FEATURES

All models are available with a wide variety of factory-
mounted options such as stainless steel heat exchangers, 
phase monitor, dirty filter switch, and coil guard to make them 
suitable for almost every application.

All units are self-contained and assembled on full perimeter 
base rails with holes in the four corners for overhead rigging. 
Every unit is completely piped, wired, charged and tested at 
the factory to simplify the field installation and to provide 
years of dependable operation.

All models (including those with an economizer) are suitable 
for either bottom or horizontal duct connections. 

Models with 

factory installed power exhaust are suitable for bottom 
duct connections only

. For bottom duct, you remove the 

sheet metal panels from the supply and return air openings 
through the base of the unit. For horizontal duct, you replace 
the supply and return air panels on the rear of the unit with a 
side duct flange accessory.

All models are available with these “factory mounted” outdoor 
air damper options:

Single enthalpy economizer with or without power 
exhaust

BAS-ready economizer with or without power exhaust

Motorized outdoor air damper

Barometric Relief Damper

A fixed outdoor air intake assembly will be shipped in the 
return air compartment of all units ordered without an econo-
mizer or motorized outdoor air damper option. The assembly 
includes a rain hood with a damper that can be set for 10, 15 
or 25% outdoor air. With bottom duct connections, the intake 
damper assembly should be mounted over the opening in the 
return air panel. With horizontal ductwork, it should be 
mounted on the return air duct.

All supply air blowers are equipped with a belt drive that can 
be adjusted to meet the exact requirements of the job. A high 
static drive option is available for applications with a higher 
CFM and/or static pressure requirement. A variable air volume 
(VAV) option using a variable frequency drive is available for 
applications requiring a constant supply duct pressure. A dif-
ferential pressure transducer is used to monitor supply duct 
static pressure and return a speed reference signal to the VFD 
to control the output of the indoor blower motor.

All compressors include scroll compressors and internal pres-
sure relief. Every refrigerant circuit includes an expansion 
valve, a liquid line filter-drier, a discharge line high pressure 
switch and a suction line with a freezestat and low pressure/
loss of charge switch to protect all system components. A hot 
gas bypass option, consisting of an adjustable compressor 
discharge bypass valve, is available for low cooling load 
applications.

Simplicity 

®

 Controls

 - 

Simplicity 

®

 control boards have 

standardized a number of features previously available 
only as options or by utilizing additional controls.

Low Ambient 

- An integrated low-ambient control 

allows all units to operate in the cooling mode down 
to 0°F outdoor ambient without additional assis-
tance. Optionally, the control board can be pro-
grammed to lockout the compressors when the 
outdoor air temperature is low or when free cooling 
is available.

Anti-Short Cycle Protection

 - To aid compressor 

life, an anti-short cycle delay is incorporated into the 
standard controls. Compressor reliability is further 
ensured by programmable minimum run times. For 
testing, the anti short cycle delay can be temporarily 
overridden with the push of a button.

Lead-Lag

 - An integrated Lead-Lag option allows 

equal run time hours on all compressors, thereby 
extending the life of all compressors. This option is 
selectable on the unit control board.

Fan Delays

 - Fan on and fan off delays are fully pro-

grammable. Furthermore, the heating and cooling 
fan delay times are independent of one another. All 
units are programmed with default values based 
upon their configuration of cooling and heat.

Safety Monitoring

 - The control board monitors the 

high and low-pressure switches, the freezestats, the 
gas valve, if applicable, and the temperature limit 
switch on gas and electric heat units. The unit con-
trol board will alarm on ignition failures, compressor 
lockouts and repeated limit switch trips.

Nuisance Trip Protection and Strikes

 - To prevent 

nuisance trouble calls, the control board uses a 
“three times, you’re out” philosophy. The high and 
low-pressure switches and the freezestats must trip 
three times within two hours before the unit control 
board will lock out the associated compressor.

On Board Diagnostics

 - Each alarm will energize a 

trouble light on the thermostat, if so equipped, and 
flash an alarm code on the control board LED. Each 
high and low-pressure switch alarm as well as each 
freezestat alarm has its own flash code. The control 
board saves the five most recent alarms in memory, 
and these alarms can be reviewed at any time. 
Alarms and programmed values are retained 
through the loss of power.

The 

Simplicity

® control board used in this product will 

effectively operate the cooling system down to 0°F 
when this product is applied in a comfort cooling 
application for people. An economizer is typically 
included in this type of application. When applying this 
product for process cooling applications (computer 
rooms, switchgear, etc.), please reference applications 
bulletin AE-011-07 or call the applications department 
for Unitary Products @ 1-877-UPG-SERV for 
guidance. Additional accessories may be needed for 
stable operation at temperatures below 30°F.

Summary of Contents for DH 180

Page 1: ...cally sealed scroll compressors with crankcase heaters Two stage heating provided by dual independent heat exchangers with aluminized steel tubes redundant gas valves spark ignition with induced draft...

Page 2: ...17 5 TON COOLING ONLY 210 MBH BOTTOM DUCT CONNECTIONS 21 11 SUPPLY AIR BLOWER PERFORMANCE 20 TON COOLING ONLY 240 MBH BOTTOM DUCT CONNECTIONS 22 12 SUPPLY AIR BLOWER PERFORMANCE 15 TON GAS HEAT 180 M...

Page 3: ...r all units These four digits will not be assigned until a quote is requested or an order placed CPC Controller DFS APS Johnson Controller UNT 1126 N2 protocol DFS APS Honeywell Controller DFS APS Nov...

Page 4: ...ypass valve is available for low cooling load applications Simplicity Controls Simplicity control boards have standardized a number of features previously available only as options or by utilizing add...

Page 5: ...motor actuator capa ble of introducing up to 100 outdoor air with nominal 1 leakage type dampers The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is c...

Page 6: ...rogrammed from the factory An optional factory installed manual bypass switch available with factory installed VFD can be found in the Blower Motor Access compartment The switch can be used to either...

Page 7: ...anced Rooftop building auto mation system controller is factory installed Includes supply air sensor return air sensor dirty filter indicator switch and air proving switch HONEYWELL BAS CONTROL The Ho...

Page 8: ...natural gas furnace to propane HIGH ALTITUDE PROPANE Burner orifices and pilot orifices are provided for proper furnace operation at alti tudes up to 6 000 feet This accessory supplements the basic p...

Page 9: ...power input in watts expressed in Btuh per watt Btuh watt IPLV3 3 IPLV Integrated part load value COOLING ONLY DH180C00 1784 4 Deduct 2 MBH 208V 10 8 11 3 DH210C00 205 10 2 10 8 DH240C00 223 9 7 10 2...

Page 10: ...7 119 5 82 2 186 8 12 3 186 8 186 8 186 8 149 5 112 2 75 0 57 191 0 10 5 191 0 191 0 191 0 153 8 116 5 79 3 183 7 12 3 183 7 183 7 183 7 146 5 109 2 71 9 AIR ON EVAPORATOR COIL TEMPERATURE OF AIR ON...

Page 11: ...77 194 0 18 0 138 6 91 2 62 0 72 179 0 17 1 151 3 122 2 93 0 63 8 67 164 0 16 2 164 0 153 2 124 0 94 8 65 7 62 154 0 16 3 154 0 154 0 154 0 124 8 95 7 66 5 57 150 0 16 6 150 0 150 0 150 0 120 8 91 7 6...

Page 12: ...183 0 139 5 96 0 215 3 15 2 215 3 215 3 215 3 171 9 128 4 84 9 57 222 0 13 9 222 0 222 0 222 0 178 5 135 0 91 6 212 7 15 2 212 7 212 7 212 7 169 3 125 8 82 3 AIR ON EVAPORATOR COIL TEMPERATURE OF AIR...

Page 13: ...4 76 4 216 8 23 0 173 6 106 4 72 4 72 211 0 20 7 182 0 148 0 114 0 80 0 198 6 22 5 177 0 143 0 109 0 74 9 67 192 1 20 2 192 1 185 6 151 6 117 6 83 6 180 4 22 0 180 4 179 5 145 5 111 5 77 5 62 179 1 19...

Page 14: ...8 133 1 269 2 12 4 269 2 269 2 269 2 219 6 169 9 120 2 57 278 9 10 6 278 9 278 9 278 9 229 2 179 5 129 8 267 1 12 2 267 1 267 1 267 1 217 4 167 7 118 0 AIR ON EVAPORATOR COIL TEMPERATURE OF AIR ON CO...

Page 15: ...235 0 22 8 228 5 150 8 100 0 72 224 0 22 4 220 8 181 9 143 0 104 1 67 213 0 22 0 213 0 213 0 186 0 147 1 108 2 62 210 0 21 6 210 0 210 0 209 0 170 1 131 2 92 4 57 208 0 21 4 208 0 208 0 208 0 169 1 1...

Page 16: ...5 6 93 5 291 6 21 8 291 6 291 6 282 0 219 9 157 8 95 7 57 288 7 20 1 288 7 288 7 288 7 226 6 164 5 102 4 286 1 21 8 286 1 286 1 286 1 224 0 161 9 99 8 AIR ON EVAPORATOR COIL TEMPERATURE OF AIR ON COND...

Page 17: ...0 77 310 4 29 4 227 1 134 6 86 0 72 282 2 28 6 240 5 191 9 143 3 94 7 67 254 0 27 8 254 0 249 2 200 6 152 0 103 4 62 249 7 27 2 249 7 249 7 248 4 199 8 151 2 102 6 57 244 9 27 3 244 9 244 9 234 9 186...

Page 18: ...the static pressure and BHP Since no temperature data is given we will assume an air temperature of 70 F Table 8 shows the correction factor to be 0 832 Corrected static pressure 1 5 x 0 832 1 248 IWC...

Page 19: ...262260 YTG E 1008 Johnson Controls Unitary Products 19 FIGURE 2 ALTITUDE TEMPERATURE CONVERSION FACTOR...

Page 20: ...0 0 9 5 2 4 7 0 7 5 7 5 1 208 VOLT AND HIGH STATIC DRIVE 965 6 0 1 2 2 9 2 6 1 0 3 6 3 2 0 8 4 0 3 6 0 5 4 7 4 2 0 4 5 0 4 4 980 5 5 1 3 3 0 2 7 1 1 3 7 3 3 0 9 4 1 3 7 0 6 4 8 4 3 0 5 5 1 4 6 1025 4...

Page 21: ...4 5 9 5 0 980 5 0 1 6 5 3 4 5 1 4 5 8 4 9 1 2 6 3 5 3 0 7 6 9 5 8 1010 4 0 1 8 5 8 4 9 1 7 6 3 5 3 1 5 6 9 5 8 1 0 7 5 6 3 1020 3 5 1 9 6 1 5 1 1 8 6 5 5 5 1 6 7 1 6 0 1 1 7 8 6 6 1035 3 0 2 0 6 2 5...

Page 22: ...9 1 2 6 3 5 3 0 7 6 9 5 8 0 2 7 3 6 1 1010 4 0 1 8 5 8 4 9 1 7 6 3 5 3 1 5 6 9 5 8 1 0 7 5 6 3 0 5 7 9 6 7 1020 3 5 1 9 6 1 5 1 1 8 6 5 5 5 1 6 7 1 6 0 1 1 7 8 6 6 0 6 8 3 7 0 1035 3 0 2 0 6 2 5 2 1 9...

Page 23: ...8 3 4 1 0 4 4 3 9 0 8 5 0 4 5 0 6 5 6 5 0 208 VOLT AND HIGH STATIC DRIVE 965 6 0 1 2 2 7 2 5 0 9 3 2 2 9 0 6 3 7 3 3 0 4 4 4 3 9 0 2 5 0 4 5 980 5 5 1 3 2 9 2 6 1 0 3 4 3 0 0 7 3 8 3 4 0 5 4 5 4 0 0 3...

Page 24: ...5 1 0 2 6 9 5 8 980 5 0 1 9 4 5 3 8 1 5 5 4 4 5 1 0 6 3 5 3 0 4 7 2 6 1 995 4 5 2 1 4 5 3 9 1 6 5 5 4 7 1 1 6 4 5 4 0 5 7 5 6 3 1025 3 5 2 3 4 9 4 1 1 8 5 8 4 9 1 3 6 7 5 7 0 7 8 0 6 7 1050 2 5 2 5 5...

Page 25: ...980 5 0 1 9 4 5 3 8 1 5 5 4 4 5 1 0 6 3 5 3 0 4 7 2 6 1 0 1 8 5 7 1 995 4 5 2 1 4 5 3 9 1 6 5 5 4 7 1 1 6 4 5 4 0 5 7 5 6 3 0 2 8 6 7 3 1025 3 5 2 3 4 9 4 1 1 8 5 8 4 9 1 3 6 7 5 7 0 7 8 0 6 7 1050 2...

Page 26: ...7 11 2 1215 4 0 2 7 8 6 7 0 2 1 10 4 8 5 1 4 12 3 10 1 0 6 14 3 11 7 1255 3 0 3 0 9 1 7 4 2 4 11 0 9 0 1 7 12 9 10 6 0 9 15 0 12 3 1290 2 0 3 2 9 5 7 8 2 7 11 5 9 4 2 0 13 5 11 1 1 2 15 6 12 8 1330 1...

Page 27: ...TION RESISTANCE IWG CFM 15 TON 17 5 TON 20 TON 25 TON 4500 6000 7200 6000 8000 9000 6000 7000 9400 7500 10000 12500 WET COIL 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 ELECTRIC HEAT OPTIONS DH mo...

Page 28: ...5 6 190 4 5 20 0 0 0 None 86 6 110 E18 13 5 1 37 5 86 6 110 E36 27 2 74 9 118 7 125 E54 40 6 2 112 7 165 9 175 E72 54 1 2 150 2 175 2 200 230 3 60 25 6 190 4 3 20 0 0 0 None 86 2 110 E18 18 0 1 43 3 8...

Page 29: ...86 6 102 9 110 575 12 4 80 1 7 10 0 0 0 None 41 3 50 E18 18 0 1 17 3 41 3 50 E36 36 0 2 34 6 55 8 60 E54 54 0 2 52 0 64 5 70 E72 72 0 2 69 3 81 8 90 TABLE 21 DH 300 ELECTRICAL DATA HIGH STATIC MOTOR...

Page 30: ...6 190 4 5 20 0 10 0 None 96 6 110 E18 13 5 1 37 5 96 6 110 E36 27 2 74 9 131 2 150 E54 40 6 2 112 7 178 4 200 E72 54 1 2 150 2 187 7 200 230 3 60 25 6 190 4 3 20 0 10 0 None 96 2 110 E18 18 0 1 43 3...

Page 31: ...86 6 109 1 110 575 12 4 80 1 7 10 0 4 0 None 45 3 50 E18 18 0 1 17 3 45 3 50 E36 36 0 2 34 6 60 8 70 E54 54 0 2 52 0 69 5 70 E72 72 0 2 69 3 86 8 90 TABLE 24 DH 300 ELECTRICAL DATA HIGH STATIC MOTOR...

Page 32: ...e heating is not required on units with a single stage electric heater 4Terminals A1 and A2 provide a relay output to close the outdoor economizer dampers when the thermostat switches to the set back...

Page 33: ...25 X 2 or 4 4 4 4 Quantity Per Unit 18 X 24 X 2 or 4 5 Total Face Area sq ft 15 0 20 0 20 0 20 0 CHARGE Refrigerant 22 lbs oz System 1 23 10 24 0 24 2 21 1 System 2 21 10 24 8 27 2 21 1 TABLE 28 OPERA...

Page 34: ...illustrate Bottom Duct openings Power and Gas Piping Connection locations 12 1 2 9 1 4 8 1 8 9 3 4 3 3 4 B POWER WIRING ENTRY A CONTROL WIRING ENTRY CONDENSER COILS OPTIONAL COIL GUARD KIT COMPRESSOR...

Page 35: ...n The covering consists of a heavy black paper composition 3 Replace the side supply and return air compartment panels For side duct applications 1 Replace the side panels on the supply and return air...

Page 36: ...CLEARANCES LOCATION CLEARANCE Front 36 Rear 24 Less Economizer 49 With Economizer Left Side Filter Access 24 Less Economizer 36 With Economizer 3 Right Side Cond Coil 36 Below Unit1 1 Units may be in...

Page 37: ...262260 YTG E 1008 Johnson Controls Unitary Products 37 FIGURE 7 UNIT CENTER OF GRAVITY 17 5 20 25 Ton FIGURE 8 TYPICAL UNIT APPLICATIONS...

Page 38: ...563 DH240N32 2340 548 596 623 573 DH300C00 2345 461 502 720 662 DH300N24 2545 501 545 781 718 DH300N32 2585 509 553 794 729 TABLE 33 DH 180 210 240 300 6 POINT LOAD WEIGHT DISTRIBUTION UNIT MODEL OPE...

Page 39: ...ducts allows ductwork penetration between roof joists that are spaced on 72 centers NOTE Ducts can be installed into the curb from the roof All electrical and gas line connections can be made inside t...

Page 40: ...S CONTROL TERMINAL BLOCK TERMINALS ON A LIMITED NUMBER OF THERMOSTATS 3 1 2 4 3 1 2 4 Second stage heating not required on single stage heating units Second stage cooling not required on single stage...

Page 41: ...ct connections for down discharge supply return or horizontal discharge supply return and be available with factory installed options or field installed accessories The units shall be factory wired pi...

Page 42: ...on thermostat evaporator coil If any of the above safety devices trip a LED light emitting diode indicator shall flash a diagnostic code that indicates which safety switch has tripped d Unit shall inc...

Page 43: ...oor return air streams are available to provide free cooling based on single enthalpy or dual enthalpy configura tions respectively If free cooling is available a call for cooling shall modulate the e...

Page 44: ...COIL GUARD KIT Guard for cooling coil OTHER FACTORY INSTALLED OPTIONS POWER EXHAUST OPTION To work in conjunction with economizers STAINLESS STEEL HEAT EXCHANGER STAINLESS STEEL DRAIN PAN TECHNICOAT P...

Reviews: