background image

 

 

OUTDOOR UNIT PICTURES

 

 

HLDA-HLJA 07-09, HEDB-HEJB 07-09

 

 

88

 

 

   

225

 

 

    

404

 

540

 

525

 

75

 

 

  

60

 

261

 

   

82

 

 

  

 

700

 

60

 

 

 

458

 

 

 

5

 

88

 

 

 

33

 

 

 

 

 

 

 
 

250

 

 

35

 

 
 

HLDA-HLJA 12, HEDB-HEJB 12,

 

 

HLDA-HLJA 09-12 [115V, 60Hz (UL)]

 

 

128

 

 

245

 

 

5

 

 

420

 

 
 

540

 

527

 

 

272

 

 

298

 

780

 

 

 

10

 

 

548

 

115

 

 

 

   

45

 

 

     

 

 

   

 

 

     

 

90

 

 

266

 

 

48

 

 
 

HLDA-HLJA 18, HEDB-HEJB 18

 

 

 
 
 
 
 
 

HLDA-HLJA 21-30, HEDB-HEJB 21-30, 
HLDA-HLJA 18 [220-230V, 60Hz (UL)]

 

  

843

 

313

 

  

301.5

 

 
 
 

3

5

1

.2

 5

6

9

4

.

 

 

135

 

 

141.5

 

560.1

 

 

 

235

 

 

125

 

 

335

 

 
 
 
 
 

HLDA-HLJA 36, HEDB-HEJB 36, 
HLDA-HLJA 24 [220-230V, 60Hz (UL)]

 

 

302

 

 
 

EN

 

 

860

 

 

62

 

 

895

 

 

77

 

 

598.6

 

142.9

 

 

328

 

 

 

285

 

 

 

750

 

 

 
 
 
 

590

 

 

 

62

 

 

 

290

 

 
 

530

 

110

 

 

 
 
 
 

 

J174_lastRev4.pmd

 

7

 

 

 

 
 
 
 
 
 

ENGLISH

 

7

 

 

 

 

3/14/05, 3:27 PM

 

 

 

 

Summary of Contents for HLEA-HLDA 07-36

Page 1: ...ual MINISPLIT MODELS HLCA HLHA 07 36 HIGH WALL HECB HEHB 07 30 HLEA HLDA 07 36 AIR CONDITIONER The units comply with one or more of the following marks see unit for details EN035M80000 000 J174_lastRe...

Page 2: ...5 Optimal operation 6 Preparation Before Installation 6 Installation Procedure 8 Maintenance 16 Operation tips 17 Trouble Shooting Guide 18 Technical Specification 19 Declaration of conformity 23 R22...

Page 3: ...e dangerous and can cause injury Installation and maintenance of this air conditioning system should only be carried out by trained and qualified personnel After unpacking please check the unit carefu...

Page 4: ...panel on the indoor unit would look like one of following NOTE All the pictures in this manual are for explanation purpose only They may be slightly different from the air conditioner you purchased T...

Page 5: ...erature you have selected and operation starts 1 1 hours 2 Set temperature 2 hours the room temperature The air conditioner will control room temperature automatically round the temperature point set...

Page 6: ...in breaker capacity are sufficient and the installation area is sufficient and complies with the requirements Check that the power supply available agrees with name plate voltage Electrical work wirin...

Page 7: ...128 245 5 420 540 527 272 298 780 10 548 115 45 90 266 48 HLDA HLJA 18 HEDB HEJB 18 HLDA HLJA 21 30 HEDB HEJB 21 30 HLDA HLJA 18 220 230V 60Hz UL 843 313 301 5 351 2 5694 135 141 5 560 1 235 125 335...

Page 8: ...ction or 6 0 A more ormore 10cm ore m or B 100cm 60cm or more C Loop the connective cable INSTALLATION PROCEDURE INDOOR UNIT Fixing Place the installation guide pattern on the designated installation...

Page 9: ...cable to terminal as identified with their respective marking Do not damage the conductor core or inner insulation of power supply cables and do not deform or crush the cables A Right B Right D Right...

Page 10: ...t be transmitted to the building structure NOTE Connect the pipe correctly Do not apply the excessive torque Use an appropriate bending tool to form curves and avoid over tightening the refrigerant tu...

Page 11: ...door Unit Liquid Line R22 R407C This unit is shipped complete with a charge of R22 R407C refrigerant that will be sufficient for an interconnecting piping length of 5 meters EN COLD AREA RECOMMENDATIO...

Page 12: ...led installation acceptance please refer to your contract with the power supplier if restrictions do apply for products like washing machines air conditioner or electrical ovens 4 For power details of...

Page 13: ...0Hz 380 415V 3Ph 50Hz 430V 3Ph 60Hz 430V 3Ph 60Hz For correct installation a proper ground connection must be made for unit Wiring Connection EN Model 07 21 Indoor Terminal block of indoor unit Outdoo...

Page 14: ...ling only type Cooling only type Model 30 3 Ph Indoor Outdoor Terminal block of indoor unit Terminal block of indoor unit Terminal block of outdoor unit Terminal block of outdoor unit 1 2 3 4 1 2 3 4...

Page 15: ...g only 1 Condition to start defrosting Units will switch to defrosting b Unit has been running at high temperature protection EN mode when either of the following conditions is met mode for 90 minutes...

Page 16: ...rom its support frame The installation and removing method of the air freshening filter is different depending on the models see the pictures marked 1 and 2 on the left Clean the air freshening filter...

Page 17: ...a normal condition when the air conditioner has not been used for a long time or during first use of the unit 5 A peculiar smell come out from the indoor unit This is caused by the indoor unit giving...

Page 18: ...separately together 3 The room was probably very hot 3 Wait while unit has enough time to cool when you star ted the cool the room system D The compressor run continuously 1 Thermostat adjustment too...

Page 19: ...4 e58 e60 59 Power Supply V Ph Hz 220 240 1 50 or 380 415 3 50 A 1 1 1 1 1 1 1 1 Air flow Hi Mi Lo m 3 h 380 350 320 450 420 390 550 500 460 750 710 650 800 760 700 1050 950 850 1150 1050 950 1350 120...

Page 20: ...Hz 220 230 1 60 Ph 1 1 1 1 1 1 1 Air flow Hi Mi Lo m 3 h 380 350 320 450 420 390 550 500 460 750 710 650 800 760 700 1050 950 850 1150 1060 960 U nit Fa n Input Power W 31W 1350 RPM 55 67 64 61 75 68...

Page 21: ...920 800 100 1000 880 U nit Fa n Input Power W 23 23 72 74 Indo or Running Current A 0 1 0 1 0 33 0 34 Height mm 250 280 330 330 Dimension Width mm 750 815 1080 1080 Depth mm 188 195 245 245 Weight kg...

Page 22: ...Power Supply V Ph Hz 220 240 1 50 or 380 415 3 50 Ph 1 1 1 1 1 1 1 Air flow Hi Mi Lo m 3 h 430 400 370 470 440 410 500 450 400 800 770 740 1050 950 850 1150 1050 950 U ni t Fa n Input Power W 37 5 36...

Page 23: ...horized Representative CM Choi Shipping Manager YORK International Northern Asia Ltd 15 F Tower II World Trade Square 123 Hoi Bun Road Kwun Tong Kowloon Hong Kong Telephone 852 2331 9286 Fax 852 2331...

Reviews: