background image

035-16408-001 Rev. B (101)

Unitary Products Group

3

UNIT INSTALLATION

LOCATION

Before starting the installation, select and check the suitability
of the location for both the indoor and outdoor unit. Observe
all limitations and clearance requirements.

A minimum of 18” is required for service at the control panel.
A 10 inch clearance is required for the air inlet to the outdoor
coil. The air discharge of the unit requires a 60 inch clearance
between the top of the unit and any obstucture.

If the unit is to be installed on a black-topped ground area,
the unit should be raised sufficiently above the ground to
avoid taking the accumulated layer of hot air into the outdoor
unit. 

Provide an adequate structural support.

GROUND INSTALLATION

The unit may be installed at ground level on a solid base that
will not shift or settle, causing strain on the refrigerant lines
and possible leaks. Maintain the clearances shown in Figure
1 and install the unit in a level position. Isolate the base from
the structure to avoid noise or vibration transmission. 

Isolate the unit from rain gutters to avoid any possible wash
out of the foundation.

Normal operating sound levels may be objectionable if the
unit is placed directly under windows of certain rooms (bed
rooms, study, etc.).

UNIT PLACEMENT

1.

Provide a base in the pre-determined location.

2.

Remove the shipping carton and inspect for possible
damage.

3.

Compressor tie-down bolts should remain tightened.

4.

Position the unit on the base provided.

5.

Make a hole(s) in the structure wall large enough to
accommodate the insulated vapor line, the liquid line and
the wiring.

TXV INSTALLATION

This condensing unit requires the installation of a thermal
expansion valve. The TXV controls the superheat of the
refrigerant at the outlet of the evaporator coil, ensuring the
proper refrigerant temperature at the suction of compressor.
Following are the basic steps for installing the TXV. For detail
instructions, refer to the Installation Instructions accompany-
ing the TXV kit.

Install TXV kit as follows:

1.

First, relieve the holding charge by depressing the
Schrader valve located in the end of the liquid line. 

2.

After holding charge is completely discharged, loosen
and remove the liquid line fitting from the orifice distribu-
tor assembly. Note that the fitting has 

right hand

threads

.

3.

Remove the orifice from the distributor body using a
small diameter wire or paper clip. Orifice is not used
when the TXV assembly is installed.

 FIGURE 1 : 

TYPICAL INSTALLATION

MINIMUM 18” SERVICE ACCESS
CLEARANCE ON ONE SIDE

60” OVERHEAD
CLEARANCE

10” CLEARANCE
COIL AREA

WEATHERPROOF
DISCONNECT
SWITCH

THERMOSTAT

TO FURNACE OR
AIR HANDLER
TERMINAL BLOCK

NEC CLASS 1 WIRING

NEC CLASS 2 WIRING

TO INDOOR COIL

SEAL OPENING(S) WITH
PERMAGUM OR EQUIVALENT

CONTROL ACCESS PANEL

NOTE: ALL OUTDOOR WIRING MUST

BE WEATHERPROOF.

Summary of Contents for H1TC048

Page 1: ...NERAL INFORMATION GROUNDING 6 POWER WIRING 6 ACCESSORY WIRING 6 THERMOSTAT MOUNTING WIRING 6 DE HUMIDIFICATION CONTROL 7 FIELD CONNECTIONS CONTROL WIRING 7 INDOOR BLOWER SPEED SETTINGS 7 WIRING DIAGRA...

Page 2: ...en to alert the installer that severe per sonal injury death or equipment damage may result if instal lation procedures are not followed properly LIMITATIONS The unit should be installed in accordance...

Page 3: ...ined location 2 Remove the shipping carton and inspect for possible damage 3 Compressor tie down bolts should remain tightened 4 Position the unit on the base provided 5 Make a hole s in the structure...

Page 4: ...nstalled only with the tubing sizes for approved system com binations as specified in Tabular Data Sheet The charge given is applicable for total tubing lengths up to 15 feet See Application Data Form...

Page 5: ...g the service port flare caps to be sure they are leak tight DO NOT OVERTIGHTEN between 40 and 60 inch lbs maximum NOTE Do not use the system refrigerant in the outdoor unit to purge or leak test 9 Do...

Page 6: ...EC Class 2 from the thermostat to the indoor unit and outdoor unit Route the control wiring into the grommeted hole in the bottom of control box of the outdoor unit Using wire nuts connect to leads in...

Page 7: ...y to Y1 on the outdoor unit Do not connect to Y at the indoor control The first stage blower operation is controlled by the G signal It is critical the Y2 OUT signal is connected to Y at the air handl...

Page 8: ...TROL CLASS 2 WIRING POWER WIRING 208 230 1 60 GND LUG T2 T1 L2 L1 M1 BLK RED BRN YEL ORG PUR C R Y2 Y1 R Y2 Y1 G W1 W2 X L W2 W1 G Y C R 1 2 Y2 OUT X L C LOW HIGH FIGURE 6 WIRING FOR USE WITH SINGLE S...

Page 9: ...T USED 2 OUTDOOR UNIT WIRE NUT CONTACTOR THERMOSTAT P DU P XU 2 STAGE FURNACE TYPICAL TWO STAGE COOLING THERMOSTAT MUST BE USED DEHUMIDISTAT OPTIONAL POWER CONTROL FACTORY CLASS 1 WIRING TS CONTROL CL...

Page 10: ...ed with the matching thermostatic expansion valve kit listed in the tabular data sheet The best way to check the system charge is by check ing the system subcooling during the second stage of opera ti...

Page 11: ...15 of the pro grammed speed during the dehumidification mode This lower airflow reduces the evaporator temperature increasing the latent capacity The humidistat for these variable speed systems opens...

Page 12: ...maintenance Instruct the owner or the opera tor how to start stop and adjust temperature setting The installer should also instruct the owner on proper opera tion and maintenance of all other system...

Reviews: