background image

035-16408-001 Rev. B (101)

2

Unitary Products Group

GENERAL INFORMATION

These outdoor condensing units are designed to be installed
with corresponding variable speed air handlers or furnaces,
two stage furnaces and single speed air handlers or furnaces
and a corresponding coil with sweat connect lines. Each unit
is factory charged with refrigerant sufficient for the smallest
indoor evaporator coil plus 15 feet of field supplied vapor and
liquid lines. A balanced port hard shut-off TXV kit must be
used for optimum system performance.

Use this instruction in conjunction with the instruction for the
appropriate indoor evaporator coil, air handler or furnace and
other accessories. Read all instructions before installing the
unit.

INSPECTION

As soon as a unit is received, it should be inspected for possi-
ble damage during transit. If damage is evident, the extent of
the damage should be noted on the carrier's freight bill. A
separate request for inspection by the carrier's agent should
be made in writing. See Form 50.15-NM for more information.

REFERENCE

Installer should pay particular attention to the words NOTE,
CAUTION and WARNING.

NOTES are intended to clarify or make the installation easier.

CAUTIONS identify procedures which, if not followed care-
fully, could result in personal injury, property damage or
equipment damage.

WARNINGS are given to alert the installer that severe per-
sonal injury, death or equipment damage may result if instal-
lation procedures are not followed properly. 

LIMITATIONS

The unit should be installed in accordance with all national
and local safety codes and the limitations listed below:

1.

Limitations for the indoor unit, coil and appropriate
accessories must also be observed.

2.

Optimal performance is gained by using a variable speed
air handler or furnace. Special care must be given when
matched with a single speed blower (furnace or air han-
dler) and a variable frequency drive control or a relay kit
to maintain the proper dehumidification.See section on
dehumidification for details.

3.

The outdoor unit must not be installed with any duct work
in the air stream. The outdoor fan is the propeller type
and is not designed to operate against any additional
external static pressure.

4.

The unit should not be operated at outdoor temperatures
below 60 °F. 

The unit is not designed to operate with

a low ambient kit. 

Do not modify the control system to

operate with any type of low ambient kit.

5.

Indoor evaporator coil orifice 

must be removed prior to

the installation of a factory supplied balanced port TXV
kit.

Incorrect installation may create a condition
where the operation of the product could cause
personal injury or property damage.

This product must be installed in strict compli-
ance with the enclosed installation instructions
and any applicable local, state, and national
codes including, but not limited to, building, elec-
trical, and mechanical codes.

Summary of Contents for H1TC048

Page 1: ...NERAL INFORMATION GROUNDING 6 POWER WIRING 6 ACCESSORY WIRING 6 THERMOSTAT MOUNTING WIRING 6 DE HUMIDIFICATION CONTROL 7 FIELD CONNECTIONS CONTROL WIRING 7 INDOOR BLOWER SPEED SETTINGS 7 WIRING DIAGRA...

Page 2: ...en to alert the installer that severe per sonal injury death or equipment damage may result if instal lation procedures are not followed properly LIMITATIONS The unit should be installed in accordance...

Page 3: ...ined location 2 Remove the shipping carton and inspect for possible damage 3 Compressor tie down bolts should remain tightened 4 Position the unit on the base provided 5 Make a hole s in the structure...

Page 4: ...nstalled only with the tubing sizes for approved system com binations as specified in Tabular Data Sheet The charge given is applicable for total tubing lengths up to 15 feet See Application Data Form...

Page 5: ...g the service port flare caps to be sure they are leak tight DO NOT OVERTIGHTEN between 40 and 60 inch lbs maximum NOTE Do not use the system refrigerant in the outdoor unit to purge or leak test 9 Do...

Page 6: ...EC Class 2 from the thermostat to the indoor unit and outdoor unit Route the control wiring into the grommeted hole in the bottom of control box of the outdoor unit Using wire nuts connect to leads in...

Page 7: ...y to Y1 on the outdoor unit Do not connect to Y at the indoor control The first stage blower operation is controlled by the G signal It is critical the Y2 OUT signal is connected to Y at the air handl...

Page 8: ...TROL CLASS 2 WIRING POWER WIRING 208 230 1 60 GND LUG T2 T1 L2 L1 M1 BLK RED BRN YEL ORG PUR C R Y2 Y1 R Y2 Y1 G W1 W2 X L W2 W1 G Y C R 1 2 Y2 OUT X L C LOW HIGH FIGURE 6 WIRING FOR USE WITH SINGLE S...

Page 9: ...T USED 2 OUTDOOR UNIT WIRE NUT CONTACTOR THERMOSTAT P DU P XU 2 STAGE FURNACE TYPICAL TWO STAGE COOLING THERMOSTAT MUST BE USED DEHUMIDISTAT OPTIONAL POWER CONTROL FACTORY CLASS 1 WIRING TS CONTROL CL...

Page 10: ...ed with the matching thermostatic expansion valve kit listed in the tabular data sheet The best way to check the system charge is by check ing the system subcooling during the second stage of opera ti...

Page 11: ...15 of the pro grammed speed during the dehumidification mode This lower airflow reduces the evaporator temperature increasing the latent capacity The humidistat for these variable speed systems opens...

Page 12: ...maintenance Instruct the owner or the opera tor how to start stop and adjust temperature setting The installer should also instruct the owner on proper opera tion and maintenance of all other system...

Reviews: