036-21359-001-B-0302
6
Unitary Products Group
BLOWER PER FORM ANCE
- 25 TON (DCE/DCG300)
BLOWER
PULLEY
SPEED
TURNS
ESP
OUTPUT
INPUT
ESP
OUTPUT
INPUT
ESP
OUTPUT
INPUT
ESP
OUTPUT
INPUT
ESP
OUTPUT
INPUT
(rpm)
OPEN:
(iwg)
(bhp)
(kW)
(iwg)
(bhp)
(kW)
(iwg)
(bhp)
(kW)
(iwg)
(bhp)
(kW)
(iwg)
(bhp)
(kW)
975
6.0*
1.4
5.9
4.9
1.0
7.3
6.0
0.5
8.8
7.2
-
-
-
-
-
-
1005
5.0
1.6
6.2
5.1
1.2
7.7
6.3
0.7
9.2
7.6
0.1
10.9
8.9
-
-
-
1040
4.0
1.8
6.6
5.4
1.4
8.1
6.7
0.9
9.7
8.0
0.3
11.4
9.4
-
-
-
1070
3.0
2.0
6.9
5.7
1.6
8.5
7.0
1.1
10.2
8.3
0.6
11.9
9.8
-
-
-
1100
2.0
2.1
7.3
6.0
1.8
8.9
7.3
1.3
10.6
8.7
0.8
12.4
10.2
0.2
14.3
11.7
1135
1.0
2.4
7.7
6.3
2.0
9.3
7.6
1.6
11.1
9.1
1.0
13.0
10.6
0.4
14.9
12.2
1165
0.0
2.6
8.0
6.6
2.2
9.7
8.0
1.8
11.6
9.5
1.3
13.5
11.0
0.7
15.5
12.7
1140
6.0
2.4
7.7
6.3
2.1
9.4
7.7
1.6
11.2
9.2
1.1
13.1
10.7
0.5
15.0
12.3
1180
5.0
2.7
8.2
6.7
2.3
9.9
8.1
1.9
11.8
9.7
1.4
13.7
11.2
0.8
15.8
12.9
1215
4.0
2.9
8.6
7.0
2.6
10.4
8.5
2.2
12.3
10.1
1.7
14.3
11.7
1.1
16.4
13.5
1255
3.0
3.2
9.1
7.4
2.9
11.0
9.0
2.5
12.9
10.6
2.0
15.0
12.3
1.4
17.2
14.1
1290
2.0
3.4
9.5
7.8
3.1
11.5
9.4
2.7
13.5
11.1
2.2
15.6
12.8
-
-
-
1330
1.0
3.7
10.0
8.2
3.4
12.0
9.9
3.0
14.1
11.6
2.6
16.4
13.4
-
-
-
1365
0.0
3.9
10.5
8.6
3.7
12.6
10.3
3.3
14.7
12.1
2.9
17.0
13.9
-
-
-
NOTES:
Blower performance is based on cooling only unit, with fixed outdoor air, 2" T/A filters and a dry evaporator coil.
Refer to page 7 for additional static resistances.
ESP - External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the
blower.
* FACTORY SETTING
7500 CFM
8750 CFM
10000 CFM
11250 CFM
12500 CFM
STANDARD DRIVE:
ACCESSORY DRIVE:
DCE300
- BOT TOM DUCT CON NEC TIONS
(
COOL ING AP PLI CA TIONS)
BLOWER
PULLEY
SPEED
TURNS
ESP
OUTPUT
INPUT
ESP
OUTPUT
INPUT
ESP
OUTPUT
INPUT
ESP
OUTPUT
INPUT
ESP
OUTPUT
INPUT
(rpm)
OPEN:
(iwg)
(bhp)
(kW)
(iwg)
(bhp)
(kW)
(iwg)
(bhp)
(kW)
(iwg)
(bhp)
(kW)
(iwg)
(bhp)
(kW)
975
6.0*
1.2
5.9
4.9
0.5
7.3
6.0
-
-
-
-
-
-
-
-
-
1005
5.0
1.4
6.2
5.1
0.7
7.7
6.3
-
-
-
-
-
-
-
-
-
1040
4.0
1.6
6.6
5.4
0.9
8.1
6.7
0.2
9.7
8.0
-
-
-
-
-
-
1070
3.0
1.8
6.9
5.7
1.1
8.5
7.0
0.4
10.2
8.3
-
-
-
-
-
-
1100
2.0
2.0
7.3
6.0
1.3
8.9
7.3
0.6
10.6
8.7
-
-
-
-
-
-
1135
1.0
2.2
7.7
6.3
1.6
9.3
7.6
0.8
11.1
9.1
-
-
-
-
-
-
1165
0.0
2.4
8.0
6.6
1.8
9.7
8.0
1.0
11.6
9.5
0.2
13.5
11.0
-
-
-
1140
6.0
2.2
7.7
6.3
1.6
9.4
7.7
0.9
11.2
9.2
-
-
-
-
-
-
1180
5.0
2.5
8.2
6.7
1.9
9.9
8.1
1.2
11.8
9.7
0.3
13.7
11.2
-
-
-
1215
4.0
2.7
8.6
7.0
2.1
10.4
8.5
1.4
12.3
10.1
0.6
14.3
11.7
-
-
-
1255
3.0
3.0
9.1
7.4
2.4
11.0
9.0
1.7
12.9
10.6
0.9
15.0
12.3
-
-
-
1290
2.0
3.2
9.5
7.8
2.7
11.5
9.4
2.0
13.5
11.1
1.2
15.6
12.8
-
-
-
1330
1.0
3.5
10.0
8.2
3.0
12.0
9.9
2.3
14.1
11.6
1.5
16.4
13.4
-
-
-
1365
0.0
3.7
10.5
8.6
3.2
12.6
10.3
2.6
14.7
12.1
1.8
17.0
13.9
-
-
-
NOTES:
Blower performance is based on cooling only unit, with fixed outdoor air, 2" T/A filters and a dry evaporator coil.
Refer to page 7 for additional static resistances.
ESP - External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the
blower.
* FACTORY SETTING
STANDARD DRIVE:
ACCESSORY DRIVE:
7500 CFM
8750 CFM
10000 CFM
11250 CFM
12500 CFM
BLOWER PERFORMANCE
- 25 TON (DCE/DCG300)
DCG300
- BOT TOM DUCT CON NEC TIONS
(
COOL ING AP PLI CA TIONS)
Summary of Contents for D2CE
Page 13: ...036 21359 001 B 0302 Unitary Products Group 13 BASE RAIL 3 56 3 69...
Page 14: ...036 21359 001 B 0302 14 Unitary Products Group...
Page 19: ...036 21359 001 B 0302 Unitary Products Group 19...
Page 20: ...036 21359 001 B 0302 20 Unitary Products Group...
Page 21: ...036 21359 001 B 0302 Unitary Products Group 21...
Page 22: ...036 21359 001 B 0302 22 Unitary Products Group...
Page 23: ...036 21359 001 B 0302 Unitary Products Group 23...