background image

INSTALLATION

OK

Unit installation details:

– unit mounting

– refrigerant piping connections

Whatever type of installation is chosen for

the unit, the following installation rules must

be observed:

– The location selected for unit installation must be capable

of withstanding the weight of the unit in its full operating

configuration.

– Select  a  location  where  neither  dust  nor  other  foreign

bodies will clog the unit coil.

– If the outdoor unit is installed on the ground, make sure that

the location is not liable to flooding.

– Make  sure  that  you  know  and  apply  any  and  all  local

rules  and  regulations  concerning  the  installation  of  air

conditioning equipment.

– Use  the  vibration  isolators  provided  to  prevent  vibration

transmission and resulting unnecessary noise.

– Do not install the equipment in explosive  environments.

– Make  sure  that  the  surrounding  atmosphere  does  not

contain  noxious  or  dangerous  substances  such  as  oil

vapours or sulphur.

– If  the  air  conditioner  is  installed  in  a  polluted  area,

increase the frequency of maintenance operations.

– Avoid installing the unit where it will be in direct sunlight,

especially if it is a cooling only model since direct sunlight

will increase condensing pressure and reduce unit efficiency.

Install units facing North whenever possible.

– In particularly windy places, the unit should be installed so

that the prevailing wind does not interfere with air discharge

from the unit (configuration with the wind blowing onto the

side of the unit).

– MOH heat pump unit : install the unit at least 10 cm above

ground  level  to  facilitate  drainage  of  defrost  water  and

prevent  accumulation  of  ice.  In  effect,  defrost  water  can

cause accumulation of ice under the unit during subfreezing

outdoor temperatures.

– condensate water drainage connections

– unit wiring connection

– Wherever possible, install the unit where it will be protected

from rain, snow and runoff from overhanging structures.

– In areas with heavy snowfall it is best to install the unit on

wall supports.

– If condensates are not to be drained, do not install the elbow

supplied with the unit.

– Make sure that the unit is installed level so that condensate

will drain off correctly.

– In some regions. It is necessary to heat the bottom of the

condensate  drainage  pan  and  the  condensate  drainage

piping to avoid ice formation, and resulting ice build-up in

the fan compartment (heater strip must be at least 25 W/m).

Summary of Contents for MOC09

Page 1: ...line protection The unit must be grounded Installation and maintenance of this air conditioning system should only be carried out by trained and qualified personnel Regular maintenance operations suc...

Page 2: ...1 590 820 280 56 58 5 8 3 8 1 2 55 12 34 61 1650 1600 1 696 850 285 65 67 5 8 3 8 25 3 3 53 6 77 48 1 35 5 8 3 8 3 5 71 9 10 53 3 6 79 11 72 62 3000 3000 1 1142 850 285 87 88 3 4 3 8 45 3800 3800 1 11...

Page 3: ...00 800 200 400 100 300 800 200 400 100 300 800 40 45 55 65 07 12 400 200 100 210 600 To prevent ice build up beneath the unit during winter operation it may be necessary to increase the dimension of C...

Page 4: ...sunlight especially if it is a cooling only model since direct sunlight will increase condensing pressure and reduce unit efficiency Install units facing North whenever possible In particularly windy...

Page 5: ...all the flare connectors and flare the ends of the pipes Heat pump discharge Evacuate the piping This operation which should last at least 15 minutes or even longer if there are large piping lengths a...

Page 6: ...860 0 856 0 852 0 849 0 845 0 842 0 838 0 835 0 831 0 828 0 824 Pipe Length L H 0 m H 3 m H 5 m H 10 m H 20 m H 25 m H 30 m Pipe Length L H 0 m H 3 m H 5 m H 10 m H 20 m H 25 m H 30 m 0 974 0 973 0 97...

Page 7: ...olating valves have been fully opened That the refrigerant charge has been topped up if necessary Start the units and check operation in both the cooling and the heating mode Unit base plate Compresso...

Page 8: ...e Flare with Schrader COOLING CIRCUIT PRESSURE TAP LOCATION PRESSURE TAP Outdoor unit C a u t i o n Risk of electric shock A fan speed controller is provided as standard on full featured condensing un...

Page 9: ...me characteristic sounds that differentiate if from those normally associated with reciprocating type compressors These sounds described below are characteristics and do not affect reliability or indi...

Page 10: ...y check that motors are operating properly Check wire gauges etc Replace it Remedy Cause Symptoms Remedy Ice build up indoor coil Faulty installation Compressor noisy Thermostat Safety device Excessiv...

Page 11: ...ting valve with pressure tap 7 HP pressure switch Interseason start up safety 8 4 way cycle changeover valve 9 Anti slugging receiver 10 Restrictor Unit Capacity Total cooling capacity can be determin...

Page 12: ...d gas isolation are secured in the OFF position The supply cables and gas pipework may then be disconnected and removed For points of connection refer to unit installation instructions 2 Remove all re...

Reviews: