Evaporator and Condenser coils shall be of the
direct expansion, draw-thru, design.

C.

Condenser coils shall be protected with factory
installed coil guards

3.

Refrigerant Circuit and Refrigerant Safety Compo-
nents shall include:

A.

Balance-port thermostatic expansion valve with
independent circuit feed system.

B.

Filter drier/strainer to eliminate any moisture or for-
eign matter.

C.

Accessible service gage connections on both suc-
tion and discharge lines to charge, evacuate, and
measure refrigerant pressure during any necessary
servicing or troubleshooting, without losing charge.

D.

The refrigeration system shall provide at least 15 °F
of sub-cooling at design conditions.

E.

All Models shall have two independent circuits..

4.

Unit Controls:

A.

Unit shall be complete with self contained low-volt-
age control circuit protected by a resetable circuit
breaker on the 24 volt transformer side.

B.

Unit shall incorporate a lock-out circuit which pro-
vides reset capability at the space thermostat or
base unit, should any of the following standard
safety devices trip and shut off compressor:

1.

Loss-of-charge/Low-pressure switch.

2.

High-pressure switch.

3.

Freeze-protection thermostat, evaporator coil.

If any of the above safety devices trip, an LED (light-
emitting diode) indicator shall illuminate.

C.

Unit shall incorporate “AUTO RESET” compressor
over temperature, over current protection.

D.

Unit shall operate with conventional thermostat
designs and have a low voltage terminal strip for
easy hook-up.

GAS HEATING SECTION (DCG MODELS)

1.

Shall be designed with induced draft combustion
with post purge logic and energy saving direct
spark ignition, redundant main gas valve. Ventor
wheel shall be constructed of stainless steel for
corrosion resistance.

2.

The heat exchanger shall be of the tubular type,
constructed of T1-40 aluminized steel for corrosion

resistance and allowing minimum mixed air enter-
ing temperature of 25 °F.

3.

Burners shall be of the in-shot type, constructed of
aluminum coated steel and contain air mixture
adjustments.

4.

All gas piping shall enter the unit cabinet at a single
location through either the side or curb, without any
field modifications.

5.

An integrated control board shall provide timed
control of evaporator fan functioning and burner
ignition.

6.

Heating section shall be provided with the following
minimum protection:

A.

Primary

and

auxiliary

high-temperature

limit

switches.

B.

Induced draft motor speed sensor.

C.

Flame roll out switch (manual reset).

D.

Flame proving controls.

7

Unit shall have two independent stages of capacity.

ELECTRIC HEATING (DCE MODELS)

1.

Nickel chromium electric heating elements shall be
provided as required by the application with 1 or 2
stage control, as required, from 13.5 KW to 72 KW
capacity.

2.

The heating section shall have a primary limit con-
trol(s) and automatic reset to prevent the heating
element system from operating at an excessive
temperature.

3.

Units with Electric Heating shall be wired for a sin-
gle point power supply with branch circuit fusing
(where required).

UNIT OPERATING CHARACTERISTICS

1.

Unit shall be capable of starting and running at 125
°F outdoor temperature, exceeding maximum load
criteria of ARI Standard 210/240.

2.

The compressor, with standard controls, shall be
capable of operation down to 25 °F outdoor tem-
perature. Accessory low ambient kit shall be avail-
able for operation to 0 °F.

3.

Unit shall be provided with fan time delay to pre-
vent cold air delivery before heat exchanger warms
up. (Gas heat only)

Summary of Contents for D2CE

Page 1: ...de an exceptionally durable finish with the 750 hour salt spray process per ASTM B117 test standard All models including those with an economizer are suit able for either bottom or horizontal duct con...

Page 2: ...knockout in the wiring panel on the front of the unit All internal factory wiring is color coded and numbered for ease in servicing and troubleshooting FACTORY INSTALLED OPTIONS ECONOMIZERS Interlock...

Page 3: ...assembly They re designed to fit inside the base rails of the unit and include both a wood nailing strip and duct hanger sup ports ANTI RECYCLE TIMERS Two solid state timers prevent the compressors fr...

Page 4: ...w e r S u p p l y w i t h E l e c t r i c H e a t E L E C T R I C E L E C T R I C U N I T S E L E C T R I C H E A T E R L O C A T I O N O P T I O N A L E L E C T R I C E L E C T R I C U N I T S I 2 0...

Page 5: ...er Coil 105 F 115 F Total Cap 1 MBH Power Input2 KW SensibleCapacity1 MBH Total Cap 1 MBH Power Input2 KW SensibleCapacity1 MBH CFM WB F En ter ing Dry Bulb F En ter ing Dry Bulb F 86 83 80 77 74 71 6...

Page 6: ...resistances have been deducted from the total static pressure of the blower FACTORY SETTING 7500 CFM 8750 CFM 10000 CFM 11250 CFM 12500 CFM STANDARD DRIVE ACCESSORY DRIVE DCE300 BOT TOM DUCT CON NEC T...

Page 7: ...18 KW 25 36 KW 30 54 KW 35 72 KW 40 Accesso ries Roof Curb 185 BarometricDamper 45 Economizer MotorizedDamper Rain Hood 55 Economizer PowerExhaustRain Hood 90 Wood Skid 220 OPERATING WEIGHTS ELECTRICA...

Page 8: ...140 1365 1B5V94 9 7 9 5 1 7 16 5VX840 84 0 1 1All mo tors have a nomi nal speed of 1800 RPM a 1 15 serv ice fac tor and a solid base They can op er ate to the limit of their serv ice fac tor be cause...

Page 9: ...n o t r e q u i r e d o n u n i t s w i t h a s i n g l e s t a g e e l e c t r i c h e a t e r C O O L I N G H E A T I N G E L E C T R O N I C T H E R M O S T A T T H E R M O S T A T 1 T E R M I N A...

Page 10: ...H RAILS Shown separately to illustrate Bottom Duct openings Power and Gas Piping Connection locations 12 1 2 9 1 4 8 1 8 9 3 4 3 3 4 B POWER WIRING ENTRY A CONTROL WIRING ENTRY 92 CONDENSER COILS OPTI...

Page 11: ...he rear of the unit SUPPLY AIR RETURN AIR OUTDOOR AIR 5 1 8 18 5 8 27 3 4 29 5 8 15 TON 39 5 8 20 TON 40 1 2 OUTDOOR AIR COMPARTMENT ACCESS FILTER ACCESS 1 NPT FEMALE COND DRAIN CONNECTION DOT PLUG Fo...

Page 12: ...ized motor 4 Point Loads 6 Point Loads DCE UNIT 4 POINT LOADS LBS TOTAL A B C D 300 2 890 487 619 646 508 DCE UNIT 6 POINT LOADS LBS TOTAL A B C D E F 300 2 890 415 471 528 551 492 433 DCG UNIT 4 POIN...

Page 13: ...036 21359 001 B 0302 Unitary Products Group 13 BASE RAIL 3 56 3 69...

Page 14: ...036 21359 001 B 0302 14 Unitary Products Group...

Page 15: ...measuring ports shall be pro vided on the outside of the cabinet to allow accu rate air measurements of evaporator fan performance without removing panels or creating air by pass of the coils 7 Conden...

Page 16: ...spark ignition redundant main gas valve Ventor wheel shall be constructed of stainless steel for corrosion resistance 2 The heat exchanger shall be of the tubular type constructed of T1 40 aluminized...

Page 17: ...e outdoor and return air damper assembly to take in the design CFM of outdoor air to meet the mini mum ventilation requirement of the conditioned space during normal operation During economizer operat...

Page 18: ...pulley and belt for higher CFM and or static pressure require ments 9 WOOD SKID Allows unit to be handled with 90 forks 10 ECONOMIZER MOTORIZED DAMPER RAIN HOOD DCE CG300 only Contains all hood panels...

Page 19: ...036 21359 001 B 0302 Unitary Products Group 19...

Page 20: ...036 21359 001 B 0302 20 Unitary Products Group...

Page 21: ...036 21359 001 B 0302 Unitary Products Group 21...

Page 22: ...036 21359 001 B 0302 22 Unitary Products Group...

Page 23: ...036 21359 001 B 0302 Unitary Products Group 23...

Page 24: ...ge without notice Printed in U S A CD 6 21359 036 21359 001 B 0302 Copyright by Unitary Products Group 2002 All rights reserved Supersedes 036 21359 001 A 0302 Unitary 5005 Norman Products York OK Gro...

Reviews: