DUCTWORK

Ductwork should be designed and sized according to the
methods in Manual Q of the Air Conditioning Contractors of
America (ACCA).
A closed return duct system shall be used. This shall not
preclude use of economizers or outdoor fresh air intake. The
supply and return air duct connections at the unit should be
made with flexible joints to minimize noise.
The supply and return air duct systems should be designed for
the CFM and static requirements of the job. They should NOT
be sized to match the dimensions of the duct connections on
the unit.
CAUTION: When fastening ductwork to side duct flanges on

unit, insert screws through duct flanges only. DO
NOT insert screws through casing.
O ut do or   du ct wor k  m us t  be   ins ul ate d  a nd
waterproofed.

Refer to Figure 10 for information concerning side and bottom
supply and return air duct openings.

FIXED OUTDOOR AIR INTAKE DAMPER 

This damper is shipped inside the return air compartment on units
that are not provided with an economizer or a motorized damper
option. It is completely assembled and ready for installation. A
damper baffle inside of the hood is adjustable to provide variable
amounts of outdoor air intake. Refer to Figure 3.

Gasketing and mounting screws are provided in a parts bag
attached to the hood assembly. Apply gasketing to the three
flange surfaces on the hood prior to installing the hood. Extend
gasketing 1/4" beyond the top and bottom of the two side
flanges to insure adequate sealing.

Adjusting the damper to the desired air flow may be done
before mounting the hood into position or (after installation) by
removing the front hood panel or the screen on the bottom of
the hood. Damper baffle in position 1 will allow approximately
10% recirculated air flow, position 2 approximately 15% and,
to allow approximately 25%, remove the damper baffle.

On units with bottom return air applications, install the damper
assembly over the opening in the side return air access panel.
Remove and discard the opening cover and the covering over
the hood mounting holes (used for shipping) before installing.
Secure with the screws provided.

On units with side return air applications, install the damper
assembly on the return air ductwork as close to the unit as
possible. Cut an opening 16" high by 18" wide in the ductwork
to accommodate the damper. Using the holes in the hood
flanges as a template, drill 9/64" dia. (#26 drill) holes into the
ductwork and secure with the screws provided.

CAUTION: If outdoor air intake will not be required on units

with bottom return air applications, the damper
assembly should still be mounted on the side return
air access panel, per the instructions above, to
insure moisture is not drawn into the unit during
operation. The covering over the mounting holes
only need be removed. Do not remove the opening
cover.

CONDENSATE DRAIN

Plumbing must conform to local codes. Use a sealing
compound on male pipe threads. Install a condensate drain line
from the 1" NPT female connection on the unit to an open drain.
An alternate drain connection (1" NPT female coupling) is
provided inboard on the same centerline as the exterior
location.

NOTE: The condensate drain line MUST be trapped to provide

proper drainage. See Figure 4.

COMPRESSORS

Units are shipped with compressor mountings factory-adjusted
and ready for operation.
CAUTION: Do Not loosen compressor mounting bolts.

FILTERS

2" filters are supplied with each unit. Filters must always be
installed ahead of the evaporator coil and must be kept clean
or replaced with same size and type. Dirty filters will reduce the
capacity of the unit and will result in frosted coils or safety
shutdown. Minimum filter area and required sizes are shown
in Table 4.

SERVICE ACCESS

Access to all serviceable components is provided by the
following removable panels:

Compressor compartment

Electric Heat compartment - DCE models

Gas Heat compartment (Two panels) - DCG models

Side Supply & Return Air compartments (Two panels)

Blower compartment (Three panels)

Main control box

Filter compartment

Outdoor Air compartment (Two panels)

Refer to Figure 10 for location of these access panels.
CAUTION: Make sure that all screws and panel latches are

replaced and properly positioned on the unit to
maintain an air-tight seal.

FIG. 3 - FIXED OUTDOOR AIR DAMPER

58-1/4

FIG. 4 - RECOMMENDED DRAIN PIPING

It is recommended that, in Canada, the outlet duct on gas
heating units be provided with a removable access panel. It
is recommended that this opening be accessible when the unit
is installed in service, and of a size such that smoke or
reflected light may be observed inside the casing to indicate
the presence of leaks in the heat exchanger. The cover should
be attached in a manner adequate to prevent leakage.

530.18-N11Y

4

Unitary Products Group

Summary of Contents for D1CE

Page 1: ...6 1V Propane Conversion Accessory 530 18 N6 2V High Altitude Accessory Nat Gas 530 18 N6 3V High Altitude Accessory Propane Renewal Parts Refer to the Renewal Parts Manual for complete listing of repl...

Page 2: ...trical Data Basic Units 10 6 Electrical Data Units With Elec Heat 10 7 Supply Air Blower Performance 13 8 Static Resistances 14 9 Power Exhaust Performance 14 10 Blower Motor and Drive Data 14 11 Heat...

Page 3: ...talled on a solid level roof curb or appropriate angle iron frame CAUTION If a unit is to be installed on a roof curb or special frame other than a YORK roof curb gasketing must be applied to all surf...

Page 4: ...uctwork to accommodate the damper Using the holes in the hood flanges as a template drill 9 64 dia 26 drill holes into the ductwork and secure with the screws provided CAUTION If outdoor air intake wi...

Page 5: ...FIG 5 TYPICAL FIELD WIRING Wire Size 1 AWG Gauge 22 20 19 18 16 40 120 150 190 305 Maximum Wire Length2 Feet Notes 1 Solid Class II copper wire CONTROL WIRE SIZES 530 18 N11Y Unitary Products Group 5...

Page 6: ...ons and to Table 6 for electrical data COMBUSTION DISCHARGE DCG Models The products of combustion are discharged horizontally through two screened hooded openings on the upper gas heat access panel GA...

Page 7: ...ediately upstream of the gas supply connection to the furnace L P UNITS TANKS AND PIPING DCG Models All gas heat units are shipped from the factory equipped for natural gas use only The unit may be co...

Page 8: ...but do not remove the two panel latches CAUTION Extreme care must be exercised in turning both the setpoint and minimum position adjusting screws to prevent twisting them off 1 The enthalpy set point...

Page 9: ...FIG 9 ENTHALPY SETPOINT ADJUSTMENT 530 18 N11Y Unitary Products Group 9...

Page 10: ...breaker 2 Although these sizes are based on 75 C copper conductors aluminum wire can be used Refer to the National Electric Code in U S A or the current Canadian Electrical Code in Canada to determine...

Page 11: ...be provided between any combustible material and the supply air ductwork for a distance of 3 feet from the unit The products of combustion must not be allowed to accumulate within a confined space an...

Page 12: ...sheet metal covers except when the unit includes a power exhaust option The covering consists of a heavy black paper composition 3 Replace the side supply and return air compartment panels For side du...

Page 13: ...12 2 2 0 16 6 13 9 HIGH SPEED DRIVE ACCESSORY 1118 6 0 2 3 8 8 7 4 1 8 10 3 8 6 1 3 11 9 10 0 0 7 13 6 11 4 0 2 15 4 12 9 1170 5 0 2 7 9 4 7 9 2 2 11 0 9 2 1 7 12 7 10 6 1 1 14 5 12 2 0 5 16 4 13 7 12...

Page 14: ...pulley below 1 turn open MOTOR SPEED STATIC RESISTANCE OF RETURN DUCTWORK IWG 0 2 0 3 0 4 0 5 0 6 CFM KW CFM KW CFM KW CFM KW CFM KW HIGH 5250 0 83 4500 0 85 4200 0 88 3750 0 93 3000 0 99 MEDIUM 4900...

Page 15: ...operate if the fan switch on the room thermostat is set in the ON position ECONOMIZER WITH DUAL ENTHALPY SENSORS The operation with the dual enthalpy sensors is identical to the single sensor except t...

Page 16: ...and the main gas valve opened Gas flows into each of the second stage main burners and is ignited from the carryover tube flame If IC2 fails to detect a pilot flame it will continue to try for a maxi...

Page 17: ...e these limits contact the local gas utility for corrective action MANIFOLD GAS PRESSURE ADJUSTMENT Small adjustments to the high fire gas flow may be made by turning the pressure regulator adjusting...

Page 18: ...resistances of both the supply and the return air duct systems With this information the RPM for the supply air blower and themotor pulley adjustment turns open can bedeterminedfrom the blower perform...

Page 19: ...and drive data CHECKING GAS INPUT NATURAL GAS 1 Turn off all other gas appliances connected to the gas meter 2 With the furnace turned on measure the time needed for one revolution of the hand on the...

Page 20: ...tructed by overhanging structures of shrubs GAS HEATING UNITS BURNER PILOT Periodically at least annually at the beginning of each heating season make a visual check of the pilot and main burner flame...

Page 21: ...go to Step f If it does not check to see if line voltage is being supplied to the contacts of the contactor 3M and if the contactor is pulled in Check for loose wiring b If contactor 3M is pulled in p...

Page 22: ...ILOT CHECKOUT b Check all wiring between the ignitor control and the gas valve Check to make sure the ground connections are intact c If the wiring is intact check for 24 volts across terminals PV and...

Page 23: ...530 18 N11Y Unitary Products Group 23...

Page 24: ...ary Products Group P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in U S A Copyright by York International Corporation 1995 All Rights Reserved Code SBY 530 18...

Reviews: