5169034-UIM-B-0216
Johnson Controls Unitary Products
13
ME16C
CM36C
#5 HI
1776
1735
1700
1657
1617
1577
1529
#4 MED-HI
1701
1663
1621
1583
1538
1497
1453
#3 MED
1522
1475
1442
1394
1349
1301
1245
#2 MED-LO
1297
1250
1203
1151
1101
1050
957
#1 LO
1112
1052
1002
951
854
816
756
CM42C
#5 HI
1754
1719
1678
1644
1599
1562
1513
#4 MED-HI
1676
1637
1599
1562
1517
1476
1423
#3 MED
1495
1454
1411
1371
1328
1280
1233
#2 MED-LO
1286
1235
1198
1143
1097
1036
992
#1 LO
1119
1055
1006
948
900
804
752
CM48C
#5 HI
1769
1727
1689
1650
1608
1568
1525
#4 MED-HI
1692
1648
1605
1568
1525
1485
1440
#3 MED
1554
1505
1461
1420
1373
1326
1273
#2 MED-LO
1308
1256
1213
1164
1088
1007
941
#1 LO
1116
1057
1007
955
839
792
741
CM60C
#5 HI
1794
1757
1720
1686
1639
1589
1545
#4 MED-HI
1700
1664
1624
1582
1543
1496
1443
#3 MED
1530
1484
1444
1402
1356
1314
1257
#2 MED-LO
1305
1257
1217
1162
1115
1060
993
#1 LO
1124
1060
1008
954
889
827
755
ME20D
CM36D
#5 HI
2061
2021
1979
1938
1904
1865
1829
#4 MED-HI
1998
1949
1914
1879
1835
1797
1756
#3 MED
1769
1711
1677
1643
1603
1570
1530
#2 MED-LO
1557
1508
1469
1439
1398
1355
1323
#1 LO
1340
1291
1252
1216
1170
1132
1058
CM42D
#5 HI
2032
1996
1959
1913
1890
1849
1820
#4 MED-HI
1974
1938
1892
1855
1824
1785
1754
#3 MED
1752
1706
1680
1633
1591
1546
1511
#2 MED-LO
1545
1505
1468
1432
1393
1351
1307
#1 LO
1340
1296
1260
1219
1169
1118
1055
CM48D
#5 HI
2062
2024
1993
1952
1910
1868
1836
#4 MED-HI
2006
1958
1932
1890
1850
1815
1770
#3 MED
1785
1741
1698
1646
1610
1582
1538
#2 MED-LO
1564
1521
1477
1443
1398
1362
1323
#1 LO
1350
1305
1257
1226
1181
1112
1029
CM60D
#5 HI
1998
1959
1923
1888
1862
1826
1786
#4 MED-HI
1933
1887
1855
1811
1791
1757
1719
#3 MED
1703
1670
1633
1592
1567
1531
1485
#2 MED-LO
1522
1474
1447
1403
1370
1328
1281
#1 LO
1306
1260
1223
1190
1131
1078
1012
CM64D
#5 HI
1940
1897
1868
1832
1806
1770
1728
#4 MED-HI
1883
1860
1829
1789
1761
1728
1688
#3 MED
1686
1648
1619
1584
1537
1508
1466
#2 MED-LO
1490
1446
1415
1385
1346
1298
1236
#1 LO
1279
1248
1206
1167
1113
1062
972
1. Air handler units have been tested to UL 1995 / CSA 22.2 standards up to 0.50" w.c. external static pressure.
Dry coil conditions only, tested without filters.
For optimal performance, external static pressures of 0.2" to 0.5" are recommended. Applications above 0.5" are not recommended.
Airflow data shown is from testing performed at 230V. AE units use a standard ECM constant torque motor, and there is minimal variation of airflow at other distribution
voltage values. The above data can be used for airflow at other distribution voltages.
TABLE 11:
Air Flow Data (CFM)
1
Models
CM Models
Blower
Motor Speed
External Static Pressure (in. wc.)
0.10
0.20
0.30
0.40
0.50
0.60
0.70