036-21318-002 Rev. A (0106)
Unitary Products Group
27
Multipliers for determining the performance with other indoor sections.
HEATING PERFORMANCE DATA
CONDENSING UNIT MODEL NO
EABA-F060S
EVAPORATOR COIL MODEL NO
F2FP060
AIR TEMP.
ENTERING
OUTDOOR
UNIT
AIR TEMP.
ENTERING
INDOOR
COIL
ID CFM
1550
1750
1950
MBTUH
KW
C.O.P.
MBTUH
KW
C.O.P.
MBTUH
KW
C.O.P.
60
60
64.7
5.61
3.38
62.9
5.42
3.41
61.1
5.26
3.40
70
66.2
5.85
3.32
64.9
5.64
3.38
63.5
5.47
3.40
80
66.2
6.83
2.84
65.4
6.54
2.93
64.4
6.34
2.98
47
60
56.3
5.41
3.05
55.9
5.27
3.11
53.9
5.18
3.05
70
56.8
5.64
2.95
57.0
5.50
3.04
55.3
5.42
3.00
80
56.3
6.44
2.56
57.0
6.27
2.66
55.8
6.17
2.65
40
60
52.4
5.17
2.97
53.0
5.19
2.99
50.8
5.13
2.91
70
52.9
5.57
2.79
53.0
5.52
2.82
52.5
5.49
2.81
80
52.6
6.22
2.48
52.1
6.07
2.52
53.3
6.06
2.58
30
60
48.6
5.12
2.78
48.9
5.07
2.83
48.7
5.01
2.85
70
47.3
5.55
2.50
47.7
5.49
2.55
47.8
5.45
2.57
80
45.4
5.88
2.27
46.0
5.80
2.33
46.5
5.78
2.36
17
60
37.5
4.67
2.36
38.6
4.72
2.40
36.5
4.71
2.27
70
36.3
4.93
2.16
37.4
4.95
2.22
35.6
4.94
2.11
80
35.2
5.30
1.95
36.2
5.26
2.02
34.7
5.26
1.93
10
60
33.0
4.50
2.15
34.3
4.52
2.22
34.6
4.50
2.25
70
31.5
4.72
1.95
32.6
4.73
2.02
33.0
4.73
2.04
80
30.2
4.89
1.81
31.1
4.90
1.86
31.6
4.91
1.89
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handler
Coil
MBH
KW
COP
N1AHD2006
G2FD060(S,H)24
0.99
0.97
1.02
G2FD060(S,H)24
0.99
0.97
1.02
G1HD060
1.00
0.98
1.02
G1NA060S24T
1.02
0.98
1.04
G1UA060S21,24
0.99
0.97
1.02
G1FA060S21,24
0.99
0.97
1.02