background image

035-20401-001 Rev. A (0904)

Unitary Products Group

5

See "System Charge” section for checking and recording system
charge.

SECTION IV: INSTALLATIONS REQUIRING 

TXV

For installations requiring a TXV, the following are the basic steps for
installation. For detailed instructions, refer to the Installation Instructions
accompanying the TXV kit.

Install TXV kit as follows:

1.

First, relieve the holding charge by depressing the Schrader valve
located in the end of the liquid line.

2.

After holding charge is completely discharged, loosen and remove
the liquid line fitting from the orifice distributor assembly. Note that
the fitting has 

right

 

hand

 

threads

.

3.

Remove the orifice from the distributor body using a small diame-
ter wire or paper clip. Orifice is not used when the TXV assembly
is installed.

4.

After orifice is removed, install the thermal expansion valve to the
orifice distributor assembly with supplied fittings. Hand tighten and
turn an additional 1/8 turn to seal. Do not overtighten fittings.

5.

Reinstall the liquid line to the top of the thermal expansion valve.
Hand modify the liquid line to align with casing opening.

6.

Install the TXV equalizer line into the vapor line as follows:

a.

Select a location on the vapor line for insertion of the equal-
izer line which will not interfere with TXV bulb placement.

b.

Use an awl to punch through the suction tube and insert the
awl to a depth to achieve a 1/8” diameter hole.

7.

Install TXV equalizer line in 1/8” hole previously made in vapor
line. Equalizer line should not be bottomed out in vapor line. Insert
equalizer line at least 1/4” in the vapor line. Braze equalizer line
making sure that tube opening is not brazed closed.

All connections to be brazed are copper-to-copper and should be
brazed with a phosphorous-copper alloy material such as Silfos-5 or
equivalent. DO NOT use soft solder.

Install the TXV bulb to the vapor line near the equalizer line, using the
two bulb clamps furnished with the TXV assembly. Ensure the bulb is
making maximum contact. Refer to TXV installation instruction for view
of bulb location.

a.

Bulb should be installed on a horizontal run of the vapor line if
possible. On lines under 7/8" OD the bulb may be installed on
top of the line. With 7/8" OD and over, the bulb should be
installed at the position of about 2 or 10 o'clock.

b.

If bulb installation is made on a vertical run, the bulb should
be located at least 16 inches from any bend, and on the tub-
ing sides opposite the plane of the bend. The bulb should be
positioned with the bulb tail at the top, so that the bulb acts as
a reservoir.

c.

Bulb should be insulated using thermal insulation provided to
protect it from the effect of the surrounding ambient tempera-
ture.

SECTION V: ELECTRICAL CONNECTIONS

GENERAL INFORMATION & GROUNDING

Check the electrical supply to be sure that it meets the values specified
on the unit nameplate and wiring label.

Power wiring, control (low voltage) wiring, disconnect switches and over
current protection must be supplied by the installer. Wire size should be
sized per NEC requirements.

The complete connection diagram and schematic wiring label is located
on the inside surface of the unit service access panel and this instruc-
tion.

FIELD CONNECTIONS POWER WIRING

1.

Install the proper size weatherproof disconnect switch outdoors
and within sight of the unit.

2.

Remove the screws at the bottom of the corner cover. Slide corner
cover down and remove from unit. See Figure 5.

3.

Run power wiring from the disconnect switch to the unit.

4.

Remove the service access panel to gain access to the unit wiring.
Route wires from disconnect through power wiring opening pro-
vided and into the unit control box.

5.

Install the proper size time-delay fuses or circuit breaker, and
make the power supply connections.

6.

Energize the crankcase heater if equipped to save time by pre-
heating the compressor oil while the remaining installation is com-
pleted.

Never attempt to repair any brazed connections while the system is
under pressure. Personal injury could result.

 Dry nitrogen should always be supplied through the tubing while it
is being brazed, because the temperature required is high enough
to cause oxidation of the copper unless an inert atmosphere is pro-
vided. The flow of dry nitrogen should continue until the joint has
cooled. Always use a pressure regulator and safety valve to insure
that only low pressure dry nitrogen is introduced into the tubing.
Only a small flow is necessary to displace air and prevent oxidation.

 In all cases, mount the TXV bulb after vapor line is brazed and has
had sufficient time to cool.

All field wiring must USE COPPER CONDUCTORS ONLY and
be in accordance with Local, National Fire, Safety & Electrical
Codes. This unit must be grounded with a separate ground
wire in accordance with the above codes.

 FIGURE 5: 

Typical Field Wiring

CONTROL
WIRING

POWER
WIRING

CORNER
COVER

SERVICE
ACCESS
PANEL

Summary of Contents for HC5B Series

Page 1: ...ractices and hazards involving only property dam age Improper installation may create a condition where the operation of the product could cause personal injury or property damage Improper installatio...

Page 2: ...topped ground area the unit should be raised sufficiently above the roof or ground to avoid taking the accumulated layer of hot air into the outdoor unit Provide an adequate structural support ADD ON...

Page 3: ...a line will result in loss of capacity and other problems caused by insufficient refrigerant flow Slope horizontal vapor lines at least 1 every 20 feet toward the out door unit to facilitate proper oi...

Page 4: ...tem from the vapor service port connection After this con nection has cooled remove the nitrogen source from the liquid fit ting service port 7 Replace the Schrader core in the liquid and vapor valves...

Page 5: ...a vertical run the bulb should be located at least 16 inches from any bend and on the tub ing sides opposite the plane of the bend The bulb should be positioned with the bulb tail at the top so that t...

Page 6: ...hat a mini mum air flow of 325 cfm ton be supplied at all times CFM SELECTION BOARD SETTINGS For proper system operation the CFM Selection Board jumpers must be set properly Refer to the Tabular Data...

Page 7: ...operation the unit must be evacuated and charge weighed in per the marking on the rating plate For the cooling operation the recommended subcooling is typically around 10 F This may vary greatly base...

Page 8: ...ys that are already energized but will not energize any additional relays until the voltage level increases If the voltage drops below approximately 16 VAC the control will imme diately de energize th...

Page 9: ...not be displayed when a fault code is present During the following conditions the control will not energize the X L out put FAULT CODE DISPLAY X L Output The X L terminal of the heat pump control is...

Page 10: ...ored fault codes from the control s memory This practice will enable better troubleshooting and diagnosis of system problems If the stored fault codes are not cleared after the cause of the problem ha...

Page 11: ...be removed and reapplied When the hard lockout condition is reset the control will de energize the LED and X L outputs and respond to thermostat inputs normally Wiring or Setting Related Lockouts The...

Page 12: ...ing cycle The control will initiate a defrost cycle every 6 hours accumulated com pressor run time to recirculate refrigerant lubricants This forced defrost timer will be reset and restarted following...

Page 13: ...es Recycling 24VAC to the control Shorting the TEST input pins If the Y2 LOCK jumper is in the OFF position the control will not imple ment second stage anticipation mode This results in second stage...

Page 14: ...uid line temperature Therefore if the control energizes Y2 OUT because the outdoor ambient temperature is greater than or equal to 50F or because the liquid line temperature exceeds the curve for the...

Page 15: ...ode If the other exit conditions are met while the unit is in defrost mode the control will complete the defrost cycle and then exit the forced second stage feature During defrost operation the contro...

Page 16: ...re is greater than the bal ance point setting the control will not energize the auxiliary heat out puts However the control shall ignore the balance point setting and energize auxiliary heat under som...

Page 17: ...t the control will de energize the compressor outputs and energize W1 OUT and W2 OUT immediately Table 11 describes the auxiliary heat operation for fossil fuel mode Bonnet Sensor Fossil Fuel Mode The...

Page 18: ...this document for detailed information The Y2 Lock jumper on the control is shown in figures 11 14 The fac tory places the Y2 Lock jumper in the ON position If the jumper is removed the control will...

Page 19: ...When applicable instruct the owner that the compressor is equipped with a crankcase heater to prevent the migration of refrigerant to the compressor during the OFF cycle The heater is energized only...

Page 20: ...404 11 105 412 6 416 9 426 12 431 11 110 441 7 445 9 454 12 458 11 115 471 8 475 10 482 12 487 11 120 503 9 507 10 512 11 516 11 125 536 10 540 10 543 11 546 10 TABLE 15 15Z48HP Subcooling Charging C...

Page 21: ...035 20401 001 Rev A 0904 Unitary Products Group 21 SECTION X WIRING DIAGRAM FIGURE 15 Wiring Diagram...

Page 22: ...035 20401 001 Rev A 0904 22 Unitary Products Group NOTES...

Page 23: ...035 20401 001 Rev A 0904 Unitary Products Group 23...

Page 24: ...ct to change without notice Printed in U S A 035 20401 001 Rev A 0904 Copyright by York International Corp 2004 All rights reserved Supersedes Nothing Unitary 5005 Norman Product York OK Group Drive 7...

Reviews: