7 RED FLASHES:

 This fault code indicates that the flame could not be

established. This no-light condition occurred 3 times (2 retries) during
the call for heat before locking out. Low gas pressure, faulty gas valve,
faulty hot surface igniter or burner problem may cause this. The furnace
will lock out for one hour and then restart.

8 RED FLASHES:

 This fault is indicated if the flame is lost 5 times (4

recycles) during the heating cycle. This could be caused by low gas
pressure or faulty gas valve. The furnace will lock out for one hour and
then restart.

9 RED FLASHES:

 Indicates reversed line voltage polarity or grounding

problem. Both heating and cooling operations will be affected. Check
polarity at furnace and branch. Check furnace grounding. Check that
flame probe is not shorted to chassis.

10 RED FLASHES:

 Gas valve energized with no call for heat. Check

gas valve and gas valve wiring.

11 RED FLASHES:

 This indicates that a primary or auxiliary limit switch

has opened its normally-closed contacts and has remained open for
more than five minutes. This condition is usually caused by a failed
blower motor or blower wheel.

STEADY ON RED: 

Control failure. Replace control board.

60-MINUTE AUTOMATIC RESET FROM LOCKOUT:

 This control

includes a “watchdog” type circuit that will reset from a lockout condition
after 60 minutes. Operational faults 6,7,8 will be reset. This provides
protection to an unoccupied structure if a temporary condition exists
causing a furnace malfunction. An example would be a low incoming
gas supply pressure preventing unit operation. When the gas pressure
is restored, at some point the “watchdog” would restart the unit and pro-
vide heat for the house.

NOTE: 

If a flame is detected the control flashes the LED for 1/8 of a

second and then enters a flame stabilization period.

DIAGNOSTIC FAULT CODE STORAGE AND 

RETRIEVAL

The control in this furnace is equipped with memory that will store up to
five error codes to allow a service technician to diagnose problems
more easily. This memory will be retained even is power to the furnace
is lost. 

This feature should only be used by a qualified service tech-

nician. 

The control stores up to five separate error codes. If more than five
error codes have occurred since the last reset, only the five most recent
will be retained. The furnace control board has a button, labeled "LAST
ERROR" that is used to retrieve error codes. This function will only work
if there are no active thermostat signals. So any call for heating, cooling
or continuous fan must be terminated before attempting to retrieve error
codes. 

To retrieve the error codes, push the LAST ERROR button. The LED on
the control will then flash the error codes that are in memory, starting
with the most recent. There will be a two-second pause between each
flash code. After the error codes have all been displayed, the LED will
resume the normal slow green flash after a five second pause. To
repeat the series of error codes, push the button again.

If there are no error codes in memory, the LED will flash two green
flashes. To clear the memory, push the LAST ERROR button and hold it
for more than five seconds. The LED will flash three green flashes when
the memory has been cleared, then will resume the normal slow green
flash after a five-second pause.

IGNITION CONTROL (P/N 031-01973-000)

Normal flame sense current is approximately

3.7 microamps DC (µa)

Low flame signal warning starts at 1.5 microamps.

Low flame signal control lockout point is

0.9 microamps DC (µa)

 FIGURE 11: 

Furnace Control Event Schedule

Thermostat Calling for Heat

Thermostat Satisfied

(Seconds)

THERMOSTAT

INDUCER

IGNITOR

MAIN VALVE

HUMIDIFIER

ELECTRONIC
AIR CLEANER

CIRCULATING
BLOWER

OFF

OFF

OFF

OFF

OFF

OFF

OFF

ON

ON

ON

ON

OFF

OFF

OFF

OFF

ON

ON

ON

OFF

OFF

OFF

OFF

OFF

OFF

OFF

15 Sec.
Post
Purge

Fan on Dela

y

30 Seconds

0 2

17

22

52

0

60, 90, 120, 180 SEC.
Selectable Fan Off Dela

y

Summary of Contents for GY8S160E30UH21

Page 1: ...ts that have been wet or the furnace if deemed necessary FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury death or prop erty damage Do not store or use...

Page 2: ...furnace casing making sure the physical support is sound without sagging cracks or gaps Examine the furnace base making sure it is physically sound without cracks gaps or sagging and has a good seal...

Page 3: ...Read the safety information above 2 Set the thermostat to the lowest setting 3 Turn off all electric power to the appliance 4 Remove furnace door 5 Move gas control switch to the OFF position Do not f...

Page 4: ...th air filters Table 1 will indicate 2 filters by using brackets with the number two 2 2 After you determine the cabinet size and what return configuration you have look up the recommended filter size...

Page 5: ...f the motor and wheel are heavily coated with dust they can be brushed and cleaned with a vac uum cleaner If the blower cannot be properly cleaned without removing it from the furnace then this servic...

Page 6: ...tor plate assem bly to the vestibule panel The surface is also gasketed The assembly including the flue baffle plate rear may be vacuumed or cleaned with hot water if necessary 3 The upper portion of...

Page 7: ...ated the number of times equal to the code For example six on flashes equals a number 6 fault code All flash code sequences are broken by a 2 sec ond off period SLOW GREEN FLASH Normal operation SLOW...

Page 8: ...CODE STORAGE AND RETRIEVAL The control in this furnace is equipped with memory that will store up to five error codes to allow a service technician to diagnose problems more easily This memory will be...

Page 9: ...ucts Group 9 SECTION III REPLACEMENT PARTS LIST NEUTRALS EAC COOL HEAT HUM PARK PARK L1 XFMR Y W R G C 37 36 28 43 46 2 25 9 4 45 7 33 38 34 8 15 1 16 32 5 27 6 3 39 22 23 18 31 14 35 29 10 47 41 44 1...

Page 10: ...R N Model PLATE RESTRICTOR L Model Style C PLATE RESTRICTOR L Model Style D 38 COLLAR FLUE 39 HANDLE DOOR 40 GASKET RESTRICTOR PLATE 41 TUBING SILICONE 42 SPRING DOOR 43 DIAGRAM WIRING 44 HARNESS WIRI...

Page 11: ...106306 UUM A 0205 Unitary Products Group 11 SECTION IV WIRING DIAGRAM FIGURE 12 Wiring Diagram...

Page 12: ...nly to products installed in the United States and Canada EXCLUSIONS This warranty does not cover any 1 Shipping labor or material charges 2 Damages resulting from transportation installation or servi...

Reviews: