background image

262260-YTG-E-1008

Johnson Controls Unitary Products

9

SSE = Steady State Efficiency (80%) - Output divided by Input

TABLE 1: INDOOR SOUND POWER RATING

1

1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field.  The dBA val-

ues provided are to be used for reference only.  Calculation of dBA values cover matters of system design and the fan manufacture has no 
way of knowing the details of each system.  This constitutes and expectation to any specification or guarantee requiring a dBA value or 
sound data in any other form than sound power level ratings.

UNIT

SIZE

CFM

ESP

BLOWER

SOUND POWER (db 10

-12

 Watts)

Octave Band Centerline Frequency (Hz)

SWL

dB(A)

dB(A)

@

10Ft.

2

2. At a distance of 10 feet from the blower.

IWG

RPM

BHP

63

125

250

500

1,000

2,000

4,000

8,000

180

6,000

1.00

1,080

4.60

99

99

89

82

84

77

72

67

89

56

210, 240

8,000

1.00

1,120

6.65

102

102

92

85

87

80

75

70

92

59

300

10,000

1.30

1,160

12.5

108

108

98

91

93

86

81

76

98

65

TABLE 2: CAPACITY RATINGS - (ARI 360)

1

1. 80/67°F Indoor and 95°F outdoor.

MODEL

MBH

EER

2

2. EER = Energy Efficiency Ratio at full load - the cooling 

capacity in Btu’s per hour (Btuh) divided by the power 
input in watts, expressed in Btuh per watt (Btuh/watt).

IPLV

3

3. IPLV = Integrated part load value.

COOLING ONLY

DH180C00

178

4

4. Deduct 2 MBH @ 208V.

10.8

11.3

DH210C00

205

10.2

10.8

DH240C00

223

9.7

10.2

DH300C00

271

9.6

9.6

COOLING WITH GAS HEAT

DH180N/S

178

4

10.8

11.3

DH210N/S

205

10.2

10.8

DH240N/S

223

9.7

10.2

DH300N/S

271

9.6

9.6

COOLING WITH ELECTRIC HEAT

DH180E18

178

4

10.8

11.3

DH180E36

178

4

10.8

11.3

DH180E54

176

4

10.5

11.0

DH180E72

176

4

10.5

11.0

DH210E18

205

10.2

10.8

DH210E36

205

10.2

10.8

DH210E54

203

10.0

10.6

DH210E72

203

10.0

10.6

DH240E18

223

9.6

10.1

DH240E36

223

9.6

10.1

DH240E54

221

9.5

9.7

DH240E72

219

9.5

9.7

DH300E18

271

9.6

9.6

DH300E36

271

9.6

9.6

DH300E54

269

9.5

9.4

DH300E72

269

9.5

9.4

TABLE 3: GAS HEAT RATINGS

1

1. All units are two-stage heating.  First stage is 50% of total.

MODEL

MBH INPUT

MBH OUTPUT

DH180N/S24

300

240

DH180N/S32

400

320

DH210N/S24

300

240

DH210N/S32

400

320

DH240N/S24

300

240

DH240N/S32

400

320

DH300N/S24

300

240

DH300N/S32

400

320

For units with VFD and electric or gas heat, the 
speed of the indoor blower motor continues to be 
controlled by duct static pressure via the VAV con-
trol board.

If there are VAV boxes present in the duct system, 
the boxes must be driven to the full-open position 
using a customer-supplied power source to assure 
adequate airflow across electric heating elements or 
gas heat exchanger tubes.

Summary of Contents for DH 180

Page 1: ...cally sealed scroll compressors with crankcase heaters Two stage heating provided by dual independent heat exchangers with aluminized steel tubes redundant gas valves spark ignition with induced draft...

Page 2: ...17 5 TON COOLING ONLY 210 MBH BOTTOM DUCT CONNECTIONS 21 11 SUPPLY AIR BLOWER PERFORMANCE 20 TON COOLING ONLY 240 MBH BOTTOM DUCT CONNECTIONS 22 12 SUPPLY AIR BLOWER PERFORMANCE 15 TON GAS HEAT 180 M...

Page 3: ...r all units These four digits will not be assigned until a quote is requested or an order placed CPC Controller DFS APS Johnson Controller UNT 1126 N2 protocol DFS APS Honeywell Controller DFS APS Nov...

Page 4: ...ypass valve is available for low cooling load applications Simplicity Controls Simplicity control boards have standardized a number of features previously available only as options or by utilizing add...

Page 5: ...motor actuator capa ble of introducing up to 100 outdoor air with nominal 1 leakage type dampers The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is c...

Page 6: ...rogrammed from the factory An optional factory installed manual bypass switch available with factory installed VFD can be found in the Blower Motor Access compartment The switch can be used to either...

Page 7: ...anced Rooftop building auto mation system controller is factory installed Includes supply air sensor return air sensor dirty filter indicator switch and air proving switch HONEYWELL BAS CONTROL The Ho...

Page 8: ...natural gas furnace to propane HIGH ALTITUDE PROPANE Burner orifices and pilot orifices are provided for proper furnace operation at alti tudes up to 6 000 feet This accessory supplements the basic p...

Page 9: ...power input in watts expressed in Btuh per watt Btuh watt IPLV3 3 IPLV Integrated part load value COOLING ONLY DH180C00 1784 4 Deduct 2 MBH 208V 10 8 11 3 DH210C00 205 10 2 10 8 DH240C00 223 9 7 10 2...

Page 10: ...7 119 5 82 2 186 8 12 3 186 8 186 8 186 8 149 5 112 2 75 0 57 191 0 10 5 191 0 191 0 191 0 153 8 116 5 79 3 183 7 12 3 183 7 183 7 183 7 146 5 109 2 71 9 AIR ON EVAPORATOR COIL TEMPERATURE OF AIR ON...

Page 11: ...77 194 0 18 0 138 6 91 2 62 0 72 179 0 17 1 151 3 122 2 93 0 63 8 67 164 0 16 2 164 0 153 2 124 0 94 8 65 7 62 154 0 16 3 154 0 154 0 154 0 124 8 95 7 66 5 57 150 0 16 6 150 0 150 0 150 0 120 8 91 7 6...

Page 12: ...183 0 139 5 96 0 215 3 15 2 215 3 215 3 215 3 171 9 128 4 84 9 57 222 0 13 9 222 0 222 0 222 0 178 5 135 0 91 6 212 7 15 2 212 7 212 7 212 7 169 3 125 8 82 3 AIR ON EVAPORATOR COIL TEMPERATURE OF AIR...

Page 13: ...4 76 4 216 8 23 0 173 6 106 4 72 4 72 211 0 20 7 182 0 148 0 114 0 80 0 198 6 22 5 177 0 143 0 109 0 74 9 67 192 1 20 2 192 1 185 6 151 6 117 6 83 6 180 4 22 0 180 4 179 5 145 5 111 5 77 5 62 179 1 19...

Page 14: ...8 133 1 269 2 12 4 269 2 269 2 269 2 219 6 169 9 120 2 57 278 9 10 6 278 9 278 9 278 9 229 2 179 5 129 8 267 1 12 2 267 1 267 1 267 1 217 4 167 7 118 0 AIR ON EVAPORATOR COIL TEMPERATURE OF AIR ON CO...

Page 15: ...235 0 22 8 228 5 150 8 100 0 72 224 0 22 4 220 8 181 9 143 0 104 1 67 213 0 22 0 213 0 213 0 186 0 147 1 108 2 62 210 0 21 6 210 0 210 0 209 0 170 1 131 2 92 4 57 208 0 21 4 208 0 208 0 208 0 169 1 1...

Page 16: ...5 6 93 5 291 6 21 8 291 6 291 6 282 0 219 9 157 8 95 7 57 288 7 20 1 288 7 288 7 288 7 226 6 164 5 102 4 286 1 21 8 286 1 286 1 286 1 224 0 161 9 99 8 AIR ON EVAPORATOR COIL TEMPERATURE OF AIR ON COND...

Page 17: ...0 77 310 4 29 4 227 1 134 6 86 0 72 282 2 28 6 240 5 191 9 143 3 94 7 67 254 0 27 8 254 0 249 2 200 6 152 0 103 4 62 249 7 27 2 249 7 249 7 248 4 199 8 151 2 102 6 57 244 9 27 3 244 9 244 9 234 9 186...

Page 18: ...the static pressure and BHP Since no temperature data is given we will assume an air temperature of 70 F Table 8 shows the correction factor to be 0 832 Corrected static pressure 1 5 x 0 832 1 248 IWC...

Page 19: ...262260 YTG E 1008 Johnson Controls Unitary Products 19 FIGURE 2 ALTITUDE TEMPERATURE CONVERSION FACTOR...

Page 20: ...0 0 9 5 2 4 7 0 7 5 7 5 1 208 VOLT AND HIGH STATIC DRIVE 965 6 0 1 2 2 9 2 6 1 0 3 6 3 2 0 8 4 0 3 6 0 5 4 7 4 2 0 4 5 0 4 4 980 5 5 1 3 3 0 2 7 1 1 3 7 3 3 0 9 4 1 3 7 0 6 4 8 4 3 0 5 5 1 4 6 1025 4...

Page 21: ...4 5 9 5 0 980 5 0 1 6 5 3 4 5 1 4 5 8 4 9 1 2 6 3 5 3 0 7 6 9 5 8 1010 4 0 1 8 5 8 4 9 1 7 6 3 5 3 1 5 6 9 5 8 1 0 7 5 6 3 1020 3 5 1 9 6 1 5 1 1 8 6 5 5 5 1 6 7 1 6 0 1 1 7 8 6 6 1035 3 0 2 0 6 2 5...

Page 22: ...9 1 2 6 3 5 3 0 7 6 9 5 8 0 2 7 3 6 1 1010 4 0 1 8 5 8 4 9 1 7 6 3 5 3 1 5 6 9 5 8 1 0 7 5 6 3 0 5 7 9 6 7 1020 3 5 1 9 6 1 5 1 1 8 6 5 5 5 1 6 7 1 6 0 1 1 7 8 6 6 0 6 8 3 7 0 1035 3 0 2 0 6 2 5 2 1 9...

Page 23: ...8 3 4 1 0 4 4 3 9 0 8 5 0 4 5 0 6 5 6 5 0 208 VOLT AND HIGH STATIC DRIVE 965 6 0 1 2 2 7 2 5 0 9 3 2 2 9 0 6 3 7 3 3 0 4 4 4 3 9 0 2 5 0 4 5 980 5 5 1 3 2 9 2 6 1 0 3 4 3 0 0 7 3 8 3 4 0 5 4 5 4 0 0 3...

Page 24: ...5 1 0 2 6 9 5 8 980 5 0 1 9 4 5 3 8 1 5 5 4 4 5 1 0 6 3 5 3 0 4 7 2 6 1 995 4 5 2 1 4 5 3 9 1 6 5 5 4 7 1 1 6 4 5 4 0 5 7 5 6 3 1025 3 5 2 3 4 9 4 1 1 8 5 8 4 9 1 3 6 7 5 7 0 7 8 0 6 7 1050 2 5 2 5 5...

Page 25: ...980 5 0 1 9 4 5 3 8 1 5 5 4 4 5 1 0 6 3 5 3 0 4 7 2 6 1 0 1 8 5 7 1 995 4 5 2 1 4 5 3 9 1 6 5 5 4 7 1 1 6 4 5 4 0 5 7 5 6 3 0 2 8 6 7 3 1025 3 5 2 3 4 9 4 1 1 8 5 8 4 9 1 3 6 7 5 7 0 7 8 0 6 7 1050 2...

Page 26: ...7 11 2 1215 4 0 2 7 8 6 7 0 2 1 10 4 8 5 1 4 12 3 10 1 0 6 14 3 11 7 1255 3 0 3 0 9 1 7 4 2 4 11 0 9 0 1 7 12 9 10 6 0 9 15 0 12 3 1290 2 0 3 2 9 5 7 8 2 7 11 5 9 4 2 0 13 5 11 1 1 2 15 6 12 8 1330 1...

Page 27: ...TION RESISTANCE IWG CFM 15 TON 17 5 TON 20 TON 25 TON 4500 6000 7200 6000 8000 9000 6000 7000 9400 7500 10000 12500 WET COIL 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 ELECTRIC HEAT OPTIONS DH mo...

Page 28: ...5 6 190 4 5 20 0 0 0 None 86 6 110 E18 13 5 1 37 5 86 6 110 E36 27 2 74 9 118 7 125 E54 40 6 2 112 7 165 9 175 E72 54 1 2 150 2 175 2 200 230 3 60 25 6 190 4 3 20 0 0 0 None 86 2 110 E18 18 0 1 43 3 8...

Page 29: ...86 6 102 9 110 575 12 4 80 1 7 10 0 0 0 None 41 3 50 E18 18 0 1 17 3 41 3 50 E36 36 0 2 34 6 55 8 60 E54 54 0 2 52 0 64 5 70 E72 72 0 2 69 3 81 8 90 TABLE 21 DH 300 ELECTRICAL DATA HIGH STATIC MOTOR...

Page 30: ...6 190 4 5 20 0 10 0 None 96 6 110 E18 13 5 1 37 5 96 6 110 E36 27 2 74 9 131 2 150 E54 40 6 2 112 7 178 4 200 E72 54 1 2 150 2 187 7 200 230 3 60 25 6 190 4 3 20 0 10 0 None 96 2 110 E18 18 0 1 43 3...

Page 31: ...86 6 109 1 110 575 12 4 80 1 7 10 0 4 0 None 45 3 50 E18 18 0 1 17 3 45 3 50 E36 36 0 2 34 6 60 8 70 E54 54 0 2 52 0 69 5 70 E72 72 0 2 69 3 86 8 90 TABLE 24 DH 300 ELECTRICAL DATA HIGH STATIC MOTOR...

Page 32: ...e heating is not required on units with a single stage electric heater 4Terminals A1 and A2 provide a relay output to close the outdoor economizer dampers when the thermostat switches to the set back...

Page 33: ...25 X 2 or 4 4 4 4 Quantity Per Unit 18 X 24 X 2 or 4 5 Total Face Area sq ft 15 0 20 0 20 0 20 0 CHARGE Refrigerant 22 lbs oz System 1 23 10 24 0 24 2 21 1 System 2 21 10 24 8 27 2 21 1 TABLE 28 OPERA...

Page 34: ...illustrate Bottom Duct openings Power and Gas Piping Connection locations 12 1 2 9 1 4 8 1 8 9 3 4 3 3 4 B POWER WIRING ENTRY A CONTROL WIRING ENTRY CONDENSER COILS OPTIONAL COIL GUARD KIT COMPRESSOR...

Page 35: ...n The covering consists of a heavy black paper composition 3 Replace the side supply and return air compartment panels For side duct applications 1 Replace the side panels on the supply and return air...

Page 36: ...CLEARANCES LOCATION CLEARANCE Front 36 Rear 24 Less Economizer 49 With Economizer Left Side Filter Access 24 Less Economizer 36 With Economizer 3 Right Side Cond Coil 36 Below Unit1 1 Units may be in...

Page 37: ...262260 YTG E 1008 Johnson Controls Unitary Products 37 FIGURE 7 UNIT CENTER OF GRAVITY 17 5 20 25 Ton FIGURE 8 TYPICAL UNIT APPLICATIONS...

Page 38: ...563 DH240N32 2340 548 596 623 573 DH300C00 2345 461 502 720 662 DH300N24 2545 501 545 781 718 DH300N32 2585 509 553 794 729 TABLE 33 DH 180 210 240 300 6 POINT LOAD WEIGHT DISTRIBUTION UNIT MODEL OPE...

Page 39: ...ducts allows ductwork penetration between roof joists that are spaced on 72 centers NOTE Ducts can be installed into the curb from the roof All electrical and gas line connections can be made inside t...

Page 40: ...S CONTROL TERMINAL BLOCK TERMINALS ON A LIMITED NUMBER OF THERMOSTATS 3 1 2 4 3 1 2 4 Second stage heating not required on single stage heating units Second stage cooling not required on single stage...

Page 41: ...ct connections for down discharge supply return or horizontal discharge supply return and be available with factory installed options or field installed accessories The units shall be factory wired pi...

Page 42: ...on thermostat evaporator coil If any of the above safety devices trip a LED light emitting diode indicator shall flash a diagnostic code that indicates which safety switch has tripped d Unit shall inc...

Page 43: ...oor return air streams are available to provide free cooling based on single enthalpy or dual enthalpy configura tions respectively If free cooling is available a call for cooling shall modulate the e...

Page 44: ...COIL GUARD KIT Guard for cooling coil OTHER FACTORY INSTALLED OPTIONS POWER EXHAUST OPTION To work in conjunction with economizers STAINLESS STEEL HEAT EXCHANGER STAINLESS STEEL DRAIN PAN TECHNICOAT P...

Reviews: