5169034-UIM-B-0216
10
Johnson Controls Unitary Products
ME16C
6HK(0,1)6500206
10
19.3
20.5
20
25
6HK(0,1)6500506
20
30.1
32.4
35
35
6HK(0,1)6500806
32
43.4
47.1
45
50
6HK(0,1)6501006
40
51.8
56.3
60
60
6HK(1,2)6501306
52
65.0
71.0
70
80
6HK(1,2)6501506
60
73.4
80.2
80
90
6HK(1,2)6501806
72
86.6
94.9
90
100
6HK(1,2)6502006
80
95.0
104.2
100
110
ME20D
6HK(0,1)6500206
10
19.3
20.5
20
25
6HK(0,1)6500506
20
30.1
32.4
35
35
6HK(0,1)6500806
32
43.4
47.1
45
50
6HK(0,1)6501006
40
51.8
56.3
60
60
6HK(1,2)6501306
52
65.0
71.0
70
80
6HK(1,2)6501506
60
73.4
80.2
80
90
6HK(1,2)6501806
72
86.6
94.9
90
100
6HK(1,2)6502006
80
95.0
104.2
100
110
6HK(1,2)6502506
100
116.7
128.1
125
150
1. (0,1) - maybe 0 (no service disconnect) or 1 (with service disconnect).
2. (1,2) maybe 1 (with service disconnect, no breaker jumper bar) or 2 (with service disconnect & breaker jumper bar).
3. MOP = Maximum Overcurrent Protection device; must be HACR type service disconnect or time delay fuse. Refer to the latest edition of the
National Electric Code or in Canada the Canadian electrical Code and local codes to determine correct wire sizing.
TABLE 7:
Electrical Data For Single Source Power Supply: 208/230-1-60 (Continued)
Air Handler Models
Heater
Models
1,2
Heater
Amps @240V
Field Wiring
Min. Circuit Ampacity
MOP.
3
208V
230V
208V
230V
TABLE 8:
Electrical Data For Multi-source Power Supply: 208/230-1-60
Air Handler
Models
Heater
Models
Heater
Amps
@240V
Min. Circuit Ampacity
MOP.
1
208V
230V
208V
230V
Circuit
Circuit
1st
3
2nd
3rd
1st
3
2nd
3rd
1st
3
2nd
3rd
1st
3
2nd
3rd
ME08B
6HK16501306
52
22.9
37.6
-
24.9
41.5
-
25
40
-
25
45
-
ME12B
6HK16501306
52
24.8
37.6
-
26.8
41.5
-
25
40
-
30
45
-
6HK16501506
60
27.7
43.3
-
30.0
47.9
-
30
45
-
30
50
-
6HK16501806
72
45.0
39.0
-
49.1
43.1
-
45
40
-
50
45
-
6HK16502006
80
49.3
43.3
-
53.9
47.9
-
50
45
-
60
50
-
ME14D
6HK16501306
52
24.8
37.6
-
26.8
41.5
-
30
40
-
30
45
-
6HK16501506
60
27.7
43.3
-
30.0
47.9
-
30
45
-
30
50
-
6HK16501806
72
45.0
39.0
-
49.1
43.1
-
45
40
-
50
45
-
ME16C
6HK16501306
52
27.3
37.6
-
29.3
41.5
-
30
40
-
30
45
-
6HK16501506
60
30.2
43.3
-
32.5
47.9
-
35
45
-
35
50
-
6HK16501806
72
47.5
39.0
-
51.6
43.1
-
50
40
-
60
45
-
6HK16502006
80
51.8
43.3
-
56.4
47.9
-
60
45
-
60
50
-
ME20D
6HK16501306
52
27.3
37.6
-
29.3
41.5
-
30
40
-
30
45
-
6HK16501506
60
30.2
43.3
-
32.5
47.9
-
35
45
-
35
50
-
6HK16501806
72
47.5
39.0
-
51.6
43.1
-
50
40
-
60
45
-
6HK16502006
80
51.8
43.3
-
56.4
47.9
-
60
45
-
60
50
-
6HK16502506
100
51.8
43.3
21.7
56.4
47.9
24.0
60
45
25
60
50
25
1. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse. The 1st circuit includes blower motor amps.
Refer to the latest edition of the National Electric Code or in Canada the Canadian electrical Code and local codes to determine correct wire sizing.