York GY8S160E30UH21 User'S Information, Maintenance And Service Manual Download Page 6

106306-UUM-A-0205

6

Unitary Products Group

FURNACE CLEANING SECTION

NOTE: 

The cleaning operations listed below must be performed only by

a qualified service agency.

Burner Removal/Cleaning

The main burners should be checked periodically for dirt accumulation.
If cleaning is required, follow this procedure:

1.

Turn off the electrical power to the unit.

2.

Turn off the gas supply at the external manual shut-off valve and
loosen the ground union joint.

3.

Remove the upper access panel and remove the burner box cover.

4.

Disconnect wires from flame sensor, rollout switch and HSI igniter.
Remove igniter carefully, as it is easily broken.

5.

Remove the screws that hold the burner box assembly to the vest
panel and remove the assembly.

6.

Remove burners from the burner assembly.

7.

Burners may be cleaned by rinsing in hot water.

8.

Reassemble the burners in the reverse order.

Cleaning the Heat Exchanger

Lower Heat Exchanger Access

1.

Turn off the electrical power to the unit and turn off gas supply at
the shutoff valve.

2.

Remove the blower and burner compartment access doors. Dis-
connect the gas supply piping at the union to permit removal of the
entire burner and gas control assembly from the vestibule panel.
Use the wrench boss on the gas valve when removing or installing
this piping. See Figure 4.

3.

Unplug the igniter from the wire harness. Disconnect sensor and
rollout switch wires located on top of the air shield. Identify and
note the location of all leads for ease of reinstallation. Also discon-
nect the wires at the side rollout switches (upflow only) and the gas
valve wires.

4.

Remove the screws holding the burner assembly to the vestibule
panel and remove this assembly. Handle the assembly carefully
since it contains the igniter, which is fragile and easily broken. The
lower portion of the heat exchanger will now be exposed. To clean
the burner assembly, use a vacuum cleaner, or remove the burn-
ers as outlined in burner cleaning, and clean in hot water.

Upper Heat Exchanger Access

1.

Perform steps 1-4 above.

2.

Disconnect vent piping from the vent motor assembly at the top
panel on the furnace (upflow only). On downflow models, the vent
pipe is secured to the vent motor outlet with a screw. Remove this
screw before proceeding.

3.

Unplug the vent motor wires and ground wire. Remove the pres-
sure switch tubing at the top on the vent motor housing.

NOTE: 

It is recommended that replacement gaskets be available

before removing vent motor.

1.

Remove six mounting screws that hold the vent motor to the
restrictor plate. The surface is gasketed and the gasket can be
reused if it is carefully removed. It is necessary to remove this
assembly to gain access to the restrictor plate mounting holes.
The assembly may be vacuumed if cleaning is necessary. If any
vent assembly parts are damaged, replace with an entire new
assembly (except for gaskets).

2.

Remove the perimeter screws attaching the restrictor plate assem-
bly to the vestibule panel. The surface is also gasketed. The
assembly, including the flue baffle plate (rear) may be vacuumed
or cleaned with hot water if necessary.

3.

The upper portion of the heat exchanger is now accessible. With a
long flexible wire brush, clean inside each tube at both the top and
bottom. The brush must pass around the rear heat exchanger
tubes. Vacuum loose scale and dirt from each tube.

4.

Clean - Replace all components in reverse order. Re-gasket all
surfaces which required a gasket. Reconnect all wiring. Reattach
vent pipe and gas supply lines before restoring service to furnace.
Restore electrical power, check gas supply piping for leaks, and
then verify furnace operation.

SEQUENCE OF OPERATION

The following describes the sequence of operation of the furnace. Refer
to Figure 1 for component location.

Continuous Blower

Cooling/heating thermostats have a fan switch that has an ON and
AUTO position. In the ON position the thermostat circuit is completed
between terminals R and G. The motor will operate on the speed tap
wire that is connected to the cooling terminal on the control board.

Intermittent Blower

Cooling/heating thermostats have a fan switch that has an ON and
AUTO position. In the AUTO position the thermostat circuit is completed
between terminals R and G when there is a call for cooling and termi-
nals R and W when there is a call for heating. The integrated control will
energize the delay ON timer relay, which is a non-adjustable fan on
delay timer. The delay on timer relay will energize the indoor fan motor
relay after the delay ON time has expired. The indoor fan motor will be
turned off after the delay OFF time on the integrated control has
expired. The delay OFF time is adjustable by changing the jumper pin
setting on the integrated control. Refer to Figure 10 for the location of
the fan off adjustment jumper. The fan off setting is fixed at 60 seconds
for SEER enhancement.

Heating Cycle

When the thermostat switch is set on HEAT and the fan is set on AUTO,
and there is a call for heat, a circuit is completed between terminals R
and W of the thermostat. When the proper amount of combustion air is
being provided, the pressure switch will close, the ignition control pro-
vides a 17-second warm-up period, the gas valve then opens, the gas
starts to flow, ignition occurs and the flame sensor begins its sensing
function. The blower motor will energize 30 seconds after the gas valve
opens, if a flame is detected. Normal furnace operation will continue
until the thermostat circuit between R and W is opened, which causes
the ignition system and gas valve to de-energize and the burner flames
to be extinguished. The vent motor will operate for 15 seconds and the
blower motor will operate for the amount of time set by the fan-off delay
jumper located on the control board. See Figure 10. The heating cycle
is complete, and ready for the start of the next heating cycle.

Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and danger-
ous operation. Verify proper operation after servicing.

Summary of Contents for GY8S160E30UH21

Page 1: ...ts that have been wet or the furnace if deemed necessary FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury death or prop erty damage Do not store or use...

Page 2: ...furnace casing making sure the physical support is sound without sagging cracks or gaps Examine the furnace base making sure it is physically sound without cracks gaps or sagging and has a good seal...

Page 3: ...Read the safety information above 2 Set the thermostat to the lowest setting 3 Turn off all electric power to the appliance 4 Remove furnace door 5 Move gas control switch to the OFF position Do not f...

Page 4: ...th air filters Table 1 will indicate 2 filters by using brackets with the number two 2 2 After you determine the cabinet size and what return configuration you have look up the recommended filter size...

Page 5: ...f the motor and wheel are heavily coated with dust they can be brushed and cleaned with a vac uum cleaner If the blower cannot be properly cleaned without removing it from the furnace then this servic...

Page 6: ...tor plate assem bly to the vestibule panel The surface is also gasketed The assembly including the flue baffle plate rear may be vacuumed or cleaned with hot water if necessary 3 The upper portion of...

Page 7: ...ated the number of times equal to the code For example six on flashes equals a number 6 fault code All flash code sequences are broken by a 2 sec ond off period SLOW GREEN FLASH Normal operation SLOW...

Page 8: ...CODE STORAGE AND RETRIEVAL The control in this furnace is equipped with memory that will store up to five error codes to allow a service technician to diagnose problems more easily This memory will be...

Page 9: ...ucts Group 9 SECTION III REPLACEMENT PARTS LIST NEUTRALS EAC COOL HEAT HUM PARK PARK L1 XFMR Y W R G C 37 36 28 43 46 2 25 9 4 45 7 33 38 34 8 15 1 16 32 5 27 6 3 39 22 23 18 31 14 35 29 10 47 41 44 1...

Page 10: ...R N Model PLATE RESTRICTOR L Model Style C PLATE RESTRICTOR L Model Style D 38 COLLAR FLUE 39 HANDLE DOOR 40 GASKET RESTRICTOR PLATE 41 TUBING SILICONE 42 SPRING DOOR 43 DIAGRAM WIRING 44 HARNESS WIRI...

Page 11: ...106306 UUM A 0205 Unitary Products Group 11 SECTION IV WIRING DIAGRAM FIGURE 12 Wiring Diagram...

Page 12: ...nly to products installed in the United States and Canada EXCLUSIONS This warranty does not cover any 1 Shipping labor or material charges 2 Damages resulting from transportation installation or servi...

Reviews: