background image

ELECTRICAL CONNECTIONS

N

1

2

L

N

1

2

N

1

3

2

L

N

1

3

2

N

1

2

L1 L  2 L  3

N

1

2

N

1

2

3

N

1

2

3

L1 L  2 L  3

MOC-MOH

Power supply

mm

2

Ph

Interconnection

(Indoor/Outdoor)

Cooling mm

2

Heating mm

2

Fuse (slow-blow)

A

07 09 12 18

25

35

40 45 55 65

1 1 1

1

3

1 3 1 3

1 1 3 3 3

3x2.5

3x4

5x2.5

5x4

3x2.5

4x2.5

10

32 16

16 10 25 10

35 40 16 20 25

Power supply

220-240V/1Ph/50Hz

208-230V/1Ph/60Hz

MOC 07 - 35 - Cooling only

Indoor unit

Outdoor unit

MOC 25 - 65 - Cooling only

Indoor unit

Outdoor unit

Power supply

380-415V/3Ph/50Hz

460V/3Ph/60Hz

Wire sizes

Terminals N and 1 (see diagrams above) correspond to power

supply to the indoor unit coming from the outdoor

unit.

Compressor power supply is established by terminal 2.

Power supply to the 4-way valve is established by terminal 3.

For further details on wiring of these units, see the diagrams

pasted inside each unit.

MOH 07 - 35 - Heat pump

Indoor unit

Outdoor unit

Outdoor unit

Power supply

220-240V/1Ph/50Hz

208-230V/1Ph/60Hz

MOH 25 - 65 - Heat pump

Indoor unit

Power supply

380-415V/3Ph/50Hz

460V/3Ph/60Hz

START-UP

Before starting the air conditioner, please check the following points:

- That the unit is installed according to instructions given in this

documentation.

- That the unit is correctly wired up.

- That flare connection nuts are tightened.

- That the unit has been evacuated and leak-tested.

- That isolating valves have been fully opened.

- That the refrigerant charge has been topped-up if necessary.

Start the units and check operation in both the cooling and the heating mode.

Unit base plate

Compressor

Diagram n°1

MOC 18 - MOH 18

Coil

DEFROST

Defrost is handled via a defrost management electronic control

board  (model  with  two  potential  meters  and  6  dip

switches, see diagram n°2). This enables defrost cycles to be

initiated when the temperature reaches -5°C at the condenser

coil  bend. The  end  of  defrost  cycle  set  point  is  +10°C. The

duration  of  the  defrost  cycle  varies  depending  on  operating

conditions but it is limited to a maximum of 10 minutes. Time

delay between successive defrost cycles is 30 minutes.

The defrost cycle can be forced into action by shunting terminals

DEF on the defrost control board in the outdoor unit.

The  time  delay  between  successive  defrost  cycles  and  the

maximum  duration  of  each  cycle  are  adjustable.  If  these

need to modified, please contact YORK first for technical advice.

If your unit does not defrost correctly, please check the follow

points carefully:

- Is the refrigerant charge correct ?

- Is the sensor in the right location on the outdoor coil ?

- Low and high pressure switch settings on units :

MOC-MOH 35-45-55 LP = 1.5 Bars HP = 28 Bars

1

“Dip  Switches”  for  adjusting  time  delay  between  defrost

cycles and maximum defrost cycle duration.

2

Female sensor connection

3

Shunt these terminals to stimulate a defrost cycle.

1    2    3   4    5   6

DEF

ON

2

1

3

Diagram n°2 - Adjustable Defrost Control Board

Transformer

Summary of Contents for MOC09

Page 1: ...line protection The unit must be grounded Installation and maintenance of this air conditioning system should only be carried out by trained and qualified personnel Regular maintenance operations suc...

Page 2: ...1 590 820 280 56 58 5 8 3 8 1 2 55 12 34 61 1650 1600 1 696 850 285 65 67 5 8 3 8 25 3 3 53 6 77 48 1 35 5 8 3 8 3 5 71 9 10 53 3 6 79 11 72 62 3000 3000 1 1142 850 285 87 88 3 4 3 8 45 3800 3800 1 11...

Page 3: ...00 800 200 400 100 300 800 200 400 100 300 800 40 45 55 65 07 12 400 200 100 210 600 To prevent ice build up beneath the unit during winter operation it may be necessary to increase the dimension of C...

Page 4: ...sunlight especially if it is a cooling only model since direct sunlight will increase condensing pressure and reduce unit efficiency Install units facing North whenever possible In particularly windy...

Page 5: ...all the flare connectors and flare the ends of the pipes Heat pump discharge Evacuate the piping This operation which should last at least 15 minutes or even longer if there are large piping lengths a...

Page 6: ...860 0 856 0 852 0 849 0 845 0 842 0 838 0 835 0 831 0 828 0 824 Pipe Length L H 0 m H 3 m H 5 m H 10 m H 20 m H 25 m H 30 m Pipe Length L H 0 m H 3 m H 5 m H 10 m H 20 m H 25 m H 30 m 0 974 0 973 0 97...

Page 7: ...olating valves have been fully opened That the refrigerant charge has been topped up if necessary Start the units and check operation in both the cooling and the heating mode Unit base plate Compresso...

Page 8: ...e Flare with Schrader COOLING CIRCUIT PRESSURE TAP LOCATION PRESSURE TAP Outdoor unit C a u t i o n Risk of electric shock A fan speed controller is provided as standard on full featured condensing un...

Page 9: ...me characteristic sounds that differentiate if from those normally associated with reciprocating type compressors These sounds described below are characteristics and do not affect reliability or indi...

Page 10: ...y check that motors are operating properly Check wire gauges etc Replace it Remedy Cause Symptoms Remedy Ice build up indoor coil Faulty installation Compressor noisy Thermostat Safety device Excessiv...

Page 11: ...ting valve with pressure tap 7 HP pressure switch Interseason start up safety 8 4 way cycle changeover valve 9 Anti slugging receiver 10 Restrictor Unit Capacity Total cooling capacity can be determin...

Page 12: ...d gas isolation are secured in the OFF position The supply cables and gas pipework may then be disconnected and removed For points of connection refer to unit installation instructions 2 Remove all re...

Reviews: