Safety and Control Device Setting
•
Compressor Protection
High Pressure Switch: This switch cuts out the
operation of the compressor when the
discharge pressure exceeds the setting.
•
Fan Motor Protection
When the thermistor temperature is reached to
the setting, motor output is decreased.
The other way, when the temperature becomes
lower, limitation is cancelled.
For Compressor
Pressure Switch
Automatic Reset, Non-Adjustable
High
Cut-Out
MPa
-0.05
-0.05
-0.05
-0.15
-0.15
-0.15
Cut-In
MPa
3.2+0.15
3.2+0.15
3.2+0.15
Fuse
A
40
40
40
A
40
40
40
A
60
60
60
CCP Timer
Non-Adjustable
Setting Time
min.
3
3
3
For Condenser Fan Motor
Automatic Reset, Non-Adjustable
Internal Thermostat
(each one for each motor)
DC
Cut-Out
o
C
120+5
120+5
120+5
AC
Cut-Out
o
C
135+5
135+5
135+5
Cut-In
o
C
110 60
For Control Circuit
Fuse Capacity on PCB1, 5
A
5
5
5
Fuse Capacity on PCB3
A
10
10
10
4.15
4.15
4.15
~
110 60
~
110 60
~
120
100
080