background image

515.28-N3Y

Unitary Products Group

9

REFRIGERANT LINE CHARGES

The outdoor condensing unit may be connected to the indoor 
evaporator coil using field supplied refrigerant grade copper 
tubing that is internally clean and dry. Units should be 
installed only with the tubing sizes for approved system com-
binations as specified in Tabular Data Sheet. The charge 
given is applicable for total tubing lengths up to 15 feet. See 
Application Data Form 690.01-AD1V for installing tubing of 
longer lengths and elevation differences.

NOTE:

 Using a larger than specified line size could result in 

oil return problems. Using too small a line will result in loss of 
capacity and other problems caused by insufficient refriger-
ant flow. Slope horizontal vapor lines at least 1" every 20 feet 
toward the outdoor unit to facilitate proper oil return.

Sweat connect units also include sufficient charge for 15 feet 
of lines. Table 2 lists the refrigerant line charges. 

The “TOTAL SYSTEM CHARGE” must be permanently 
stamped on the unit data plate.

Total system charge is determined as follows:

1.

Determine outdoor unit charge from tabular data sheet.

2.

Determine indoor coil adjustment from tabular data
sheet.

3.

Calculate the line charge with the factors in Table 2 for-
sweat lines in excess of 15 ft.

NOTE: 

The line charge over 15 feet should be included on the-
data plate and must be added to the system.

4.

Total system charge = item 1 + item 2 + item 3.

5.

Permanently stamp the unit data plate with the total
amount of refrigerant in the system.

USE THE FOLLOWING CHARGING METHOD WHENEVER 
ADDITIONAL REFRIGERANT IS REQUIRED FOR THE 
SYSTEM CHARGE.

Measurement Method

A calibrated charging cylinder or accurate weighing device 
must be used to add refrigerant. This is the only accurate 
charging method for heat pumps in the heat pump mode.

Check flare caps on service ports to be sure they are leak 
tight. DO NOT OVERTIGHTEN (between 40 and 60 inch-lbs. 
maximum).

Superheat Charging Method

NOTE:

 Use this method only during system maintenace and

repair

1.

Operate system until temperatures and pressures stabi-
lize (minimum of 10 minutes).

2.

Measure and record indoor wet bulb (WB) temperature
using a sling psychrometer and the outdoor dry bulb
(DB) temperature using a thermometer.

3.

Measure and record the suction pressure at the suction
service valve port.

4.

Using Table 3, note the superheat value corresponding
to the intersection of the indoor wet bulb and the outdoor
dry bulb.

5.

With the superheat value obtained in step 4 and the suc-
tion pressure value from step 3, find the intersection of
the values in Table 4. This is the required suction tube
tempera-ture at the suction service valve.

6.

To bring the tube temperature in line with the required
value from Table 4, add refrigerant to the service port to
cause the tube temperature to fall and reclaim refrigerant
to cause the temperature to rise.

Check flare caps on Schrader fittings to be sure they are 
tight. DO NOT OVERTIGHTEN (40-60 inch-lbs. maximum).

SYSTEM START-UP

ENERGIZE CRANKCASE HEATER

This unit is equipped with a crankcase heater for the com-
pressor.

A warning label with an adhesive back is supplied in the unit 
installation instruction packet. This label should be attached 
to the field supplied disconnect switch where it will be easily 
seen. See below.

In order to energize the crankcase heater:- Set indoor two 
stage cooling thermostat to "OFF" position.- Close the line 
power disconnect to the unit.  

SYSTEM OPERATION

See Figure 8 to trace the flow of refrigerant through the sys-
tem.

WITH POWER TO UNIT AND THERMOSTAT IN 

COOLING

 

POSITION.

1.

Reversing valve is energized through thermostat system
switch to position refrigerant circuit for cooling operation.
In the cooling cycle, discharge gas is pumped to the out-

Table 2: REFRIGERANT LINE CHARGES

LIQUID OD

VAPOR OD

R-22 CHARGE OZ./FT.

3/8"

5/8"

0.66

3/8"

3/4"

0.68

3/8"

7/8"

0.70

3/8"

1-1/8"

0.76

IMPORTANT

 An attempt to start the compressor without at least 8
hours of crankcase heat will damage the compressor.

Summary of Contents for E4FH018

Page 1: ...ECTRICAL CONNECTIONS 7 GENERAL INFORMATION GROUNDING 7 POWER WIRING 7 ACCESSORY WIRING 7 THERMOSTAT MOUNTING WIRING 7 EVACUATION 8 SYSTEM CHARGE 8 REFRIGERANT LINE CHARGES 9 MEASUREMEN T METHOD 9 SUPE...

Page 2: ...sonal injury and or equipment damage may result if installation pro cedures are not handled properly INSPECTION As soon as a unit is received it should be inspected for possi ble damage during transit...

Page 3: ...nsate will drain from beneath the coil of the outdoor unit during the defrost cycle Normally this condensate may be allowed to drain directly on the ground Elevate the unit sufficiently to prevent any...

Page 4: ...ths up to 15 feet See Application Data Form 690 01 AD1V for installing tubing of longer lengths and elevation differences NOTE Using a larger than specified line size could result in oil return proble...

Page 5: ...ened by removing the plunger cap and fully inserting a hex wrench into the stem and backing out counter clockwise until valve stem just touches retaining ring Replace plunger cap finger tight then tig...

Page 6: ...See Precautions Dur ing Brazing Angle Valves on page 6 11 If the refrigerant tubing indoor evaporator coil or outdoor condensing unit has developed a leak during shipment or was for any other reason o...

Page 7: ...ram and schematic wiring label is located on the inside surface of the unit electrical box cover and this instruction POWER WIRING 1 Install the proper size weatherproof disconnect switch outdoors and...

Page 8: ...ped a leak during shipment or was for any other rea son opened to the atmosphere If a leak is suspected leak test to locate the leak Repair the leak and test again To verify if the system has no leaks...

Page 9: ...between 40 and 60 inch lbs maximum Superheat Charging Method NOTE Use this method only during system maintenace and repair 1 Operate system until temperatures and pressures stabi lize minimum of 10 m...

Page 10: ...the test terminals on Yorkguard V terminal block for 3 seconds and releasing The lights will flash the code separated by a pause indi cating the failure mode shown in Table 3 8 To restore operation af...

Page 11: ...ow the cut off point the compressor operation cannot be justified due to small amount of heat generated 2 YORKGUARD senses this and performs the following functions a De energizes compressor circuit b...

Page 12: ...F for a continuous 3 minutes YORKGUARD V de energizes the fan relay and reversing valve relay to return unit to normal heating cycle INDICATIONS OF PROPER OPERATION COOLING Cooling operation is the s...

Page 13: ...motor is permanently lubricated and does not require periodic oiling 3 If the coil needs to be cleaned it should be washed with Calgon Coilclean mix one part Coilclean to seven parts water Allow solut...

Page 14: ...27 26 25 23 Evaporator Entering Air F Table 5 Temperature and Pressure SUCTION PRES SURE PSIG Service Port SUCTION SERVICE VALVE SUPERHEAT 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 61 5 35 37 3...

Page 15: ...35 108 220 02 49 82 389 64 109 26 79 141 30 94 179 06 109 223 17 50 84 03 65 111 23 80 143 63 95 181 80 110 226 35 51 85 69 66 113 22 81 145 99 96 184 56 111 229 56 52 87 38 67 115 24 82 148 37 97 18...

Page 16: ...ditioning Unitary Products Group 5005 York Drive Norman Oklahoma 73069 Subject to change without notice Printed in U S A Copyright by Unitary Products Group 1999 All rights reserved Supersedes 515 28...

Reviews: