background image

515.28-N3Y

5

Unitary Products Group

5.

Use PVC piping as a conduit for all underground installa-
tions as shown in Figure 4. Buried lines should be kept
as short as possible to minimize the build up of liquid
refrigerant in the vapor line during long periods of shut-
down

6.

Pack fiber glass insulation and a sealing material such
as permagum around refrigerant lines where they pen-
etrate a wall to reduce vibration and to retain some
flexibility.

7.

See Form 690.01-AD1V for additional piping informa-
tion..

PRECAUTIONS DURING BRAZING OF LINES

All outdoor unit and evaporator coil connections are copper-
to-copper and should be brazed with a phosphorous-copper 
alloy material such as Silfos-5 or equivalent. DO NOT use 
soft solder. The outdoor units have re-usable service valves 
on both the liquid and vapor connections. The total system 
refrigerant charge is retained within the outdoor unit during 
shipping and installation. The re-usable service valves are 
provided to evacuate and charge per this instruction.

Serious service problems can be avoided by taking adequate 
precautions to assure an internally clean and dry system..

PRECAUTIONS DURING BRAZING ANGLE VALVE 

Precautions should be taken to prevent heat damage to 
angle valve by wrapping a wet rag around it as shown in Fig-
ure 5. Also, protect all painted surfaces and insulation during 
brazing. After brazing - cool joint with wet rag.

Valve can be opened by removing the plunger cap and fully 
inserting a hex wrench into the stem and backing out counter-
clockwise until valve stem just touches retaining ring.  

Replace plunger  cap finger  tight,  then  tighten  an additional 
1/12 turn (1/2 hex flat). Cap must be replaced to prevent 
leaks.

 

Connect the refrigerant lines using the following procedure:

1.

Remove the cap and Schrader core from both the liquid
and vapor angle valve service ports at the outdoor unit.
Connect low pressure nitrogen to the liquid line service
port.

2.

Braze the liquid line to the liquid valve at the outdoor
unit. Be sure to wrap the valve body with a wet rag. Allow
the nitrogen to continue flowing.

 FIGURE 3 :   TUBING HANGER

 FIGURE 4 :   UNDERGROUND INSTALLATION

 Dry nitrogen should always be supplied through the
tubing while it is being brazed, because the tempera-
ture required is high enough to cause oxidation of the
copper unless an inert atmosphere is provided. The
flow of dry nitrogen should continue until the joint has
cooled. Always use a pressure regulator and safety
valve to insure that only low pressure dry nitrogen is
introduced into the tubing. Only a small flow is neces-
sary to displace air and prevent oxidation.

This is not a backseating valve. The service access
port has a valve core. Opening or closing valve does
not close service access port.

 If the valve stem is backed out past the retaining ring,
the O-ring can be damaged causing leakage or sys-
tem pressure could force the valve stem out of the
valve body possibly causing personal injury. In the
event the retaining ring is missing, do not attempt to
open the valve.

Summary of Contents for E4FH018

Page 1: ...ECTRICAL CONNECTIONS 7 GENERAL INFORMATION GROUNDING 7 POWER WIRING 7 ACCESSORY WIRING 7 THERMOSTAT MOUNTING WIRING 7 EVACUATION 8 SYSTEM CHARGE 8 REFRIGERANT LINE CHARGES 9 MEASUREMEN T METHOD 9 SUPE...

Page 2: ...sonal injury and or equipment damage may result if installation pro cedures are not handled properly INSPECTION As soon as a unit is received it should be inspected for possi ble damage during transit...

Page 3: ...nsate will drain from beneath the coil of the outdoor unit during the defrost cycle Normally this condensate may be allowed to drain directly on the ground Elevate the unit sufficiently to prevent any...

Page 4: ...ths up to 15 feet See Application Data Form 690 01 AD1V for installing tubing of longer lengths and elevation differences NOTE Using a larger than specified line size could result in oil return proble...

Page 5: ...ened by removing the plunger cap and fully inserting a hex wrench into the stem and backing out counter clockwise until valve stem just touches retaining ring Replace plunger cap finger tight then tig...

Page 6: ...See Precautions Dur ing Brazing Angle Valves on page 6 11 If the refrigerant tubing indoor evaporator coil or outdoor condensing unit has developed a leak during shipment or was for any other reason o...

Page 7: ...ram and schematic wiring label is located on the inside surface of the unit electrical box cover and this instruction POWER WIRING 1 Install the proper size weatherproof disconnect switch outdoors and...

Page 8: ...ped a leak during shipment or was for any other rea son opened to the atmosphere If a leak is suspected leak test to locate the leak Repair the leak and test again To verify if the system has no leaks...

Page 9: ...between 40 and 60 inch lbs maximum Superheat Charging Method NOTE Use this method only during system maintenace and repair 1 Operate system until temperatures and pressures stabi lize minimum of 10 m...

Page 10: ...the test terminals on Yorkguard V terminal block for 3 seconds and releasing The lights will flash the code separated by a pause indi cating the failure mode shown in Table 3 8 To restore operation af...

Page 11: ...ow the cut off point the compressor operation cannot be justified due to small amount of heat generated 2 YORKGUARD senses this and performs the following functions a De energizes compressor circuit b...

Page 12: ...F for a continuous 3 minutes YORKGUARD V de energizes the fan relay and reversing valve relay to return unit to normal heating cycle INDICATIONS OF PROPER OPERATION COOLING Cooling operation is the s...

Page 13: ...motor is permanently lubricated and does not require periodic oiling 3 If the coil needs to be cleaned it should be washed with Calgon Coilclean mix one part Coilclean to seven parts water Allow solut...

Page 14: ...27 26 25 23 Evaporator Entering Air F Table 5 Temperature and Pressure SUCTION PRES SURE PSIG Service Port SUCTION SERVICE VALVE SUPERHEAT 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 61 5 35 37 3...

Page 15: ...35 108 220 02 49 82 389 64 109 26 79 141 30 94 179 06 109 223 17 50 84 03 65 111 23 80 143 63 95 181 80 110 226 35 51 85 69 66 113 22 81 145 99 96 184 56 111 229 56 52 87 38 67 115 24 82 148 37 97 18...

Page 16: ...ditioning Unitary Products Group 5005 York Drive Norman Oklahoma 73069 Subject to change without notice Printed in U S A Copyright by Unitary Products Group 1999 All rights reserved Supersedes 515 28...

Reviews: