TABLE 3 - ELECTRICAL DATA
DSC
Model
Compressors
Supply Air Blower Motor
(3-Phase)
Condenser Fan Motors
(1-Phase)
Unit
Ampa-
city,
Amps
Max.
Fuse
Size,
3
Amps
Min. Wire
Size,
4
AWG/MCM
Max.
Wire
Length,
5
Ft.
Volts
Nom.
Tons(*)
RLA
LRA
Power
Factor
2
Volts
HP
FLA
Volts
HP(*)
FLA
360
17
208
30 (1)
126
565
0.90
200
10
15
32
48
200
1/2 (6) 3.4 ea.
210.0
230.0
250
300
0000
225
205
28
230
30 (1)
122
565
0.81
230
10
15
28
42
230
1/2 (6) 3.4 ea.
205.0
215.0
250
0000
250
235
46
460
30 (1)
61
283
0.81
460
10
15
14
21
460
1/2 (6) 2.0 ea.
105.0
110.0
125
2
400
385
58
575
30 (1)
49
230
0.81
575
10
15
11
17
460
6
1/2 (6) 2.0 ea.
85.0
95.0
100
110
4
3
405
450
480
17
208
20 (2)
80 ea.
374
0.90 ea.
208
15
20
48
59
200
1/2 (6) 3.4 ea.
248.4
259.4
300
250
300
205
220
28
230
20 (2)
80 ea.
374
0.81 ea.
230
15
20
42
54
230
1/2 (6) 3.4 ea.
242.4
254.4
300
250
230
220
46
460
20 (2)
40 ea.
187
0.81 ea.
460
15
20
21
27
460
1/2 (6) 2.0 ea.
123.0
129.0
150
1
405
390
58
575
20 (2) 32.3 ea. 135
0.81 ea.
575
15
20
17
22
460
6
1/2 (6) 2.0 ea.
101.7
106.7
125
2
500
480
*
Quantity listed in ( ).
1
Refer to the following table for electrical data of unit with exhaust air fans.
4
Based on three 75ÉC, insulated copper conductors in steel conduit.
2
Rated at a 45ÉET and a 130ÉCT.
5
Based on a 3% voltage drop.
3
Dual element, time delay type.
6
A 575 to 460 volt transformer is provided for these motors.
ELECTRICAL DATA (UNITS WITHOUT EXHAUST AIR FANS )
1
DSC
Model
Supply Air
Blower Motor HP
Exhaust Air Fan Motors
(1-Phase)
Unit
Ampacity
Amps
Max. Fuse
Size,
2
Amps
Min. Wire Size,
3
AWG/MCM
Max. Wire
Length,
4
Ft.
Volts
HP(*)
FLA
360
17
10
15
200
3/4 (2)
4.2 ea.
220.0
235.0
250
300
0000
250
215
220
28
10
15
230
3/4 (2)
4.2 ea.
210.0
225.0
250
300
0000
245
225
46
10
15
460
3/4 (2)
2.4 ea.
110.0
115.0
125
150
2
385
365
58
10
15
460
5
3/4 (2)
2.4 ea.
90.0
100.0
110
3
475
425
480
17
15
20
200
3/4 (3)
4.2 ea.
261.0
272.0
300
350
300
275
250
28
15
20
230
3/4 (3)
4.2 ea.
255.0
267.0
300
250
300
250
300
46
15
20
460
3/4 (3)
2.4 ea.
130.2
136.2
150
175
0
375
375
58
15
20
460
5
3/4 (3)
2.4 ea.
108.9
113.9
125
2
2
375
375
*
Quantity listed in ( ).
3
Based on three 75ÉC, insulated copper conductors in steel conduit.
1
Refer to the table above for electrical data on compressors and fan motors.
4
Based on a 3% voltage drop.
2
Dual element, time delay type.
5
A 575 to 460 volt transformer is provided for these motors.
ELECTRICAL DATA (UNITS WITH EXHAUST AIR FANS )
1
530.25-N3Y
10
Unitary Products Group