 m H 10 m H 20 m H 25 m H 30 m Pipe Length L H 0 m H 3 m H 5 m H 10 m H 20 m H 25 m H 30 m 0 974 0 973 0 97...

Page 7: ...olating valves have been fully opened That the refrigerant charge has been topped up if necessary Start the units and check operation in both the cooling and the heating mode Unit base plate Compresso...

Page 8: ...e Flare with Schrader COOLING CIRCUIT PRESSURE TAP LOCATION PRESSURE TAP Outdoor unit C a u t i o n Risk of electric shock A fan speed controller is provided as standard on full featured condensing un...

Page 9: ...me characteristic sounds that differentiate if from those normally associated with reciprocating type compressors These sounds described below are characteristics and do not affect reliability or indi...

Page 10: ...y check that motors are operating properly Check wire gauges etc Replace it Remedy Cause Symptoms Remedy Ice build up indoor coil Faulty installation Compressor noisy Thermostat Safety device Excessiv...

Page 11: ...ting valve with pressure tap 7 HP pressure switch Interseason start up safety 8 4 way cycle changeover valve 9 Anti slugging receiver 10 Restrictor Unit Capacity Total cooling capacity can be determin...

Page 12: ...d gas isolation are secured in the OFF position The supply cables and gas pipework may then be disconnected and removed For points of connection refer to unit installation instructions 2 Remove all re...

Reviews: