background image

262260-YTG-E-1008

Johnson Controls Unitary Products

43

controls, shall be capable of operation down to 0° F outdoor 
temperature. Unit shall be provided with fan time delay to 
prevent cold air delivery before heat exchanger warms up 
(Gas heat only). 

ELECTRICAL REQUIREMENTS

All unit power wiring shall enter unit cabinet at a single factory 
provided location and be capable of side or bottom entry, to 
minimize roof penetrations and avoid unit field modifications. 
Separate side and bottom openings shall be provided for the 
control wiring. 

STANDARD LIMITED WARRANTIES

Compressor 5 Years

Heat Exchanger 10 Years

Electric Heat Element 5 Years

Other Parts 1 Year

OPTIONAL OUTDOOR AIR

 (Shall be made available by 

either/or): 

ELECTRONIC ENTHALPY AUTOMATIC ECONO-
MIZER

 - Outdoor and return air dampers that are inter-

locked and positioned by a fully-modulating, spring-
return damper actuator. The maximum leakage rate for 
the outdoor air intake dampers shall not exceed 2% 
when dampers are fully closed and operating against a 
pressure differential of 0.5 IWG. A unit-mounted potenti-
ometer shall be provided to adjust the outdoor and return 
air damper assembly to take in CFM of outdoor air to 
meet the minimum ventilation requirement of the condi-
tioned space during normal operation. During econo-
mizer operation, a mixed-air temperature control shall 
modulate the outdoor and return air damper assembly to 
prevent the supply air temperature from dropping below 
55°F. Changeover from compressor to economizer oper-
ation shall be provided by an integral electronic enthalpy 
control that feeds input into the basic module. The out-
door intake opening shall be covered with a rain hood 
that matches the exterior of the unit. Water eliminator/fil-
ters shall be provided. Simultaneous economizer/com-
pressor operation is also possible. Dampers shall fully 
close on power loss.

BAS-READY ECONOMIZER -

 Outdoor and return air 

dampers that are interlocked and positioned by a fully-
modulating, spring return damper actuator. The maxi-
mum leakage rate for the outdoor air intake dampers 
shall not exceed 2% when dampers are fully closed and 
operating against a pressure differential of 0.5 IWG.

For units with optional VAV or Simplicity® Intelli-Com-
fort™ control, free-cooling shall be available while the 
outdoor dry bulb temperature (OAT) remains below a 
programmable set-point of the controller. Field-installed 
humidity sensors for either outdoor air or outdoor & 
return air streams are available to provide free-cooling 
based on single-enthalpy or dual-enthalpy configura-
tions, respectively. If free-cooling is available, a call for 

cooling shall modulate the economizer in order to main-
tain a supply air temperature (SAT) programmable set-
point. With the use of a field-installed indoor air quality 
sensor, the controller shall provide Demand Ventilation 
by modulating the economizer dampers to allow more 
outside airflow upon detection of elevated indoor CO

2

 

concentrations above a programmable set-point. With an 
additional field-installed outdoor air quality sensor, Differ-
ential Demand Ventilation shall be provided.

The outdoor intake opening shall be covered with a rain 
hood that matches the exterior of the unit. Water elimina-
tor/filters shall be provided.

Simultaneous economizer/compressor operation is also 
possible. Dampers shall fully close on power loss.

MOTORIZED OUTDOOR AIR DAMPERS

 - Outdoor and 

return air dampers that are interlocked and positioned by 
a 2-position, spring-return damper actuator. The maxi-
mum leakage rate for the outdoor air intake dampers shall 
not exceed 2% when dampers are fully closed and operat-
ing against a pressure differential of 0.5 IWG. A unit-
mounted potentiometer shall be provided to adjust the 
outdoor and return air damper assembly to take in the 
design CFM of outdoor air to meet the ventilation require-
ments of the conditioned space during normal operation. 
Whenever the indoor fan motor is energized, the dampers 
open up to one of two pre-selected positions - regardless 
of the outdoor air enthalpy. Dampers return to the fully 
closed position when the indoor fan motor is de-ener-
gized. Dampers shall fully close on power loss. 

OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE

ROOF CURB

 - 14" high, full perimeter curb with wood 

nailer (shipped knocked-down). 

100% BAROMETRIC RELIEF DAMPER

 - Contains a 

rain hood, air inlet screen, exhaust damper and mount-
ing hardware. Used to relieve internal air pressure 
through the unit. 

PROPANE CONVERSION KIT

 - Contains new orifices 

and gas valve parts to convert from natural to L.P. gas. 
One per unit required. 

HIGH ALTITUDE - NATURAL GAS

 - Contains orifices 

required for applications between 2000 and 6000 feet 
altitude. 

HIGH ALTITUDE - PROPANE GAS

 - Contains orifices 

required for applications between 2000 and 6000 feet 
altitude. Must be used with propane conversion kit. 

BURGLAR BARS

 - Designed to work with above roof 

curbs, depending on unit model. Fits duct openings of 
curb supply and return air openings. 

SIDE DUCT FLANGE

 - Supply and return air duct 

flanges for side duct applications. Do not use on units 
with power exhaust. 

Summary of Contents for DH 180

Page 1: ...cally sealed scroll compressors with crankcase heaters Two stage heating provided by dual independent heat exchangers with aluminized steel tubes redundant gas valves spark ignition with induced draft...

Page 2: ...17 5 TON COOLING ONLY 210 MBH BOTTOM DUCT CONNECTIONS 21 11 SUPPLY AIR BLOWER PERFORMANCE 20 TON COOLING ONLY 240 MBH BOTTOM DUCT CONNECTIONS 22 12 SUPPLY AIR BLOWER PERFORMANCE 15 TON GAS HEAT 180 M...

Page 3: ...r all units These four digits will not be assigned until a quote is requested or an order placed CPC Controller DFS APS Johnson Controller UNT 1126 N2 protocol DFS APS Honeywell Controller DFS APS Nov...

Page 4: ...ypass valve is available for low cooling load applications Simplicity Controls Simplicity control boards have standardized a number of features previously available only as options or by utilizing add...

Page 5: ...motor actuator capa ble of introducing up to 100 outdoor air with nominal 1 leakage type dampers The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is c...

Page 6: ...rogrammed from the factory An optional factory installed manual bypass switch available with factory installed VFD can be found in the Blower Motor Access compartment The switch can be used to either...

Page 7: ...anced Rooftop building auto mation system controller is factory installed Includes supply air sensor return air sensor dirty filter indicator switch and air proving switch HONEYWELL BAS CONTROL The Ho...

Page 8: ...natural gas furnace to propane HIGH ALTITUDE PROPANE Burner orifices and pilot orifices are provided for proper furnace operation at alti tudes up to 6 000 feet This accessory supplements the basic p...

Page 9: ...power input in watts expressed in Btuh per watt Btuh watt IPLV3 3 IPLV Integrated part load value COOLING ONLY DH180C00 1784 4 Deduct 2 MBH 208V 10 8 11 3 DH210C00 205 10 2 10 8 DH240C00 223 9 7 10 2...

Page 10: ...7 119 5 82 2 186 8 12 3 186 8 186 8 186 8 149 5 112 2 75 0 57 191 0 10 5 191 0 191 0 191 0 153 8 116 5 79 3 183 7 12 3 183 7 183 7 183 7 146 5 109 2 71 9 AIR ON EVAPORATOR COIL TEMPERATURE OF AIR ON...

Page 11: ...77 194 0 18 0 138 6 91 2 62 0 72 179 0 17 1 151 3 122 2 93 0 63 8 67 164 0 16 2 164 0 153 2 124 0 94 8 65 7 62 154 0 16 3 154 0 154 0 154 0 124 8 95 7 66 5 57 150 0 16 6 150 0 150 0 150 0 120 8 91 7 6...

Page 12: ...183 0 139 5 96 0 215 3 15 2 215 3 215 3 215 3 171 9 128 4 84 9 57 222 0 13 9 222 0 222 0 222 0 178 5 135 0 91 6 212 7 15 2 212 7 212 7 212 7 169 3 125 8 82 3 AIR ON EVAPORATOR COIL TEMPERATURE OF AIR...

Page 13: ...4 76 4 216 8 23 0 173 6 106 4 72 4 72 211 0 20 7 182 0 148 0 114 0 80 0 198 6 22 5 177 0 143 0 109 0 74 9 67 192 1 20 2 192 1 185 6 151 6 117 6 83 6 180 4 22 0 180 4 179 5 145 5 111 5 77 5 62 179 1 19...

Page 14: ...8 133 1 269 2 12 4 269 2 269 2 269 2 219 6 169 9 120 2 57 278 9 10 6 278 9 278 9 278 9 229 2 179 5 129 8 267 1 12 2 267 1 267 1 267 1 217 4 167 7 118 0 AIR ON EVAPORATOR COIL TEMPERATURE OF AIR ON CO...

Page 15: ...235 0 22 8 228 5 150 8 100 0 72 224 0 22 4 220 8 181 9 143 0 104 1 67 213 0 22 0 213 0 213 0 186 0 147 1 108 2 62 210 0 21 6 210 0 210 0 209 0 170 1 131 2 92 4 57 208 0 21 4 208 0 208 0 208 0 169 1 1...

Page 16: ...5 6 93 5 291 6 21 8 291 6 291 6 282 0 219 9 157 8 95 7 57 288 7 20 1 288 7 288 7 288 7 226 6 164 5 102 4 286 1 21 8 286 1 286 1 286 1 224 0 161 9 99 8 AIR ON EVAPORATOR COIL TEMPERATURE OF AIR ON COND...

Page 17: ...0 77 310 4 29 4 227 1 134 6 86 0 72 282 2 28 6 240 5 191 9 143 3 94 7 67 254 0 27 8 254 0 249 2 200 6 152 0 103 4 62 249 7 27 2 249 7 249 7 248 4 199 8 151 2 102 6 57 244 9 27 3 244 9 244 9 234 9 186...

Page 18: ...the static pressure and BHP Since no temperature data is given we will assume an air temperature of 70 F Table 8 shows the correction factor to be 0 832 Corrected static pressure 1 5 x 0 832 1 248 IWC...

Page 19: ...262260 YTG E 1008 Johnson Controls Unitary Products 19 FIGURE 2 ALTITUDE TEMPERATURE CONVERSION FACTOR...

Page 20: ...0 0 9 5 2 4 7 0 7 5 7 5 1 208 VOLT AND HIGH STATIC DRIVE 965 6 0 1 2 2 9 2 6 1 0 3 6 3 2 0 8 4 0 3 6 0 5 4 7 4 2 0 4 5 0 4 4 980 5 5 1 3 3 0 2 7 1 1 3 7 3 3 0 9 4 1 3 7 0 6 4 8 4 3 0 5 5 1 4 6 1025 4...

Page 21: ...4 5 9 5 0 980 5 0 1 6 5 3 4 5 1 4 5 8 4 9 1 2 6 3 5 3 0 7 6 9 5 8 1010 4 0 1 8 5 8 4 9 1 7 6 3 5 3 1 5 6 9 5 8 1 0 7 5 6 3 1020 3 5 1 9 6 1 5 1 1 8 6 5 5 5 1 6 7 1 6 0 1 1 7 8 6 6 1035 3 0 2 0 6 2 5...

Page 22: ...9 1 2 6 3 5 3 0 7 6 9 5 8 0 2 7 3 6 1 1010 4 0 1 8 5 8 4 9 1 7 6 3 5 3 1 5 6 9 5 8 1 0 7 5 6 3 0 5 7 9 6 7 1020 3 5 1 9 6 1 5 1 1 8 6 5 5 5 1 6 7 1 6 0 1 1 7 8 6 6 0 6 8 3 7 0 1035 3 0 2 0 6 2 5 2 1 9...

Page 23: ...8 3 4 1 0 4 4 3 9 0 8 5 0 4 5 0 6 5 6 5 0 208 VOLT AND HIGH STATIC DRIVE 965 6 0 1 2 2 7 2 5 0 9 3 2 2 9 0 6 3 7 3 3 0 4 4 4 3 9 0 2 5 0 4 5 980 5 5 1 3 2 9 2 6 1 0 3 4 3 0 0 7 3 8 3 4 0 5 4 5 4 0 0 3...

Page 24: ...5 1 0 2 6 9 5 8 980 5 0 1 9 4 5 3 8 1 5 5 4 4 5 1 0 6 3 5 3 0 4 7 2 6 1 995 4 5 2 1 4 5 3 9 1 6 5 5 4 7 1 1 6 4 5 4 0 5 7 5 6 3 1025 3 5 2 3 4 9 4 1 1 8 5 8 4 9 1 3 6 7 5 7 0 7 8 0 6 7 1050 2 5 2 5 5...

Page 25: ...980 5 0 1 9 4 5 3 8 1 5 5 4 4 5 1 0 6 3 5 3 0 4 7 2 6 1 0 1 8 5 7 1 995 4 5 2 1 4 5 3 9 1 6 5 5 4 7 1 1 6 4 5 4 0 5 7 5 6 3 0 2 8 6 7 3 1025 3 5 2 3 4 9 4 1 1 8 5 8 4 9 1 3 6 7 5 7 0 7 8 0 6 7 1050 2...

Page 26: ...7 11 2 1215 4 0 2 7 8 6 7 0 2 1 10 4 8 5 1 4 12 3 10 1 0 6 14 3 11 7 1255 3 0 3 0 9 1 7 4 2 4 11 0 9 0 1 7 12 9 10 6 0 9 15 0 12 3 1290 2 0 3 2 9 5 7 8 2 7 11 5 9 4 2 0 13 5 11 1 1 2 15 6 12 8 1330 1...

Page 27: ...TION RESISTANCE IWG CFM 15 TON 17 5 TON 20 TON 25 TON 4500 6000 7200 6000 8000 9000 6000 7000 9400 7500 10000 12500 WET COIL 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 ELECTRIC HEAT OPTIONS DH mo...

Page 28: ...5 6 190 4 5 20 0 0 0 None 86 6 110 E18 13 5 1 37 5 86 6 110 E36 27 2 74 9 118 7 125 E54 40 6 2 112 7 165 9 175 E72 54 1 2 150 2 175 2 200 230 3 60 25 6 190 4 3 20 0 0 0 None 86 2 110 E18 18 0 1 43 3 8...

Page 29: ...86 6 102 9 110 575 12 4 80 1 7 10 0 0 0 None 41 3 50 E18 18 0 1 17 3 41 3 50 E36 36 0 2 34 6 55 8 60 E54 54 0 2 52 0 64 5 70 E72 72 0 2 69 3 81 8 90 TABLE 21 DH 300 ELECTRICAL DATA HIGH STATIC MOTOR...

Page 30: ...6 190 4 5 20 0 10 0 None 96 6 110 E18 13 5 1 37 5 96 6 110 E36 27 2 74 9 131 2 150 E54 40 6 2 112 7 178 4 200 E72 54 1 2 150 2 187 7 200 230 3 60 25 6 190 4 3 20 0 10 0 None 96 2 110 E18 18 0 1 43 3...

Page 31: ...86 6 109 1 110 575 12 4 80 1 7 10 0 4 0 None 45 3 50 E18 18 0 1 17 3 45 3 50 E36 36 0 2 34 6 60 8 70 E54 54 0 2 52 0 69 5 70 E72 72 0 2 69 3 86 8 90 TABLE 24 DH 300 ELECTRICAL DATA HIGH STATIC MOTOR...

Page 32: ...e heating is not required on units with a single stage electric heater 4Terminals A1 and A2 provide a relay output to close the outdoor economizer dampers when the thermostat switches to the set back...

Page 33: ...25 X 2 or 4 4 4 4 Quantity Per Unit 18 X 24 X 2 or 4 5 Total Face Area sq ft 15 0 20 0 20 0 20 0 CHARGE Refrigerant 22 lbs oz System 1 23 10 24 0 24 2 21 1 System 2 21 10 24 8 27 2 21 1 TABLE 28 OPERA...

Page 34: ...illustrate Bottom Duct openings Power and Gas Piping Connection locations 12 1 2 9 1 4 8 1 8 9 3 4 3 3 4 B POWER WIRING ENTRY A CONTROL WIRING ENTRY CONDENSER COILS OPTIONAL COIL GUARD KIT COMPRESSOR...

Page 35: ...n The covering consists of a heavy black paper composition 3 Replace the side supply and return air compartment panels For side duct applications 1 Replace the side panels on the supply and return air...

Page 36: ...CLEARANCES LOCATION CLEARANCE Front 36 Rear 24 Less Economizer 49 With Economizer Left Side Filter Access 24 Less Economizer 36 With Economizer 3 Right Side Cond Coil 36 Below Unit1 1 Units may be in...

Page 37: ...262260 YTG E 1008 Johnson Controls Unitary Products 37 FIGURE 7 UNIT CENTER OF GRAVITY 17 5 20 25 Ton FIGURE 8 TYPICAL UNIT APPLICATIONS...

Page 38: ...563 DH240N32 2340 548 596 623 573 DH300C00 2345 461 502 720 662 DH300N24 2545 501 545 781 718 DH300N32 2585 509 553 794 729 TABLE 33 DH 180 210 240 300 6 POINT LOAD WEIGHT DISTRIBUTION UNIT MODEL OPE...

Page 39: ...ducts allows ductwork penetration between roof joists that are spaced on 72 centers NOTE Ducts can be installed into the curb from the roof All electrical and gas line connections can be made inside t...

Page 40: ...S CONTROL TERMINAL BLOCK TERMINALS ON A LIMITED NUMBER OF THERMOSTATS 3 1 2 4 3 1 2 4 Second stage heating not required on single stage heating units Second stage cooling not required on single stage...

Page 41: ...ct connections for down discharge supply return or horizontal discharge supply return and be available with factory installed options or field installed accessories The units shall be factory wired pi...

Page 42: ...on thermostat evaporator coil If any of the above safety devices trip a LED light emitting diode indicator shall flash a diagnostic code that indicates which safety switch has tripped d Unit shall inc...

Page 43: ...oor return air streams are available to provide free cooling based on single enthalpy or dual enthalpy configura tions respectively If free cooling is available a call for cooling shall modulate the e...

Page 44: ...COIL GUARD KIT Guard for cooling coil OTHER FACTORY INSTALLED OPTIONS POWER EXHAUST OPTION To work in conjunction with economizers STAINLESS STEEL HEAT EXCHANGER STAINLESS STEEL DRAIN PAN TECHNICOAT P...

Reviews: