EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
(1) Quick Function
This function is used when decreasing/increasing the indoor temperature quickly.
This function operates as follows for 30 minutes from the operation start-up.
This function is only available when the operation mode is COOL or HEAT.
The unit starts each time in quick mode until the setting is canceled.
(2) Power Up Setting
If the cooling/heating capacity seems insufficient during the normal operation, set this function.
By setting this function, the target frequency and upper limit of the compressor are set higher as
follows.
Setting Condition
Compressor Frequency
Indoor Fan
Upper Limit
Target Frequency
Variation Width
Default Setting
-
-
-
-
COOL
Default S20% Default S20% Default S200%
Automatically
HEAT
Default S20% Default S20% Default S50%
-
Setting Condition
Power Up Mode
Compressor Frequency for Cooling Operation Compressor Frequency for Heating Operation
Upper Limit
Target Frequency
Upper Limit
Target Frequency
0 (Default Setting)
-
-
-
-
1
Default S20% Default S20%
-
-
2
-
-
Default S20% Default S20%
3
Default S20% Default S20% Default S20% Default S20%
NOTES:
1. If this function is set, indoor fan speed is automatically controlled regardless fan speed setting from
wired controller. (If there is an upper/lower limit of airflow, do not use this function.)
In case of Ducted (EconoFresh), do not use this function. If it is used for Ducted (EconoFresh), the
thermal load of the room may significantly increase depending on the outdoor temperature conditions.
2. The upper limit and target frequency of the compressor are same as Function Setting “Hc” or “Hh”.
3. This function may increase power consumption.
NOTE:
The upper limit and target frequency of the compressor are same as Function Setting “Hc” or “Hh”.
5.5.4 Comfort Function
Following functions are not available depending on connected outdoor unit.
Summary of Contents for HIDS006B21S
Page 2: ......
Page 10: ...viii SM 18001 rev 1...
Page 15: ...SM 18001 rev 1 1 1 INSTALLATION 1 Installation...
Page 19: ...SM 18001 rev 1 2 1 OPERATION 2 Operation...
Page 22: ......
Page 23: ...SM 18001 rev 1 3 1 TROUBLESHOOTING 3 Troubleshooting...
Page 75: ...MAINTENANCE SM 18001 rev 1 4 1 4 Maintenance...
Page 130: ......
Page 172: ......
Page 173: ...SM 18001 rev 1 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions...
Page 182: ...6 10 SM 18001 rev 1 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b...
Page 183: ...SERVICE PARTS LIST SM 18001 rev 1 7 1 7 Service Parts List...
Page 185: ......
Page 186: ...2018 Johnson Controls Inc SM 18001 rev 1 Code No LIT 12013047 Revised February 2019...