GUIDE SPECIFICATIONS

GENERAL

Units shall be manufactured by Unitary Products in an ISO 
9001 certified facility.

York's Sunline Ultra™ units are convertible single package 
units. All models have dual independent refrigerant circuits 
for efficient part load operation and maximum comfort con-
trol. Although the units are primarily designed for curb 
mounting on a roof, they can also be slab-mounted at 
ground level or set on steel beams above a finished roof. 
Cooling only, cooling with gas heat and cooling with electric 
heat models are available with a wide variety of factory-
mounted options and field-installed accessories to make 
them suitable for almost every application. All units are self-
contained and assembled on full perimeter base rails with 
holes in the four corners for overhead rigging. Every unit is 
completely piped, wired, charged and tested at the factory 
to simplify the field installation and to provide years of 
dependable operation. All models (including those with an 
economizer) are suitable for either bottom or horizontal duct 
connections. Models with power exhaust are suitable for 
bottom duct connections only. For bottom duct, remove the 
sheet metal panels from the supply and return air openings 
through the base of the unit. For horizontal duct, replace the 
supply and return air panels on the rear of the unit with a 
side duct flange accessory. All supply air blowers are 
equipped with a belt drive that can be adjusted to meet the 
exact requirements of the job. A high static drive option is 
available for applications with a higher CFM and/or static 
pressure requirement.

Each unit shall have 2 condenser fan motors. All compres-
sors include crankcase heat and internal pressure relief. 
Every refrigerant circuit includes an expansion valve, a liq-
uid line filter-drier, a discharge line high pressure switch and 
a suction line with a freezestat and low pressure/loss of 
charge switch. The unit control circuit includes a 75 VA 
transformer, a 24-volt circuit breaker and a relay board with 
two compressor lockout circuits, a terminal strip for thermo-
stat wiring, plus an additional set of pin connectors to sim-
plify the interface of additional field controls. All models are 
CSA approved. All models include a 1-year limited warranty 
on the complete unit. Compressors and electric heater ele-
ments carry an additional 4-year warranty. Aluminized steel 
tubular heat exchangers carry an additional 9-year warranty.

DESCRIPTION

Units shall be factory-assembled, single packaged, DH***N 
Electric Cooling/Gas Heat, DH***C/E Electric Cooling/
Optional Electric Heat, designed for outdoor mounted instal-
lation. The 15 ton units shall have minimum EER ratings of 
10.8, the 17.5 ton units shall have minimum EER ratings of 
10.2, the 20 ton units shall have minimum EER ratings of 9.7 
and the 25 ton units shall have minimum EER ratings of 9.6.

They shall have built-in field convertible duct connections 
for down discharge supply/return or horizontal discharge 

supply/return, and be available with factory installed options 
or field installed accessories. The units shall be factory 
wired, piped, charged with R-22 refrigerant and factory 
tested prior to shipment. All unit wiring shall be both num-
bered and color coded. All units shall be manufactured in a 
facility certified to ISO 9001 standards and the cooling per-
formance shall be rated in accordance with DOE and ARI 
test procedures. Units shall be CSA listed, classified to 
ANSIZ21.47 standards, UL 1995/CAN/CSA No. 236-M90 
conditions. 

UNIT CABINET

Unit cabinet shall be constructed of galvanized steel, with 
exterior surfaces coated with a non-chalking, powdered 
paint finish, certified at 1000 hour salt spray test per ASTM-
B117 standards. Indoor blower section shall be insulated 
with a minimum 1/2" thick insulation, coated on the airside. 
Aluminum foil faced insulation shall be used in the furnace 
compartment and be fastened with ridged fasteners to pre-
vent insulation from entering the air stream. Cabinet panels 
shall be "large" size, easily removable for servicing and 
maintenance. Full perimeter base rails shall be provided to 
assure reliable transit of equipment, overhead rigging and 
proper sealing on roof curb applications. Disposable 2" fil-
ters shall be furnished and be accessible through a remov-
able access door, sealed airtight. Units filter track shall be 
designed to accommodate either 2" or 4" filters. Fan perfor-
mance measuring ports shall be provided on the outside of 
the cabinet to allow accurate air measurements of evapora-
tor fan performance without removing panels or creating air 
by-pass of the coils. Condensate pan shall be internally 
sloped and conform to ASHRAE 62-89 self-draining stan-
dards. Condensate connection shall be a minimum of 1" I.D. 
female and be a ridged mount connection. Unit shall incor-
porate a fixed outdoor air damper with an outdoor air intake 
opening covered with a bird screen and a rain hood painted 
to match the exterior of the unit. 

INDOOR (EVAPORATOR) FAN ASSEMBLY 

Fan shall be a belt drive assembly and include an adjustable- 
pitch motor pulley. Job site selected (B.H.P.) brake horse-
power shall not exceed the motors nameplate horsepower 
rating, plus the service factor. Units shall be designed not to 
operate above service factor. Fan wheel shall be double-inlet 
type with forward-curved blades, dynamically balanced to 
operate smoothly throughout the entire range of operation. 
Airflow design shall be constant air volume.

A variable air volume (VAV) option using a variable frequency 
drive (VFD) is available for applications requiring a constant 
supply duct static pressure. Units equipped for VAV shall be 
controlled by a duct pressure transducer with a 0 - 5” WC pres-
sure range. The pressure transducer shall provide a 0 - 5 VDC 
output signal to a VAV control board which, in turn shall provide 
a 2 - 10 VDC speed reference signal to the VFD. The VAV 
control board shall operate using factory-installed Supply 
Air, Return Air and Outside Air Temperature Sensors. Units 
equipped with VFD’s shall have factory-installed manual 
bypass as an option.

Summary of Contents for DH 180

Page 1: ...cally sealed scroll compressors with crankcase heaters Two stage heating provided by dual independent heat exchangers with aluminized steel tubes redundant gas valves spark ignition with induced draft...

Page 2: ...17 5 TON COOLING ONLY 210 MBH BOTTOM DUCT CONNECTIONS 21 11 SUPPLY AIR BLOWER PERFORMANCE 20 TON COOLING ONLY 240 MBH BOTTOM DUCT CONNECTIONS 22 12 SUPPLY AIR BLOWER PERFORMANCE 15 TON GAS HEAT 180 M...

Page 3: ...r all units These four digits will not be assigned until a quote is requested or an order placed CPC Controller DFS APS Johnson Controller UNT 1126 N2 protocol DFS APS Honeywell Controller DFS APS Nov...

Page 4: ...ypass valve is available for low cooling load applications Simplicity Controls Simplicity control boards have standardized a number of features previously available only as options or by utilizing add...

Page 5: ...motor actuator capa ble of introducing up to 100 outdoor air with nominal 1 leakage type dampers The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is c...

Page 6: ...rogrammed from the factory An optional factory installed manual bypass switch available with factory installed VFD can be found in the Blower Motor Access compartment The switch can be used to either...

Page 7: ...anced Rooftop building auto mation system controller is factory installed Includes supply air sensor return air sensor dirty filter indicator switch and air proving switch HONEYWELL BAS CONTROL The Ho...

Page 8: ...natural gas furnace to propane HIGH ALTITUDE PROPANE Burner orifices and pilot orifices are provided for proper furnace operation at alti tudes up to 6 000 feet This accessory supplements the basic p...

Page 9: ...power input in watts expressed in Btuh per watt Btuh watt IPLV3 3 IPLV Integrated part load value COOLING ONLY DH180C00 1784 4 Deduct 2 MBH 208V 10 8 11 3 DH210C00 205 10 2 10 8 DH240C00 223 9 7 10 2...

Page 10: ...7 119 5 82 2 186 8 12 3 186 8 186 8 186 8 149 5 112 2 75 0 57 191 0 10 5 191 0 191 0 191 0 153 8 116 5 79 3 183 7 12 3 183 7 183 7 183 7 146 5 109 2 71 9 AIR ON EVAPORATOR COIL TEMPERATURE OF AIR ON...

Page 11: ...77 194 0 18 0 138 6 91 2 62 0 72 179 0 17 1 151 3 122 2 93 0 63 8 67 164 0 16 2 164 0 153 2 124 0 94 8 65 7 62 154 0 16 3 154 0 154 0 154 0 124 8 95 7 66 5 57 150 0 16 6 150 0 150 0 150 0 120 8 91 7 6...

Page 12: ...183 0 139 5 96 0 215 3 15 2 215 3 215 3 215 3 171 9 128 4 84 9 57 222 0 13 9 222 0 222 0 222 0 178 5 135 0 91 6 212 7 15 2 212 7 212 7 212 7 169 3 125 8 82 3 AIR ON EVAPORATOR COIL TEMPERATURE OF AIR...

Page 13: ...4 76 4 216 8 23 0 173 6 106 4 72 4 72 211 0 20 7 182 0 148 0 114 0 80 0 198 6 22 5 177 0 143 0 109 0 74 9 67 192 1 20 2 192 1 185 6 151 6 117 6 83 6 180 4 22 0 180 4 179 5 145 5 111 5 77 5 62 179 1 19...

Page 14: ...8 133 1 269 2 12 4 269 2 269 2 269 2 219 6 169 9 120 2 57 278 9 10 6 278 9 278 9 278 9 229 2 179 5 129 8 267 1 12 2 267 1 267 1 267 1 217 4 167 7 118 0 AIR ON EVAPORATOR COIL TEMPERATURE OF AIR ON CO...

Page 15: ...235 0 22 8 228 5 150 8 100 0 72 224 0 22 4 220 8 181 9 143 0 104 1 67 213 0 22 0 213 0 213 0 186 0 147 1 108 2 62 210 0 21 6 210 0 210 0 209 0 170 1 131 2 92 4 57 208 0 21 4 208 0 208 0 208 0 169 1 1...

Page 16: ...5 6 93 5 291 6 21 8 291 6 291 6 282 0 219 9 157 8 95 7 57 288 7 20 1 288 7 288 7 288 7 226 6 164 5 102 4 286 1 21 8 286 1 286 1 286 1 224 0 161 9 99 8 AIR ON EVAPORATOR COIL TEMPERATURE OF AIR ON COND...

Page 17: ...0 77 310 4 29 4 227 1 134 6 86 0 72 282 2 28 6 240 5 191 9 143 3 94 7 67 254 0 27 8 254 0 249 2 200 6 152 0 103 4 62 249 7 27 2 249 7 249 7 248 4 199 8 151 2 102 6 57 244 9 27 3 244 9 244 9 234 9 186...

Page 18: ...the static pressure and BHP Since no temperature data is given we will assume an air temperature of 70 F Table 8 shows the correction factor to be 0 832 Corrected static pressure 1 5 x 0 832 1 248 IWC...

Page 19: ...262260 YTG E 1008 Johnson Controls Unitary Products 19 FIGURE 2 ALTITUDE TEMPERATURE CONVERSION FACTOR...

Page 20: ...0 0 9 5 2 4 7 0 7 5 7 5 1 208 VOLT AND HIGH STATIC DRIVE 965 6 0 1 2 2 9 2 6 1 0 3 6 3 2 0 8 4 0 3 6 0 5 4 7 4 2 0 4 5 0 4 4 980 5 5 1 3 3 0 2 7 1 1 3 7 3 3 0 9 4 1 3 7 0 6 4 8 4 3 0 5 5 1 4 6 1025 4...

Page 21: ...4 5 9 5 0 980 5 0 1 6 5 3 4 5 1 4 5 8 4 9 1 2 6 3 5 3 0 7 6 9 5 8 1010 4 0 1 8 5 8 4 9 1 7 6 3 5 3 1 5 6 9 5 8 1 0 7 5 6 3 1020 3 5 1 9 6 1 5 1 1 8 6 5 5 5 1 6 7 1 6 0 1 1 7 8 6 6 1035 3 0 2 0 6 2 5...

Page 22: ...9 1 2 6 3 5 3 0 7 6 9 5 8 0 2 7 3 6 1 1010 4 0 1 8 5 8 4 9 1 7 6 3 5 3 1 5 6 9 5 8 1 0 7 5 6 3 0 5 7 9 6 7 1020 3 5 1 9 6 1 5 1 1 8 6 5 5 5 1 6 7 1 6 0 1 1 7 8 6 6 0 6 8 3 7 0 1035 3 0 2 0 6 2 5 2 1 9...

Page 23: ...8 3 4 1 0 4 4 3 9 0 8 5 0 4 5 0 6 5 6 5 0 208 VOLT AND HIGH STATIC DRIVE 965 6 0 1 2 2 7 2 5 0 9 3 2 2 9 0 6 3 7 3 3 0 4 4 4 3 9 0 2 5 0 4 5 980 5 5 1 3 2 9 2 6 1 0 3 4 3 0 0 7 3 8 3 4 0 5 4 5 4 0 0 3...

Page 24: ...5 1 0 2 6 9 5 8 980 5 0 1 9 4 5 3 8 1 5 5 4 4 5 1 0 6 3 5 3 0 4 7 2 6 1 995 4 5 2 1 4 5 3 9 1 6 5 5 4 7 1 1 6 4 5 4 0 5 7 5 6 3 1025 3 5 2 3 4 9 4 1 1 8 5 8 4 9 1 3 6 7 5 7 0 7 8 0 6 7 1050 2 5 2 5 5...

Page 25: ...980 5 0 1 9 4 5 3 8 1 5 5 4 4 5 1 0 6 3 5 3 0 4 7 2 6 1 0 1 8 5 7 1 995 4 5 2 1 4 5 3 9 1 6 5 5 4 7 1 1 6 4 5 4 0 5 7 5 6 3 0 2 8 6 7 3 1025 3 5 2 3 4 9 4 1 1 8 5 8 4 9 1 3 6 7 5 7 0 7 8 0 6 7 1050 2...

Page 26: ...7 11 2 1215 4 0 2 7 8 6 7 0 2 1 10 4 8 5 1 4 12 3 10 1 0 6 14 3 11 7 1255 3 0 3 0 9 1 7 4 2 4 11 0 9 0 1 7 12 9 10 6 0 9 15 0 12 3 1290 2 0 3 2 9 5 7 8 2 7 11 5 9 4 2 0 13 5 11 1 1 2 15 6 12 8 1330 1...

Page 27: ...TION RESISTANCE IWG CFM 15 TON 17 5 TON 20 TON 25 TON 4500 6000 7200 6000 8000 9000 6000 7000 9400 7500 10000 12500 WET COIL 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 ELECTRIC HEAT OPTIONS DH mo...

Page 28: ...5 6 190 4 5 20 0 0 0 None 86 6 110 E18 13 5 1 37 5 86 6 110 E36 27 2 74 9 118 7 125 E54 40 6 2 112 7 165 9 175 E72 54 1 2 150 2 175 2 200 230 3 60 25 6 190 4 3 20 0 0 0 None 86 2 110 E18 18 0 1 43 3 8...

Page 29: ...86 6 102 9 110 575 12 4 80 1 7 10 0 0 0 None 41 3 50 E18 18 0 1 17 3 41 3 50 E36 36 0 2 34 6 55 8 60 E54 54 0 2 52 0 64 5 70 E72 72 0 2 69 3 81 8 90 TABLE 21 DH 300 ELECTRICAL DATA HIGH STATIC MOTOR...

Page 30: ...6 190 4 5 20 0 10 0 None 96 6 110 E18 13 5 1 37 5 96 6 110 E36 27 2 74 9 131 2 150 E54 40 6 2 112 7 178 4 200 E72 54 1 2 150 2 187 7 200 230 3 60 25 6 190 4 3 20 0 10 0 None 96 2 110 E18 18 0 1 43 3...

Page 31: ...86 6 109 1 110 575 12 4 80 1 7 10 0 4 0 None 45 3 50 E18 18 0 1 17 3 45 3 50 E36 36 0 2 34 6 60 8 70 E54 54 0 2 52 0 69 5 70 E72 72 0 2 69 3 86 8 90 TABLE 24 DH 300 ELECTRICAL DATA HIGH STATIC MOTOR...

Page 32: ...e heating is not required on units with a single stage electric heater 4Terminals A1 and A2 provide a relay output to close the outdoor economizer dampers when the thermostat switches to the set back...

Page 33: ...25 X 2 or 4 4 4 4 Quantity Per Unit 18 X 24 X 2 or 4 5 Total Face Area sq ft 15 0 20 0 20 0 20 0 CHARGE Refrigerant 22 lbs oz System 1 23 10 24 0 24 2 21 1 System 2 21 10 24 8 27 2 21 1 TABLE 28 OPERA...

Page 34: ...illustrate Bottom Duct openings Power and Gas Piping Connection locations 12 1 2 9 1 4 8 1 8 9 3 4 3 3 4 B POWER WIRING ENTRY A CONTROL WIRING ENTRY CONDENSER COILS OPTIONAL COIL GUARD KIT COMPRESSOR...

Page 35: ...n The covering consists of a heavy black paper composition 3 Replace the side supply and return air compartment panels For side duct applications 1 Replace the side panels on the supply and return air...

Page 36: ...CLEARANCES LOCATION CLEARANCE Front 36 Rear 24 Less Economizer 49 With Economizer Left Side Filter Access 24 Less Economizer 36 With Economizer 3 Right Side Cond Coil 36 Below Unit1 1 Units may be in...

Page 37: ...262260 YTG E 1008 Johnson Controls Unitary Products 37 FIGURE 7 UNIT CENTER OF GRAVITY 17 5 20 25 Ton FIGURE 8 TYPICAL UNIT APPLICATIONS...

Page 38: ...563 DH240N32 2340 548 596 623 573 DH300C00 2345 461 502 720 662 DH300N24 2545 501 545 781 718 DH300N32 2585 509 553 794 729 TABLE 33 DH 180 210 240 300 6 POINT LOAD WEIGHT DISTRIBUTION UNIT MODEL OPE...

Page 39: ...ducts allows ductwork penetration between roof joists that are spaced on 72 centers NOTE Ducts can be installed into the curb from the roof All electrical and gas line connections can be made inside t...

Page 40: ...S CONTROL TERMINAL BLOCK TERMINALS ON A LIMITED NUMBER OF THERMOSTATS 3 1 2 4 3 1 2 4 Second stage heating not required on single stage heating units Second stage cooling not required on single stage...

Page 41: ...ct connections for down discharge supply return or horizontal discharge supply return and be available with factory installed options or field installed accessories The units shall be factory wired pi...

Page 42: ...on thermostat evaporator coil If any of the above safety devices trip a LED light emitting diode indicator shall flash a diagnostic code that indicates which safety switch has tripped d Unit shall inc...

Page 43: ...oor return air streams are available to provide free cooling based on single enthalpy or dual enthalpy configura tions respectively If free cooling is available a call for cooling shall modulate the e...

Page 44: ...COIL GUARD KIT Guard for cooling coil OTHER FACTORY INSTALLED OPTIONS POWER EXHAUST OPTION To work in conjunction with economizers STAINLESS STEEL HEAT EXCHANGER STAINLESS STEEL DRAIN PAN TECHNICOAT P...

Reviews: