9
(4) Fix the outdoor unit firmly so that declining,
making noise, and falling down by strong
wind or earthquake is avoided.
75
110
1173
Fixing Plate
(Field-Supplied)
Both sides on the unit fixing
can be possible.
When vibration measures
are necessary,
add vibration proof rubber.
(Field-Supplied)
Fig. 4.10 Frame and Base Installation
Fig. 4.9 Additional Fixing Arrangement
(5) When installing the unit on a roof or a
veranda, drain water sometimes turns to
ice in a cold morning. Therefore, avoid
draining in an area where people often use
because it is slippery.
(6) In case of the drain piping is necessary for
the outdoor unit, use the drain-kit
(DBS-26 or DBS-26L: Optional Parts).
Base Width of Outdoor Unit
100mm
Frame Width 60mm
(Field-Supplied)
Frame
Incorrect
Outdoor Unit
is Unstable.
Metal Plate
100mm or more
Metal Plate
Correct
Frame
Base Width of Outdoor Unit
100mm
Outdoor Unit
is Stable.
Recommended Metal Plate Size (Field-Supplied)
Material: Hot-Rolled Mild Steel Plate (SPHC)
Plate Thickness: 4.5T
120
420
(560)
70
70
20
4-C10
2-Long Hole
14
60
R
(7) The whole of the base of the outdoor unit
should be installed on a foundation. When
using vibration-proof mat, it should also be
positioned the same way.
When installing the outdoor unit on a field-
supplied frame, use metal plates to adjust
the frame width for stable installation as
shown in Fig. 4.10.
360
165
396
68
127
66
73
Drain Hole
(3-
φ
24)
Air Inlet
Drain Hole (2-
φ
26)
(Drain Boss Attaching Position)
Summary of Contents for JDOH Series