Table 4: - Superheat Value
INDOOR
WB
°°
F
*
OUTDOOR DB
°°
F
55
60
65
70
75
80
85
90
95
100
105
110
115
50
9
7
52
12
10
6
54
14
12
10
7
56
17
15
14
10
6
58
20
18
16
13
9
5
60
23
21
19
16
12
8
6
62
26
24
22
19
16
12
8
5
64
29
27
24
21
18
15
11
9
6
66
32
31
30
24
23
18
15
11
9
6
68
35
33
30
27
24
21
19
16
14
12
9
6
70
35
33
30
28
25
22
20
18
15
13
11
8
72
35
33
30
28
26
24
20
20
17
15
14
74
34
31
30
27
25
23
22
20
18
76
35
33
31
29
27
26
25
23
* .
Evaporator Entering Air
°°
F
Table 5: Temperature and Pressure
SUCTION PRES-
SURE PSIG
(Service Port)
SUCTION SERVICE VALVE SUPERHEAT
0
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
61.5
35
37
39
41
43
45
47
49
51
53
55
57
59
61
63
65
67
69
64.2
37
39
41
43
45
47
49
51
53
55
57
59
61
63
65
67
69
71
67.1
39
41
43
45
47
49
51
53
55
57
59
61
63
65
67
69
71
73
70.0
41
43
45
47
49
51
53
55
57
59
61
63
65
67
69
71
73
75
73.0
43
45
47
49
51
53
55
57
59
61
63
63
67
69
71
73
75
77
76.0
45
47
49
51
53
55
57
59
61
63
65
67
69
71
73
75
77
79
79.2
47
49
51
53
55
57
59
61
63
65
67
69
71
73
75
77
79
81
82.4
49
51
53
55
57
59
61
63
65
67
69
71
73
75
77
79
81
83