7
(2) Obstacles on Discharge Side
(a) Upper Side is Open.
(3) Obstacles in Right and Left
(a) Upper Side is Open.
(b) Obstacles in Above
(mm)
Min. 500
Min. 50
Single Installation
L
Min. 500
Min. 100
L
(mm)
Single Installation
Min. 500
Min. 50
L
Min.
1000
Min. 500
L
Min.
1000
Min. 100
If L is larger than H, mount the units on a base so
that H is greater or equal to L.
H: Unit Height (1650mm) + Base Concrete Height
In this situation ensure that the base is closed and does not allow the airflow to short circuit.
In each case, install the outdoor unit so that the discharge flow is not short-circuited.
NOTE
Fig. 4.3 Installation Space (3)
Fig. 4.4 Installation Space (4)
Min.
150
Single Installation
Multiple Installation
(mm)
NOTE:
Mount the airflow guide and open both
right and left sides.
NOTE:
Mount the airflow guide
and open both right and
left sides.
Min.
700
Front
Side
Min. 700
H
Min. 700
Min.
100
Min. 700
NOTE:
Mount the airflow guide and
open right end or left end.
H
350
No more than 2 units for
multiple installation
NOTE:
Mount the airflow
guide and open both
right and left sides.
350
L
L
Min.50
Min.100
Fit positions " " with unit front side.
L
A
0 < L < 1/2H
600 or more
1/2H < L < H
1400 or more