JOHNSON CONTROLS
62
FORM 100.50-NOM7 (808)
Parameter Descriptions and Options
TABLE 7 – SETPOINTS AND VALUES
Continued on next page
DESCRIPTION TEXT ON OCC
UNITS
DEFAULT
VALUE
OCC
VALUE
RANGE
KEY
1.
Unit Type
CV
CV, VAV, MIT-VAV
Configuration
2.
Dirty Filter Switch
OFF
ON or OFF
Configuration
3.
ASCD Override
OFF
ON or OFF
Configuration
4.
Run Test
OFF
ON or OFF
Configuration
5.
Panel Test
OFF
ON or OFF
Configuration
6.
# of Compressors
4
4 or 6
Configuration
7.
# of Heat Steps
0
0-6
2
Configuration
8.
Heating Type
1
None, Gas
None, Gas, Electric,
Configuration
HW, or Steam
9.
Freezestat
OFF
ON or OFF
Configuration
10.
Transducer Package
0
0 – 3
Configuration
11.
Reset Lead-Lag
OFF
ON or OFF
Configuration
12.
Cooling SAT Limit #1
°F
45°F
40°-50°F
Configuration
13.
Cooling SAT Limit #2
°F
50°F
40°-65°F
Configuration
14.
Heating SAT Limit
°F
160°F
100°-195°F
Configuration
15.
Power Exhaust Config
0
0 - 3
Configuration
16.
Economizer Installed
NO
YES – NO
Configuration
17.
Duct Sensor Hi Limit
inwg
5.0
2.5 – 5.0
Configuration
18.
Sys X Comp Runtimes
2
starts
0
(> expected value)
Service
19.
Sys X Comp Starts
2
hr
0
(> expected value)
Service
20.
Exhaust (Fan Runtimes)
2
hr
0
(> expected value)
Service
21.
Unoccupied Heating
°F
60°
45°-99°
Setpoint
22.
Unoccupied Cooling
°F
85°
45°-99°
Setpoint
23.
Occupied Heating
°F
68°
45°-99°
Setpoint
24.
Occupied Cooling
°F
72°
45°-99°
Setpoint
25.
VAV Cool High Temp
°F
60°
50°-70°
Setpoint
26.
VAV Cool Low Temp
°F
55°
50°-70°
Setpoint
27.
VAV Cool Reset Temp
°F
72°
60°-95°
Setpoint
28.
Duct Static Pressure
inwg
1.50
0.00-5.00
Setpoint
29.
Building Pressure
inwg
+0.100
-0.200-+0.200
Setpoint
30.
Economizer 1st Stage
°F
55°
40°-65°
Setpoint
31.
Economizer 2nd Stage
°F
50°
40°-65°
Setpoint
32.
SAT Econo Load Heat
°F
150
100 – 195
Setpoint
33.
Outside Air Enthalpy
btu/lb
28
22-40
Setpoint
34.
Cmfrt Vent High SAT
°F
80°
60°-85°
Setpoint
35.
Cmfrt Vent Low SAT
°F
70°
60°-85°
Setpoint
36.
Warm-Up RAT
°F
70°
50°-85°
Setpoint
37.
Hydro Heat 1st Stage
°F
100°
75°-150°
Setpoint
38.
Hydro Heat 2nd Stage
°F
115°
75°-150°
Setpoint
39.
OA Damper Min Pos #1
%
15%
0-100%
Setpoint
40.
OA Damper Min Pos #2
%
30%
0-100%
Setpoint
41.
Demand Ventilation
ppm
1000
750-1500
Setpoint
42.
(FlexSys) MSAT Setpoint
°F
62
55 – 70
Setpoint
43.
(FlexSys) Min Dewpt Diff
°F
3
1 – 5
Setpoint
44.
Language Option
English
English, Spanish
Unit Setup
45.
Measurement Units
Imperial
Imperial, SI Canada, SI
Unit Setup
46.
Space Sensor Enable
OFF
ON or OFF
Unit Setup
47.
Unocc Override Time
min
60 min
0-240 min
Unit Setup
48.
Space Setpt Offset
°F
3°F
0°-5°F
Unit Setup
49.
Fan ON With Sensor
ON
ON or OFF
Unit Setup
50.
RAT Sensor Enable
OFF
ON or OFF
Unit Setup
51.
Space Temp Alrm Diff
°F
5°F
0°-25°F
Unit Setup
52.
Space Temp Alrm Time
min
60 min
0-120 min
Unit Setup
53.
Sens Consist Enable
OFF
ON or OFF
Unit Setup
54.
SAT Control For Cool
ON
ON or OFF
Unit Setup
55.
SAT Control For Heat
°F
OFF
ON or OFF
Unit Setup
56.
Rev Act Heat Valve
OFF
ON or OFF
Unit Setup
Summary of Contents for J Series
Page 85: ...FORM 100 50 NOM7 808 85 JOHNSON CONTROLS 6 ELECTRICAL NOTES AND LEGEND LD13862 ...
Page 87: ...FORM 100 50 NOM7 808 87 JOHNSON CONTROLS 6 LD13864 ...
Page 88: ...JOHNSON CONTROLS 88 FORM 100 50 NOM7 808 Service OPTI CONVERSION TO 25 40 TON LD13854 ...
Page 89: ...FORM 100 50 NOM7 808 89 JOHNSON CONTROLS 6 LD13865 ELEMENTARY DIAGRAM ALL UNITS ...
Page 91: ...FORM 100 50 NOM7 808 91 JOHNSON CONTROLS 6 ELEMENTARY DIAGRAM GAS HEAT 25 40 TON 575V LD13861 ...