background image

035-16408-001 Rev. B (101)

4

Unitary Products Group

4.

After orifice is removed, install the thermal expansion
valve to the orifice distributor assembly with supplied fit-
tings. Hand tighten and turn an additional 1/8 turn to
seal. Do not overtighten fittings.

5.

Reinstall the liquid line to the top of the thermal expan-
sion valve. Hand modify the liquid line to align with cas-
ing opening.

6.

Install the TXV equalizer line into the vapor line as fol-
lows:

a.

Select a location on the vapor line for insertion of the
equalizer line which will not interfere with TXV bulb
placement.

b.

Use an awl to punch through the suction tube and
insert the awl to a depth to achieve a 1/8 inch diam-
eter hole.

7.

Install TXV equalizer line in 1/8 hole previously made in
vapor line. Equalizer line can be bottomed out in vapor
line as end of equalizer line is cut on 45 degrees angle to
prevent blockage. Braze equalizer line making sure that
tube opening is not brazed closed.

All connections to be brazed are copper-to-copper and
should be brazed with a phosphorous-copper alloy material
such as Silfos-5 or equivalent. DO NOT use soft solder.

Install the TXV bulb to the vapor line near the equalizer line,
using the two bulb clamps furnished with the TXV assembly.
Ensure the bulb is making maximum contact. Refer to TXV
installation instruction for view of bulb location.

1.

Bulb should be installed on a horizontal run of the vapor
line if possible. On lines under 7/8" OD the bulb may be
installed on top of the line. With 7/8" OD and over, the
bulb should be installed at the position of about 4 or 8
o'clock.

2.

If bulb installation is made on a vertical run, the bulb
should be located at least 16 inches from any bend, and
on the tubing sides opposite the plane of the bend. On
vertical bulb installations, the bulb should be positioned
with the bulb tail at the top, so that the bulb acts as a res-
ervoir.

3.

Bulb should be insulated using thermal insulation pro-
vided to protect it from the effect of the surrounding
ambient temperature.

PIPING CONNECTIONS

The outdoor condensing unit may be connected to the indoor
evaporator coil using field supplied refrigerant grade copper
tubing that is internally clean and dry. Units should be
installed only with the tubing sizes for approved system com-
binations as specified in Tabular Data Sheet. The charge
given is applicable for total tubing lengths up to 15 feet. See
Application Data Form 690.01-AD1V for installing tubing of
longer lengths and elevation differences.

NOTE:  

Using a larger than specified line size could result in

oil return problems. Using too small a line will result
in loss of capacity and other problems caused by
insufficient refrigerant flow. Slope horizontal vapor
lines at least 1" every 20 feet toward the outdoor
unit to facilitate proper oil return.

PRECAUTIONS DURING LINE INSTALLATION

1.

Install the lines with as few bends as possible. Care must
be taken not to damage the couplings or kink the tubing.
Use clean hard drawn copper tubing where no apprecia-
ble amount of bending around obstruction is necessary.
If soft copper must be used, care must be taken to avoid
sharp bends which may cause a restriction.

2.

The lines should be installed so that they will not obstruct
service access to the coil, air handling system or filter.

3.

Care must also be taken to isolate the refrigerant lines to
minimize noise transmission from the equipment to the
structure.

4.

The vapor line must be insulated with a minimum of 1/2"
foam rubber insulation (Arm-A-Flex or equivalent). Liquid
lines that will be exposed to direct sunlight and/or high
temperatures must also be insulated.

Tape and suspend the refrigerant lines as shown. DO NOT
allow metal-to metal contact. See Figure 2.

5.

Pack fiber glass insulation and a sealing material such
as permagum around refrigerant lines where they pene-
trate a wall to reduce vibration and to retain some flexibil-
ity. 

6.

See Form 690.01-AD1V for additional piping information.

Dry nitrogen should always be supplied through
the tubing while it is being brazed, because the
temperature required is high enough to cause
oxidation of the copper unless an inert atmo-
sphere is provided. The flow of dry nitrogen
should continue until the joint has cooled. Always
use a pressure regulator and safety valve to
insure that only low pressure dry nitrogen is intro-
duced into the tubing. Only a small flow is neces-
sary to displace air and prevent oxidation.

In all cases, mount the TXV bulb after vapor line
is brazed and has had sufficient time to cool.

 FIGURE 2 : 

INSULATION OF VAPOR LINE

Liquid
Line

Incorrect

Correct

Tape

Sheet Metal Hanger

Insulated Vapor Line

Summary of Contents for H1TC048

Page 1: ...NERAL INFORMATION GROUNDING 6 POWER WIRING 6 ACCESSORY WIRING 6 THERMOSTAT MOUNTING WIRING 6 DE HUMIDIFICATION CONTROL 7 FIELD CONNECTIONS CONTROL WIRING 7 INDOOR BLOWER SPEED SETTINGS 7 WIRING DIAGRA...

Page 2: ...en to alert the installer that severe per sonal injury death or equipment damage may result if instal lation procedures are not followed properly LIMITATIONS The unit should be installed in accordance...

Page 3: ...ined location 2 Remove the shipping carton and inspect for possible damage 3 Compressor tie down bolts should remain tightened 4 Position the unit on the base provided 5 Make a hole s in the structure...

Page 4: ...nstalled only with the tubing sizes for approved system com binations as specified in Tabular Data Sheet The charge given is applicable for total tubing lengths up to 15 feet See Application Data Form...

Page 5: ...g the service port flare caps to be sure they are leak tight DO NOT OVERTIGHTEN between 40 and 60 inch lbs maximum NOTE Do not use the system refrigerant in the outdoor unit to purge or leak test 9 Do...

Page 6: ...EC Class 2 from the thermostat to the indoor unit and outdoor unit Route the control wiring into the grommeted hole in the bottom of control box of the outdoor unit Using wire nuts connect to leads in...

Page 7: ...y to Y1 on the outdoor unit Do not connect to Y at the indoor control The first stage blower operation is controlled by the G signal It is critical the Y2 OUT signal is connected to Y at the air handl...

Page 8: ...TROL CLASS 2 WIRING POWER WIRING 208 230 1 60 GND LUG T2 T1 L2 L1 M1 BLK RED BRN YEL ORG PUR C R Y2 Y1 R Y2 Y1 G W1 W2 X L W2 W1 G Y C R 1 2 Y2 OUT X L C LOW HIGH FIGURE 6 WIRING FOR USE WITH SINGLE S...

Page 9: ...T USED 2 OUTDOOR UNIT WIRE NUT CONTACTOR THERMOSTAT P DU P XU 2 STAGE FURNACE TYPICAL TWO STAGE COOLING THERMOSTAT MUST BE USED DEHUMIDISTAT OPTIONAL POWER CONTROL FACTORY CLASS 1 WIRING TS CONTROL CL...

Page 10: ...ed with the matching thermostatic expansion valve kit listed in the tabular data sheet The best way to check the system charge is by check ing the system subcooling during the second stage of opera ti...

Page 11: ...15 of the pro grammed speed during the dehumidification mode This lower airflow reduces the evaporator temperature increasing the latent capacity The humidistat for these variable speed systems opens...

Page 12: ...maintenance Instruct the owner or the opera tor how to start stop and adjust temperature setting The installer should also instruct the owner on proper opera tion and maintenance of all other system...

Reviews: