SM-18001-rev.1
5-5
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
5.4.1 External Input and Output Settings
On the Indoor Unit Printed Circuit Board (PCB), there are two input terminals (CN3) to receive external
signals and three output terminals (CN7, CN8
5
) to send signals out. Functions shown in these tables are
available when setting input and output terminals.
Input and Output Number Display and Connectors
Input and Output Settings and Display Codes
Input Number Display
Port
Factory Setting
Setting
Input/Output Indication
Setting Item
Indication
Input 1
CN3 1-2 Remote ON/OFF 1 (Level)
03
Input 2
CN3 2-3 Prohibiting Remote Control after Manual Stoppage
06
Output 1
CN7 1-2
Operation
01
Output 2
CN7 1-3 Alarm
02
Output 3
CN8
5
1-2
Thermo-ON for Heating
06
Code Indicated
Input
Output
00
Not set
Not set
01
Room Thermostat (for Cooling)
Operation
02
Room Thermostat (for Heating)
Alarm
03
Remote ON/OFF 1 (Level)
Cooling
04
Remote ON/OFF 2 (Operation)
Thermo-ON for Cooling
05
Remote ON/OFF 2 (Stoppage)
Heating
06
Forbidding Remote Control after Manual Stoppage Thermo-ON for Heating
07
Remote Cooling / Heating Change
Total Heat Exchanger
09
Setback Temperature
N/A
NOTES:
1. Change the optional setting after waiting at least three minutes elapsed time after start-up.
2. Do not set the elevating grille for the total heat exchanger.
3. Record the setting conditions for each input and output in the “Setting” column of the table.
4. When PSC-5RA (optional) is used for connection between the auxiliary heater and indoor unit, DO NOT
connect connector (CN7) to indoor unit PCB. Otherwise, fire may result.
Use another PSC-5RA (optional) for input/output integration functionality.
5. Output terminal (CN8) is no longer available for Ducted Medium Static type and Ducted Slim type indoor
units produced in April 2018 or later.
Summary of Contents for HIDS006B21S
Page 2: ......
Page 10: ...viii SM 18001 rev 1...
Page 15: ...SM 18001 rev 1 1 1 INSTALLATION 1 Installation...
Page 19: ...SM 18001 rev 1 2 1 OPERATION 2 Operation...
Page 22: ......
Page 23: ...SM 18001 rev 1 3 1 TROUBLESHOOTING 3 Troubleshooting...
Page 75: ...MAINTENANCE SM 18001 rev 1 4 1 4 Maintenance...
Page 130: ......
Page 172: ......
Page 173: ...SM 18001 rev 1 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions...
Page 182: ...6 10 SM 18001 rev 1 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b...
Page 183: ...SERVICE PARTS LIST SM 18001 rev 1 7 1 7 Service Parts List...
Page 185: ......
Page 186: ...2018 Johnson Controls Inc SM 18001 rev 1 Code No LIT 12013047 Revised February 2019...