(3) Remote ON/OFF 3 (Pulse Signal Input) [ Input Setting: Code (05) ]
The setting for Remote ON/OFF 3 shall be the same as that for Remote ON/OFF 2. By using the
signal from a building management system, the indoor units can be stopped.
If a signal is input during the stoppage of the indoor units, the unit remains unchanged.
An example of basic wiring and time chart is shown below.
OFF
X1
Power
Supply
Control Circuit
Indoor Unit PCB
CN3
X1
3P Connector
3
2
1
2
1
NOTE:
The pulse range is 200ms or more.
Wiring Diagram Example of Remote ON/OFF 3
(Example: Stoppage Input is set to terminals 1 and 2 of CN3.)
Signal to terminals 1 & 2 of CN3
Control by Wired Controller
Unit Operation
Time Chart
Time
(Example: Stoppage Input is set to terminals 1 and 2 of CN3.)
NOTES:
1. Picking up signal within 10 seconds after power supply is turned ON is not possible due to initialization
of the components.
Do not change the signal (ON/OFF) in this period.
2. Wired Controller is required for this function.
3. If multiple indoor units are connected to the same communication cable for wired controller, input the
signal to any of these indoor units.
4. When the communication cable is not used in the twin, triple and quad combinations for simultaneous
operation, input the signal to the main indoor unit.
Summary of Contents for HIDS006B21S
Page 2: ......
Page 10: ...viii SM 18001 rev 1...
Page 15: ...SM 18001 rev 1 1 1 INSTALLATION 1 Installation...
Page 19: ...SM 18001 rev 1 2 1 OPERATION 2 Operation...
Page 22: ......
Page 23: ...SM 18001 rev 1 3 1 TROUBLESHOOTING 3 Troubleshooting...
Page 75: ...MAINTENANCE SM 18001 rev 1 4 1 4 Maintenance...
Page 130: ......
Page 172: ......
Page 173: ...SM 18001 rev 1 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions...
Page 182: ...6 10 SM 18001 rev 1 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b...
Page 183: ...SERVICE PARTS LIST SM 18001 rev 1 7 1 7 Service Parts List...
Page 185: ......
Page 186: ...2018 Johnson Controls Inc SM 18001 rev 1 Code No LIT 12013047 Revised February 2019...