FORM 100.50-NOM7 (808)
63
JOHNSON CONTROLS
55
DESCRIPTION TEXT ON OCC
UNITS
DEFAULT
VALUE
OCC
VALUE
RANGE
KEY
57.
Cooling Mode Enable
ON
ON or OFF
Unit Setup
58.
Heating Mode Enable
ON
ON or OFF
Unit Setup
59.
Heat Lockout OAT
°F
75°F
0°-100°F
Unit Setup
60.
Cool Lockout OAT
°F
45°F
45°-100°F
Unit Setup
61.
Cooling SAT Alarm
°F
0°F
0°/50°-80°F
Unit Setup
62.
Heating SAT Alarm
°F
0°F
0°/70°-120°F
Unit Setup
63.
Duct Pressure Limit
inwg
3.00 inwg
0.00-5.00 inwg
Unit Setup
64.
VAV Occupied Heat
OFF
ON or OFF
Unit Setup
65.
OA SAT Reset
OFF
ON or OFF
Unit Setup
66.
SAT Temper Enable
OFF
ON or OFF
Unit Setup
67.
VAV With Thermostat
ON
ON or OFF
Unit Setup
68.
VAV Control Offset
°F
4.5
2.0 – 6.0
Unit Setup
69.
FlexSys Dewpt Reset
OFF
ON or OFF
Unit Setup
70.
Exh Dmpr Pos For ON
%
80%
0-100%
Unit Setup
71.
Exh Dmpr Pos For OFF
%
20%
0-100%
Unit Setup
72.
OA Dmpr Pos For ON
%
60%
0-100%
Unit Setup
73.
OA Dmpr Pos For OFF
%
20%
0-100%
Unit Setup
74.
OAH Sensor Enable
OFF
ON or OFF
Unit Setup
75.
RAH Sensor Enable
OFF
ON or OFF
Unit Setup
76.
Exhaust Cntrl Offset
inwg
0.015 inwg
0.010 – 0.050
Unit Setup
77.
Economizer Enable
ON
ON or OFF
Unit Setup
78.
SAT Econo Loading
ON
ON or OFF
Unit Setup
79.
Power Exhaust Enable
OFF
ON or OFF
Unit Setup
80.
OA Flow Cntrl Enable
OFF
ON or OFF
Unit Setup
81.
Comfort Vent Mode
OFF
ON or OFF
Unit Setup
82.
Cmfrt Vent Max Dampr
%
75%
0-100%
Unit Setup
83.
IAQ Sensor Enable
OFF
ON or OFF
Unit Setup
84.
IAQ Sensor Span
ppm
5000
0 – 10000
Unit Setup
85.
MAX DV Multiplier
1.25
1-2
Unit Setup
86.
Altitude
Ft
1000
0-10000 Ft
Unit Setup
87.
Morning Warm-Up
OFF
ON or OFF
Unit Setup
88.
Max Warm-Up Time
min
120 min
0-240 min
Unit Setup
89.
Pre-Occupancy Purge
OFF
ON or OFF
Unit Setup
90.
Purge Schedule
4am - 5am
Daily-Holiday
Unit Setup
all days
hh:mm start-end time
91.
Purge OAT High Limit
°F
85°
0°-110°F
Unit Setup
92.
Purge OAT Low Limit
°F
55°
0°-110°F
Unit Setup
93.
Smoke Purge Mode
0
0 – 5
Unit Setup
94.
Internal Clk/Sched
OFF
ON or OFF
Unit Setup
95.
Weekly Schedule
7am - 6pm
8 start/stop entries
Unit Setup
weekdays
96.
Holiday Schedule
(No Sched)
16 entries
Unit Setup
97.
Date and Time
(none)
dd-mm-year
Unit Status
hh:mm:ss am/pm
NOTES:
1. Both gas and electric heat are referred to functionally as “stepped”
heating or heating “stages”; both HW (hot water) and steam are
functionally referred to as “hydronic” heat.
NOTES FOR TABLE 7 – SETPOINTS AND VALUES
2. The compressor runtimes and starts and fan runtimes are entered
only when a compressor or fan is replaced.
Summary of Contents for J Series
Page 85: ...FORM 100 50 NOM7 808 85 JOHNSON CONTROLS 6 ELECTRICAL NOTES AND LEGEND LD13862 ...
Page 87: ...FORM 100 50 NOM7 808 87 JOHNSON CONTROLS 6 LD13864 ...
Page 88: ...JOHNSON CONTROLS 88 FORM 100 50 NOM7 808 Service OPTI CONVERSION TO 25 40 TON LD13854 ...
Page 89: ...FORM 100 50 NOM7 808 89 JOHNSON CONTROLS 6 LD13865 ELEMENTARY DIAGRAM ALL UNITS ...
Page 91: ...FORM 100 50 NOM7 808 91 JOHNSON CONTROLS 6 ELEMENTARY DIAGRAM GAS HEAT 25 40 TON 575V LD13861 ...