SM-18001-rev.1
3-9
TROUBLESHOOTING
(8) Fuse Recover (DSW7)
* When applying high voltage to terminals 1 and 2 of TB2, the fuse (0.5A)
on the PCB is blown. If this happens, first connect the wiring to TB2,
and then turn on the No.1 pin.
(10) Optional Function Setting (DSW9)
No setting is required. Factory settings are all OFF.
(7) Unit Model Code Setting (DSW4)
No setting is required.
This switch is utilized to set the model code of
the indoor unit.
* Factory Setting
1 2
ON
OFF
1 2
ON
OFF
1 2
ON
OFF
(6) Refrigerant Cycle Number Settings
(RSW2 and DSW5)
This setting is required. The unit arrives with all
settings in the OFF position.
34
1
0
89
2
56
7
34
1
0
89
2
56
7
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
DSW5 (Tens Digit)
Refrigerant Cycle Number Setting
RSW2 (Units Digit)
Setting
Position
Set by inserting
slotted screwdriver
into the groove.
Ex.) Set at No.5 Cycle
DSW5
RSW2
Set All Pins OFF
Set at "5"
Factory settings for DSW5 and RSW2 are set at "0".
For the units supporting H-LINK II, the refrigerant cycle
numbers can be set for a maximum of 64 cycles.
(No. 0 to 63)
Ducted
High Static
Medium Static
Slim
1 2 3 4
ON
OFF
1 2 3 4
ON
OFF
1 2 3 4
ON
OFF
(9) Optional (DSW8)
▪ Ducted High Static
No setting is required. This is for setting the model code of the indoor unit.
▪ Ducted Medium Static and Slim
No setting is required.
Factory settings are all OFF.
2
1
3
ON
OFF
2
1
3
ON
OFF
2
1
3
ON
OFF
Produced in March 2018 or earlier
Produced in April 2018 or later
Summary of Contents for HIDS006B21S
Page 2: ......
Page 10: ...viii SM 18001 rev 1...
Page 15: ...SM 18001 rev 1 1 1 INSTALLATION 1 Installation...
Page 19: ...SM 18001 rev 1 2 1 OPERATION 2 Operation...
Page 22: ......
Page 23: ...SM 18001 rev 1 3 1 TROUBLESHOOTING 3 Troubleshooting...
Page 75: ...MAINTENANCE SM 18001 rev 1 4 1 4 Maintenance...
Page 130: ......
Page 172: ......
Page 173: ...SM 18001 rev 1 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions...
Page 182: ...6 10 SM 18001 rev 1 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b...
Page 183: ...SERVICE PARTS LIST SM 18001 rev 1 7 1 7 Service Parts List...
Page 185: ......
Page 186: ...2018 Johnson Controls Inc SM 18001 rev 1 Code No LIT 12013047 Revised February 2019...