FORM 100.50-NOM7 (808)
23
JOHNSON CONTROLS
3
TABLE 3 – MODES OF OPERATION
Heating Cooling
Control
Occupied Unoccupied Occupied
Unoccupied
Thermostat
Controller Occupied input
Controller Occupied input
Controller Occupied input is ON
is ON (energized by ‘stat
is OFF (deenergized by
(energized by ‘stat occ. output,
occ. output, or by an
‘stat occ. output, or by
or by an external command).
external command).
an external command).
‘stat uses its programmed
‘stat uses its
Economizer damper is at
occupied clg. setpoint.
Supply
programmed occupied
0% Control is same as
fan controlled by ‘stat’s G output
htg. Setpoint. Supply fan
occupied heating, except
Economizer damper at
controlled by ‘stat’s G
‘stat uses its
programmed min. position, may
output.
programmed unoccupied
modulate open if free cooling is
Economizer damper at
heating setpoint.
being used.
programmed min. position.
Mechanical cooling mode:
‘stat W1, W2 outputs
‘stat Y1, Y2 outputs control
control heating stages 1
stage 1 and 2 compressors.
and 2.
Economizer mode:
If hydronic heat, ‘stat W1,
‘stat Y1, Y2 outputs select High
W2 outputs select
and Low programmed
programmed “Hydronic
Economizer SAT setpoints, SAT
heat 1
st
and 2
nd
stage
controlled by economizer
Setpoints.
control algorithm.
Space
Controller Occupied input
Controller Occupied input
Controller Occupied input is ON
Sensor
is ON (energized by an
is OFF (deenergized by
(energized by an external
external command).
an external command).
command).
Space temperature is
Economizer damper is at
Space temperature is controlled
controlled to a
0% Supply fan is in
to a programmed occupied clg.
programmed occupied
“Auto” mode (i.e. goes off
setpoint.
htg. setpoint.
when space is satisfied).
For supply fan, setting of the
For supply fan, setting of
Control is same as
parameter “Fan ON mode with
the parameter “Fan ON
occupied heating, except
the Sensor Option” determines
mode with the Sensor
space temperature is
if the supply fan is ON
Option” determines if the
controlled to a
continuously, or is in “Auto”
supply fan is ON
programmed unoccupied
mode (i.e. goes off when space
continuously, or is in
heating setpoint.
is satisfied).
“Auto” mode (i.e. goes off
Economizer damper at
when space is satisfied).
programmed min. position, may
Economizer damper at
modulate open if free cooling is
programmed min. position.
being used.
Heating is controlled by a
Mechanical cooling mode:
PI algorithm that controls
Cooling is controlled by a PI
staging of heat stages
algorithm that controls
and modulates duty cycle
compressor staging and
of the highest numbered
modulates duty cycle of the
running heating stage.
highest numbered running
If hydronic heat, space
compressor.
control algorithm selects
Economizer mode:
programmed “Hydronic
Space control algorithm selects
Heat 1
st
Stage SAT
High and Low programmed
Setpoint” and “Hydronic
Economizer SAT setpoints, SAT
Heat 2
nd
Stage SAT
controlled by economizer
Setpoint”.
control algorithm.
Controller Occupied input is
OFF (deenergized by ‘stat
occ. output, or by an external
command).
Economizer damper is at 0%
(damper may modulate open
if free cooling is being used).
Control is same as occupied
cooling, except ‘stat uses
its programmed unoccupied
cooling setpoint.
Controller Occupied input
is OFF (deenergized by an
external command).
Economizer damper is at 0%
(damper may modulate open
if free cooling is being used).
Supply fan is in “Auto” mode
(i.e. goes off when space is
satisfied).
Control is same as occupied
cooling with a space sensor,
except space temperature is
controlled to a programmed
unoccupied clg. setpoint.
Summary of Contents for J Series
Page 85: ...FORM 100 50 NOM7 808 85 JOHNSON CONTROLS 6 ELECTRICAL NOTES AND LEGEND LD13862 ...
Page 87: ...FORM 100 50 NOM7 808 87 JOHNSON CONTROLS 6 LD13864 ...
Page 88: ...JOHNSON CONTROLS 88 FORM 100 50 NOM7 808 Service OPTI CONVERSION TO 25 40 TON LD13854 ...
Page 89: ...FORM 100 50 NOM7 808 89 JOHNSON CONTROLS 6 LD13865 ELEMENTARY DIAGRAM ALL UNITS ...
Page 91: ...FORM 100 50 NOM7 808 91 JOHNSON CONTROLS 6 ELEMENTARY DIAGRAM GAS HEAT 25 40 TON 575V LD13861 ...