036-21318-002 Rev. A (0106)
2
Unitary Products Group
Physical and Electrical Data - 1 Phase
MODEL
EBBA-F018S EBBA-F024S EABA-F030S EABA-F036S EABA-F042S EBBA-F048S EABA-F060S
Unit Supply Voltage
208/230 – 1 – 60
Normal Voltage Range
1
187 to 252
Minimum Circuit Ampacity
11.8
14.9
19.0
23
28.5
31.7
40.7
Max. Overcurrent Device Amps
2
20
25
30
40
40
55
60
Compressor Type
3
Recip
Recip
Recip
Recip
Recip
Scroll
B
Scroll
C
Compressor Amps
Rated Load
9.0
11.5
14.1
17.3
21.7
24.3
31.5
Locked Rotor
48
60
73
94
105
140
169
Crankcase Heater
Yes
Yes
Yes
Yes
Yes
No
No
Fan Motor Amps
Rated Load
0.5
0.5
1.4
1.4
1.3
1.3
1.3
Fan Diameter Inches
18
18
18
18
22
22
22
Fan Motor
Rated HP
1/12
1/12
1/4
1/4
1/4
1/4
1/4
Nominal RPM
1,100
1,100
1,100
1,100
850
850
850
Nominal CFM
1,850
1,850
2,750
2,750
3,150
3,350
3,350
Coil
Face Area Sq. Ft.
9.15
12.58
12.58
12.58
15.72
19.65
23.58
Rows Deep
1
1
1
1
1
1
1
Fin / Inches
13
13
14
14
13
13
13
Liquid Line OD
3/8
3/8
3/8
3/8
3/8
3/8
3/8
Vapor Line OD
3/4
3/4
3/4
3/4
3/4
7/8
7/8
Unit Charge (Lbs. - Oz.)
4
4 - 14
5 - 0
4 - 8
5 - 12
6 - 9
8 - 3
9 - 8
Charge Per Foot, Oz.
0.68
0.68
0.68
0.68
0.68
0.70
0.70
Operating Weight Lbs.
131
141
154
159
172
204
217
Physical and Electrical Data - 3 Phase
MODEL
EABA-
T036S
EBBA-
T048S
EABA-
T060S
EABA-
T090S
EABA-
W036S
EBBA-
W048S
EABA-
W060S
EABA-
W090S
Unit Supply Voltage
208/230-3-60
460 - 3 - 60
Normal Voltage Range
1
187 to 252
432 to 504
Minimum Circuit Ampacity
15.0
18.9
24.5
40.6
8.0
10.1
12.0
20.7
Max. Qvercurrent Device Amps
2
25
30
40
60
15
15
20
35
Compressor Type
3
Inertia
Scroll
B
Scroll
C
Scroll
C
Inertia
Scroll
B
Scroll
C
Scroll
C
Compressor Amps Rated Load
10.9
14.1
18.6
28.8
5.8
7.0
9.0
14.7
Locked Rotor
78
125
128
195
40
55
63
95
Crankcase Heater
Yes
No
No
No
Yes
No
No
No
Fan Motor Amps
Rated Load
1.4
1.3
1.3
4.6
.8
.7
.8
2.3
Fan Diameter Inches
18
22
24
24
18
22
24
24
Fan Motor
Rated HP
1/4
1/4
1/4
3/4
1/4
1/5
1/4
3/4
Nominal RPM
1,100
850
850
1100
1,100
825
850
1100
Nominal CFM
2,750
3,500
3,100
5000
2,750
3,500
3,100
5000
Coil
Face Area Sq. Ft.
12.58
19.65
18.00
22.5
12.58
19.65
18.00
22.5
Rows Deep
1
1
2
2
1
1
2
2
Fin / Inches
14
13
14
16
14
13
14
16
Liquid Line OD
3/8
3/8
3/8
1/2
3/8
3/8
3/8
1/2
Vapor Line OD
3/4
7/8
7/8
1-1/8
3/4
7/8
7/8
1-1/8
Unit Charge (Lbs. - Oz.)
4
5 - 12
8 - 3
11 - 3
16
5 - 12
8 - 3
11 - 3
16
Charge Per Foot, Oz.
.68
.70
.70
1.26
.68
.70
.70
1.26
Operating Weight Lbs.
178
232
243
354
178
232
243
354
1. Rated in accordance with ARI Standard 110, utilization range “A”.
2. Dual element fuses or HACR circuit breaker.
3. All scrolls listed with a superscript “B” are Bristol scrolls. All scrolls listed with a superscript “C” are Copeland scrolls.
4. The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than
15 feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.