![York E4FH018 Installation Instructions Manual Download Page 3](http://html1.mh-extra.com/html/york/e4fh018/e4fh018_installation-instructions-manual_3758920003.webp)
515.28-N3Y
3
Unitary Products Group
UNIT INSTALLATION
LOCATION
Before starting the installation, select and check the suitability
of the location for both the indoor and outdoor unit. Observe
all limitations and clearance requirements.
The outdoor unit must have sufficient clearance for air
entrance to the condenser coil, for air discharge and for ser-
vice access. See Figure 1.
NOTE:
For multiple unit installatins, units must be spaced a
minimum of 18 inches apart. (Coil face to coil face.)
If the unit is to be installed on a hot sun exposed roof or a
black-topped ground area, the unit should be raised suffi-
ciently above the roof or ground to avoid taking the accumu-
lated layer of hot air into the outdoor unit.
Provide an adequate structural support.
GROUND INSTALLATION
The unit may be installed at ground level on a solid base that
will not shift or settle, causing strain on the refrigerant lines
and possible leaks. Maintain the clearances shown in Figure
1 and install the unit in a level position. Isolate the base from
the structure to avoid noise or vibration transmission.
Normal operating sound levels may be objectionable if the
unit is placed directly under windows of certain rooms (bed-
rooms, study, etc.).
Condensate will drain from beneath the coil of the outdoor
unit during the defrost cycle. Normally this condensate may
be allowed to drain directly on the ground.
Elevate the unit sufficiently to prevent any blockage of the air
entrances by snow in areas where there will be snow accu-
mulation. Check the local weather bureau for the expected
snow accumulation in your area.
ROOF INSTALLATION
When installing units on a roof, the structure must be capable
of supporting the total weight of the unit, including a pad, lin-
tels, rails, etc., which should be used to minimize the trans-
mission of sound or vibration into the conditioned space.
Isolate the unit from rain gutters to avoid any possible wash
out of the foundation.
FIGURE 1: TYPICAL INSTALLATION
THERMOSTAT
TO
BLOWER
MOTOR
RELAY
TO POWER
SUPPLY
NEC CLASS 1
WIRING
NEC CLASS 2
WIRING
TO
COIL
NOTE: ALL OUTDOOR WIRING
MUST BE WEATHERPROOF
SEAL OPENING(S) WITH PERMAGUM OR EQUIVALENT
24” SERVICE
ACCESS CLEARANCE
REQUIRED
WEATHERPROOF
DISCONNECT
SWITCH
48” OVERHEAD
CLEARANCE
REQUIRED
12” REAR
AND SIDES
CLEARANCE
REQUIRED
The outdoor unit should not be installed in an area
where mud or ice could cause personal injury.
Remember that condensate will drip from the unit coils
during heat and defrost cycles and that this conden-
sate will will freeze when the temperature of the out-
door air is below 32*F..
Sit unit on
rubber
elevator
grommets
to reduce
noise and
allow for
proper
drainage.