background image

515.28-N3Y

2

Unitary Products Group

GENERAL

The outdoor units are designed to be connected to a match-
ing indoor coil with sweat connect lines. Sweat connect units 
are factory charged with refrigerant for a matching indoor coil 
plus 15 feet of field supplied lines.

NOMENCLATURE

                                                                 E    4    FH   030  S   06

Product Category

E = Outdoor Split System 

            Heat Pump

Product Generation

4  = Design Level

Product Identifier

FH = High Efficiency Heat Pump

Nominal Cooling Capacity

018 = 1.5 Tons

042 = 3.5 Tons

024 = 2 Tons

048 = 4 Tons

030 = 2.5 Tons

060 = 5 Tons

036 = 3 Tons

Refrigerant Line Connections

S = Sweat-Fittings

Voltage Code

06 = 208/230-1-60

Matching indoor coils are available with a thermal expansion-
valve or an orifice liquid feed (YORKMATE flow control 
device) sized for the most common usage. The orifice size 
and/or refrigerant charge may need to be changed for some 
indoor-outdoor unit combinations, elevation differences or 
total line lengths. Refer to Application Data covering “General 
Piping Recommendations and Refrigerant Line Length” 
(Form 690.01-AD1V).

SAFETY

Use this instruction in conjunction with the instruction for the 
appropriate indoor evaporator coil, variable speed air handler  
or furnace and other accessories. Read all instructions before 
installing the unit.

Installer should pay particular attention to the words: NOTE, 
CAUTION and WARNING.

NOTES are intended to clarify or make the installation easier.

CAUTIONS are given to prevent equipment damage. 

WARNINGS are given to alert the installer that personal 
injury and/or equipment damage may result if installation pro-
cedures are not handled properly.

 

INSPECTION

As soon as a unit is received, it should be inspected for possi-
ble damage during transit. If damage is evident, the extent of 
the damage should be noted on the carrier’s delivery receipt. 
A separate request for inspection by the carrier’s agent 
should be made in writing. See Local Distributor for more 
information. 

LIMITATIONS

The unit should be installed in accordance with all national 
and local safety codes and the limitations listed below:

1.

Limitations for the indoor unit, coil and appropriate
accessories must also be observed.

2.

The outdoor unit must not be installed with any duct work
in the air stream. The outdoor fan is the propeller type
and is not designed to operate against any additional
external static pressure.

3.

The maximum and minimum conditions for operation
must be observed to assure a system that will give maxi-

mum performance with minimum service.

   

This product must be installed in strict compliance

with the enclosed installation instructions and any
applicable local, stat, and national codes including,
but not limited to, building, electrical and mechanical
codes. 

Incorrect installation may create a condition where the
operation of the product could cause personal injury
or property damage.

Table 1: Application Limitations

AIR TEMPERATURE 

°°

DB ON 

OUTDOOR COIL

AIR TEMPERATURE ON 

INDOOR COIL

Min.

Max.

Min.

Max.

Cool

Heat

Cool

Heat

°

WB 

Cool

°

DB 

Heat

°

WB 

Cool

°

DB 

Heat

50

-10

*

*.

Below -10°F, the unit operates automatically with resistance 
heat only.

115

75

57

50

†.

Operation below this temperature is permissible for a short 
period of time,during morning warm-up.

72

80

Summary of Contents for E4FH018

Page 1: ...ECTRICAL CONNECTIONS 7 GENERAL INFORMATION GROUNDING 7 POWER WIRING 7 ACCESSORY WIRING 7 THERMOSTAT MOUNTING WIRING 7 EVACUATION 8 SYSTEM CHARGE 8 REFRIGERANT LINE CHARGES 9 MEASUREMEN T METHOD 9 SUPE...

Page 2: ...sonal injury and or equipment damage may result if installation pro cedures are not handled properly INSPECTION As soon as a unit is received it should be inspected for possi ble damage during transit...

Page 3: ...nsate will drain from beneath the coil of the outdoor unit during the defrost cycle Normally this condensate may be allowed to drain directly on the ground Elevate the unit sufficiently to prevent any...

Page 4: ...ths up to 15 feet See Application Data Form 690 01 AD1V for installing tubing of longer lengths and elevation differences NOTE Using a larger than specified line size could result in oil return proble...

Page 5: ...ened by removing the plunger cap and fully inserting a hex wrench into the stem and backing out counter clockwise until valve stem just touches retaining ring Replace plunger cap finger tight then tig...

Page 6: ...See Precautions Dur ing Brazing Angle Valves on page 6 11 If the refrigerant tubing indoor evaporator coil or outdoor condensing unit has developed a leak during shipment or was for any other reason o...

Page 7: ...ram and schematic wiring label is located on the inside surface of the unit electrical box cover and this instruction POWER WIRING 1 Install the proper size weatherproof disconnect switch outdoors and...

Page 8: ...ped a leak during shipment or was for any other rea son opened to the atmosphere If a leak is suspected leak test to locate the leak Repair the leak and test again To verify if the system has no leaks...

Page 9: ...between 40 and 60 inch lbs maximum Superheat Charging Method NOTE Use this method only during system maintenace and repair 1 Operate system until temperatures and pressures stabi lize minimum of 10 m...

Page 10: ...the test terminals on Yorkguard V terminal block for 3 seconds and releasing The lights will flash the code separated by a pause indi cating the failure mode shown in Table 3 8 To restore operation af...

Page 11: ...ow the cut off point the compressor operation cannot be justified due to small amount of heat generated 2 YORKGUARD senses this and performs the following functions a De energizes compressor circuit b...

Page 12: ...F for a continuous 3 minutes YORKGUARD V de energizes the fan relay and reversing valve relay to return unit to normal heating cycle INDICATIONS OF PROPER OPERATION COOLING Cooling operation is the s...

Page 13: ...motor is permanently lubricated and does not require periodic oiling 3 If the coil needs to be cleaned it should be washed with Calgon Coilclean mix one part Coilclean to seven parts water Allow solut...

Page 14: ...27 26 25 23 Evaporator Entering Air F Table 5 Temperature and Pressure SUCTION PRES SURE PSIG Service Port SUCTION SERVICE VALVE SUPERHEAT 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 61 5 35 37 3...

Page 15: ...35 108 220 02 49 82 389 64 109 26 79 141 30 94 179 06 109 223 17 50 84 03 65 111 23 80 143 63 95 181 80 110 226 35 51 85 69 66 113 22 81 145 99 96 184 56 111 229 56 52 87 38 67 115 24 82 148 37 97 18...

Page 16: ...ditioning Unitary Products Group 5005 York Drive Norman Oklahoma 73069 Subject to change without notice Printed in U S A Copyright by Unitary Products Group 1999 All rights reserved Supersedes 515 28...

Reviews: