background image

035-16408-001 Rev. B (101)

10

Unitary Products Group

INDOOR BLOWER SPEED SETTINGS

Refer to the Tabular Data Sheet for the recommended air flow
settings for each size condensing unit.

Variable Speed Air Handlers and Furnaces

 - Set the high

speed cooling speed per the instructions for the air handler or
furnace by selecting the correct “cool” and “ADJ” taps. The
low speed setting will automatically be programmed for the
correct airflow. Verify the airflow by LED display on the speed
selection board.

Single Speed Air Handlers and Furnaces - 

It is mandatory

a fan relay kit be applied to the furnace or air handler. The air
handlers are designed to use the 2SF06700124 fan relay and
the furnaces should use a SPDT 24VAC Coil (15 AMP rating
@ 115V). See figures 5 and 6 for wiring connections. The
ideal fan setting is to set the high speed (second stage) air
flow at the fan motor high speed and the low speed (first
stage) airflow at the fan low speed. If the low speed air flow is
too high, unsatisfactory dehumidifaction may occur on first
stage operation. To correct for unsatisfactory dehumidifica-
tion, either add a dehumidistat per figures 5 and 6 or change
the blower motor for better air flow performance.

Two Stage Furnaces

 - The ideal fan setting is to set the high

speed (second stage) air flow at the fan motor high speed
and the low speed (first stage) airflow at the fan low speed. If
the low speed air flow is too high, unsatisfactory dehumidifac-
tion may occur on first stage operation. To correct for unsatis-
factory dehumidification, either add a dehumidistat per figure
7 or change the blower motor for better air flow performance.

SYSTEM START-UP

ENERGIZE CRANKCASE HEATER

This unit is equipped with a crankcase heater for the com-
pressor.

IMPORTANT - 

An attempt to start the compressor without

at least 8 hours of crankcase heat will damage the compres-
sor.

In order to energize the crankcase heater, set the indoor ther-
mostat system switch to “OFF”. Close (turn on) the line power
disconnect to the unit.

CHECKING SYSTEM CHARGE

This condensing unit must only be used with the matching
thermostatic expansion valve kit listed in the tabular data
sheet. The best way to check the system charge is by check-
ing the system subcooling during the second stage of opera-
tion.

SERVICING AND VERIFY:

For 2nd stage (2 cylinder) operation, the recommended sub-
cooling is 15°F for all models. For 1st stage (1 cylinder) oper-
ation, the recommended subcooling is 10F for all models.

1.

Set the system running in the second stage (2 cylinder
operation) by setting the thermostat at least 6°F below
the room temperature. Short the “TEST” pin to bypass
the 5 minute anti-short cycle timer if necessary. See Fig-
ure 8.

2.

Operate the system for a minimum of 15 to 20 minutes.

3.

Refer to the tabular data sheet for the recommended air-
flow and verify this indoor air flow (it should be about 400
SCFM per ton).

4.

Measure the liquid refrigerant pressure P and tempera-
ture T at the service valve.

5.

Calculate the saturated liquid temperature ST from Table
1.

6.

Subcooling temperature TC = Saturated Temperature ST
Liquid temp T.

Example:

 The pressure P and temperature T measured at

the outdoor unit service port is 220 Psig and 95°F. From Table
1 the saturated temperature for 220 Psig is 108. The subcool-
ing temperature TC = 108 - 95 = 13°F.

The recommended subcooling level should be about 15+/
3°F for all models. Add charge if the calculated subcooling
temperature TC in step 6 is lower than the recommended
level. Remove and recover the refrigerant if the subcooling
Temperature TS is higher than the recommended level.

It is unlawful to knowingly vent, release or dis-
charge refrigerant into open air. It is necessary to
recover the refrigerant during any repair or instal-
lation of the system.

Refrigerant charging should only be carried out
by a qualified air conditioning contractor.

Table 1: R-22 SATURATION TEMPERATURE

ST

1

P

2

1.

ST = Saturated Temperature

2.

P = Pressure

90

168

91

171

92

174

93

176

94

179

ST

P

95

182

96

185

97

187

98

190

99

193

ST

P

100
196

101
199

102
202

103
205

104
208

ST

P

105
211

106
214

107
217

108
220

109
223

ST

P

110
226

111

229

112
233

113
236

114
239

ST

P

115
243

116
246

117
250

118
253

119
256

ST

P

120
260

121
263

122
267

123
271

124
274

ST

P

125
278

126
282

127
285

128
289

129
293

ST

P

130
297

131
301

132
305

133
309

134
313

Summary of Contents for H1TC048

Page 1: ...NERAL INFORMATION GROUNDING 6 POWER WIRING 6 ACCESSORY WIRING 6 THERMOSTAT MOUNTING WIRING 6 DE HUMIDIFICATION CONTROL 7 FIELD CONNECTIONS CONTROL WIRING 7 INDOOR BLOWER SPEED SETTINGS 7 WIRING DIAGRA...

Page 2: ...en to alert the installer that severe per sonal injury death or equipment damage may result if instal lation procedures are not followed properly LIMITATIONS The unit should be installed in accordance...

Page 3: ...ined location 2 Remove the shipping carton and inspect for possible damage 3 Compressor tie down bolts should remain tightened 4 Position the unit on the base provided 5 Make a hole s in the structure...

Page 4: ...nstalled only with the tubing sizes for approved system com binations as specified in Tabular Data Sheet The charge given is applicable for total tubing lengths up to 15 feet See Application Data Form...

Page 5: ...g the service port flare caps to be sure they are leak tight DO NOT OVERTIGHTEN between 40 and 60 inch lbs maximum NOTE Do not use the system refrigerant in the outdoor unit to purge or leak test 9 Do...

Page 6: ...EC Class 2 from the thermostat to the indoor unit and outdoor unit Route the control wiring into the grommeted hole in the bottom of control box of the outdoor unit Using wire nuts connect to leads in...

Page 7: ...y to Y1 on the outdoor unit Do not connect to Y at the indoor control The first stage blower operation is controlled by the G signal It is critical the Y2 OUT signal is connected to Y at the air handl...

Page 8: ...TROL CLASS 2 WIRING POWER WIRING 208 230 1 60 GND LUG T2 T1 L2 L1 M1 BLK RED BRN YEL ORG PUR C R Y2 Y1 R Y2 Y1 G W1 W2 X L W2 W1 G Y C R 1 2 Y2 OUT X L C LOW HIGH FIGURE 6 WIRING FOR USE WITH SINGLE S...

Page 9: ...T USED 2 OUTDOOR UNIT WIRE NUT CONTACTOR THERMOSTAT P DU P XU 2 STAGE FURNACE TYPICAL TWO STAGE COOLING THERMOSTAT MUST BE USED DEHUMIDISTAT OPTIONAL POWER CONTROL FACTORY CLASS 1 WIRING TS CONTROL CL...

Page 10: ...ed with the matching thermostatic expansion valve kit listed in the tabular data sheet The best way to check the system charge is by check ing the system subcooling during the second stage of opera ti...

Page 11: ...15 of the pro grammed speed during the dehumidification mode This lower airflow reduces the evaporator temperature increasing the latent capacity The humidistat for these variable speed systems opens...

Page 12: ...maintenance Instruct the owner or the opera tor how to start stop and adjust temperature setting The installer should also instruct the owner on proper opera tion and maintenance of all other system...

Reviews: