background image

035-20401-001 Rev. A (0904)

4

Unitary Products Group

PRECAUTIONS DURING BRAZING OF LINES

All outdoor unit and evaporator coil connections are copper-to-copper
and should be brazed with a phosphorous-copper alloy material such
as Silfos-5 or equivalent. DO NOT use soft solder. The outdoor units
have reusable service valves on both the liquid and vapor connections.
The total system refrigerant charge is retained within the outdoor unit
during shipping and installation. The reusable service valves are pro-
vided to evacuate and charge per this instruction.

Serious service problems can be avoided by taking adequate precau-
tions to assure an internally clean and dry system.

PRECAUTIONS DURING BRAZING SERVICE VALVE

Precautions should be taken to prevent heat damage to service valve
by wrapping a wet rag around it as shown in Figure 4. Also, protect all
painted surfaces, insulation, and plastic base during brazing. After braz-
ing cool joint with wet rag.

Valve can be opened by removing the plunger cap and fully inserting a
hex wrench into the stem and backing out counter-clockwise until valve
stem just touches the chamfered retaining wall.

Connect the refrigerant lines using the following procedure:

1.

Remove the cap and Schrader core from both the liquid and vapor
service valve service ports at the outdoor unit. Connect low pres-
sure nitrogen to the liquid line service port.

2.

Braze the liquid line to the liquid valve at the outdoor unit. Be sure
to wrap the valve body with a wet rag. Allow the nitrogen to con-
tinue flowing. Refer to the Tabular Data Sheet for proper liquid line
sizing.

3.

Carefully remove the rubber plugs from the evaporator liquid and
vapor connections at the indoor coil.

4.

Braze the liquid line to the evaporator liquid connection. Nitrogen
should be flowing through the evaporator coil.

5.

Slide the grommet away from the vapor connection at the indoor
coil. Braze the vapor line to the evaporator vapor connection. After
the connection has cooled, slide the grommet back into original
position. Refer to the Tabular Data Sheet for proper vapor line siz-
ing.

6.

Protect the vapor valve with a wet rag and braze the vapor line
connection to the outdoor unit. The nitrogen flow should be exiting
the system from the vapor service port connection. After this con-
nection has cooled, remove the nitrogen source from the liquid fit-
ting service port.

7.

Replace the Schrader core in the liquid and vapor valves.

8.

Go to “SECTION IV” for TXV installation.

9.

Leak test all refrigerant piping connections including the service
port flare caps to be sure they are leak tight. DO NOT OVER-
TIGHTEN (between 40 and 60 inch - lbs. maximum).

10. Evacuate the vapor line, evaporator and the liquid line, to 500

microns or less.

NOTE: 

Line set and indoor coil can be pressurized to 250 psig with dry

nitrogen and leak tested with a bubble type leak detector. Than
release the nitrogen charge.

NOTE: 

Do not use the system refrigerant in the outdoor unit to purge or

leak test.

11.

Replace cap on service ports. Do not remove the flare caps from
the service ports except when necessary for servicing the system.

12. Release the refrigerant charge into the system. Open both the liq-

uid and vapor valves by removing the plunger cap and with an
allen wrench back out counter-clockwise until valve stem just
touches the chamfered retaining wall. See Page 4 "PRECAU-
TIONS DURING BRAZING SERVICE VALVE".

13. Replace plunger cap finger tight, then tighten an additional 1/12

turn (1/2 hex flat). Cap must be replaced to prevent leaks.

 FIGURE 3: 

Underground Installation

 Dry nitrogen should always be supplied through the tubing while it
is being brazed, because the temperature required is high enough
to cause oxidation of the copper unless an inert atmosphere is pro-
vided. The flow of dry nitrogen should continue until the joint has
cooled. Always use a pressure regulator and safety valve to insure
that only low pressure dry nitrogen is introduced into the tubing.
Only a small flow is necessary to displace air and prevent oxidation.

This is not a backseating valve. The service access port has a
valve core. Opening or closing valve does not close service access
port.
 If the valve stem is backed out past the chamfered retaining wall,
the O-ring can be damaged causing leakage or system pressure
could force the valve stem out of the valve body possibly causing
personal injury.

TO INDOOR COIL

TO O UTDOOR UNIT

LIQUID LINE

CAP

PVC

CONDUIT

INSULATED

VAPOR LINE

 FIGURE 4: 

Heat Protection

The evaporator is pressurized.

 Do not connect manifold gauges unless trouble is suspected.
Approximately 3/4 ounce of refrigerant will be lost each time a stan-
dard manifold gauge is connected.

Summary of Contents for HC5B Series

Page 1: ...ractices and hazards involving only property dam age Improper installation may create a condition where the operation of the product could cause personal injury or property damage Improper installatio...

Page 2: ...topped ground area the unit should be raised sufficiently above the roof or ground to avoid taking the accumulated layer of hot air into the outdoor unit Provide an adequate structural support ADD ON...

Page 3: ...a line will result in loss of capacity and other problems caused by insufficient refrigerant flow Slope horizontal vapor lines at least 1 every 20 feet toward the out door unit to facilitate proper oi...

Page 4: ...tem from the vapor service port connection After this con nection has cooled remove the nitrogen source from the liquid fit ting service port 7 Replace the Schrader core in the liquid and vapor valves...

Page 5: ...a vertical run the bulb should be located at least 16 inches from any bend and on the tub ing sides opposite the plane of the bend The bulb should be positioned with the bulb tail at the top so that t...

Page 6: ...hat a mini mum air flow of 325 cfm ton be supplied at all times CFM SELECTION BOARD SETTINGS For proper system operation the CFM Selection Board jumpers must be set properly Refer to the Tabular Data...

Page 7: ...operation the unit must be evacuated and charge weighed in per the marking on the rating plate For the cooling operation the recommended subcooling is typically around 10 F This may vary greatly base...

Page 8: ...ys that are already energized but will not energize any additional relays until the voltage level increases If the voltage drops below approximately 16 VAC the control will imme diately de energize th...

Page 9: ...not be displayed when a fault code is present During the following conditions the control will not energize the X L out put FAULT CODE DISPLAY X L Output The X L terminal of the heat pump control is...

Page 10: ...ored fault codes from the control s memory This practice will enable better troubleshooting and diagnosis of system problems If the stored fault codes are not cleared after the cause of the problem ha...

Page 11: ...be removed and reapplied When the hard lockout condition is reset the control will de energize the LED and X L outputs and respond to thermostat inputs normally Wiring or Setting Related Lockouts The...

Page 12: ...ing cycle The control will initiate a defrost cycle every 6 hours accumulated com pressor run time to recirculate refrigerant lubricants This forced defrost timer will be reset and restarted following...

Page 13: ...es Recycling 24VAC to the control Shorting the TEST input pins If the Y2 LOCK jumper is in the OFF position the control will not imple ment second stage anticipation mode This results in second stage...

Page 14: ...uid line temperature Therefore if the control energizes Y2 OUT because the outdoor ambient temperature is greater than or equal to 50F or because the liquid line temperature exceeds the curve for the...

Page 15: ...ode If the other exit conditions are met while the unit is in defrost mode the control will complete the defrost cycle and then exit the forced second stage feature During defrost operation the contro...

Page 16: ...re is greater than the bal ance point setting the control will not energize the auxiliary heat out puts However the control shall ignore the balance point setting and energize auxiliary heat under som...

Page 17: ...t the control will de energize the compressor outputs and energize W1 OUT and W2 OUT immediately Table 11 describes the auxiliary heat operation for fossil fuel mode Bonnet Sensor Fossil Fuel Mode The...

Page 18: ...this document for detailed information The Y2 Lock jumper on the control is shown in figures 11 14 The fac tory places the Y2 Lock jumper in the ON position If the jumper is removed the control will...

Page 19: ...When applicable instruct the owner that the compressor is equipped with a crankcase heater to prevent the migration of refrigerant to the compressor during the OFF cycle The heater is energized only...

Page 20: ...404 11 105 412 6 416 9 426 12 431 11 110 441 7 445 9 454 12 458 11 115 471 8 475 10 482 12 487 11 120 503 9 507 10 512 11 516 11 125 536 10 540 10 543 11 546 10 TABLE 15 15Z48HP Subcooling Charging C...

Page 21: ...035 20401 001 Rev A 0904 Unitary Products Group 21 SECTION X WIRING DIAGRAM FIGURE 15 Wiring Diagram...

Page 22: ...035 20401 001 Rev A 0904 22 Unitary Products Group NOTES...

Page 23: ...035 20401 001 Rev A 0904 Unitary Products Group 23...

Page 24: ...ct to change without notice Printed in U S A 035 20401 001 Rev A 0904 Copyright by York International Corp 2004 All rights reserved Supersedes Nothing Unitary 5005 Norman Product York OK Group Drive 7...

Reviews: