ORIFICE SELECTION

YORKMATE FLOW CONTROL COILS

NOTE: 

The proper orifice must be installed in the indoor coil liq-

uid connection prior to the connection of the refrigerant
lines.

   

Sweat coils are shipped with a standard orifice in a plastic 
bag attached to the liquid line connection or factory installed 
in the liquid line distributor. The standard orifice size is 
marked on the coil data plate.

The orifice that is shipped with the coil is based on the “most 
sold” combination, but it may have to be changed, depending 
on the capacity and efficiency of the outdoor unit, elevation 
differences, and/or long total line lengths. An additional ori-
fice (s) is shipped with most outdoor units in the literature 
packet for the most commonly required replacement combi-
nations. Other sizes must be ordered from the Parts Depart-
ment if required.

See the appropriate Tabular Data Sheet for the correct orifice 
size. If the orifice sizes match, nothing further is required and 
the refrigerant lines may be connected per the outdoor unit 
instruction. However, if another orifice should be used, see 
the coil instruction for details to change the orifice in the coil.

ELECTRICAL CONNECTIONS

GENERAL INFORMATION & GROUNDING 

Check the electrical supply to be sure that it meets the values 
specified on the unit nameplate and wiring label.

Power wiring, control (low voltage) wiring, disconnect 
switches and over current protection to be supplied by the 
installer. Wire size should be sized per NEC requirements.

The complete connection diagram and schematic wiring label 
is located on the inside surface of the unit electrical box cover 
and this instruction.

POWER WIRING

1.

Install the proper size weatherproof disconnect switch
outdoors and within sight of the unit.

2.

Run power wiring from the disconnect switch to the unit.

3.

Remove the control box cover to gain access to the unit
wiring. Route wires from disconnect through power wir-
ing opening provided and into the unit control box as
shown in Figure 6.

4.

Install the proper size time-delay fuses or circuit breaker,
and make the power supply connections.

5.

Energize the crankcase heater to save time by preheat-
ing the compressor oil while the remaining installation is
completed.    

ACCESSORY WIRING

The electrical accessories available for this unit are a two 
stage cooling thermostat and an optional De-humidification 
Control. Refer to the individual instructions packaged with the 
accessories for installation.

THERMOSTAT MOUNTING / WIRING

This condensing unit must be installed with the factory rec-
ommended thermostat, or any conventional heat pump ther-
mostat.  

The thermostat should be located about 5 ft. above the floor, 
where it will be exposed to normal room air circulation. Do not 
place it on an outside wall or where it is exposed to the radi-
ant effect from exposed glass or appliances, drafts from out-

Sweat coil is under 35 PSIG helium pressure.

All field wiring must USE COPPER CONDUCTORS
ONLY and be in accordance with Local, National Fire,
Safety & Electrical Codes. This unit must be grounded
with a separate ground wire in accordance with the
above codes.

 FIGURE 6 :   TYPICAL FIELD WIRING

POWER 
WIRING

GROUND 
LUG

CONTROL        
WIRING

All outdoor wiring must 
be weatherproof. Use 
copper conductors only.

CONNECTIONS TO

YORKGUARD "V"

Summary of Contents for E4FH018

Page 1: ...ECTRICAL CONNECTIONS 7 GENERAL INFORMATION GROUNDING 7 POWER WIRING 7 ACCESSORY WIRING 7 THERMOSTAT MOUNTING WIRING 7 EVACUATION 8 SYSTEM CHARGE 8 REFRIGERANT LINE CHARGES 9 MEASUREMEN T METHOD 9 SUPE...

Page 2: ...sonal injury and or equipment damage may result if installation pro cedures are not handled properly INSPECTION As soon as a unit is received it should be inspected for possi ble damage during transit...

Page 3: ...nsate will drain from beneath the coil of the outdoor unit during the defrost cycle Normally this condensate may be allowed to drain directly on the ground Elevate the unit sufficiently to prevent any...

Page 4: ...ths up to 15 feet See Application Data Form 690 01 AD1V for installing tubing of longer lengths and elevation differences NOTE Using a larger than specified line size could result in oil return proble...

Page 5: ...ened by removing the plunger cap and fully inserting a hex wrench into the stem and backing out counter clockwise until valve stem just touches retaining ring Replace plunger cap finger tight then tig...

Page 6: ...See Precautions Dur ing Brazing Angle Valves on page 6 11 If the refrigerant tubing indoor evaporator coil or outdoor condensing unit has developed a leak during shipment or was for any other reason o...

Page 7: ...ram and schematic wiring label is located on the inside surface of the unit electrical box cover and this instruction POWER WIRING 1 Install the proper size weatherproof disconnect switch outdoors and...

Page 8: ...ped a leak during shipment or was for any other rea son opened to the atmosphere If a leak is suspected leak test to locate the leak Repair the leak and test again To verify if the system has no leaks...

Page 9: ...between 40 and 60 inch lbs maximum Superheat Charging Method NOTE Use this method only during system maintenace and repair 1 Operate system until temperatures and pressures stabi lize minimum of 10 m...

Page 10: ...the test terminals on Yorkguard V terminal block for 3 seconds and releasing The lights will flash the code separated by a pause indi cating the failure mode shown in Table 3 8 To restore operation af...

Page 11: ...ow the cut off point the compressor operation cannot be justified due to small amount of heat generated 2 YORKGUARD senses this and performs the following functions a De energizes compressor circuit b...

Page 12: ...F for a continuous 3 minutes YORKGUARD V de energizes the fan relay and reversing valve relay to return unit to normal heating cycle INDICATIONS OF PROPER OPERATION COOLING Cooling operation is the s...

Page 13: ...motor is permanently lubricated and does not require periodic oiling 3 If the coil needs to be cleaned it should be washed with Calgon Coilclean mix one part Coilclean to seven parts water Allow solut...

Page 14: ...27 26 25 23 Evaporator Entering Air F Table 5 Temperature and Pressure SUCTION PRES SURE PSIG Service Port SUCTION SERVICE VALVE SUPERHEAT 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 61 5 35 37 3...

Page 15: ...35 108 220 02 49 82 389 64 109 26 79 141 30 94 179 06 109 223 17 50 84 03 65 111 23 80 143 63 95 181 80 110 226 35 51 85 69 66 113 22 81 145 99 96 184 56 111 229 56 52 87 38 67 115 24 82 148 37 97 18...

Page 16: ...ditioning Unitary Products Group 5005 York Drive Norman Oklahoma 73069 Subject to change without notice Printed in U S A Copyright by Unitary Products Group 1999 All rights reserved Supersedes 515 28...

Reviews: