background image

CRANKCASE HEATERS

It is important that the crankcase heaters be energized 8 hours
before starting the compressors. To energize the crankcase
heaters, the room thermostat or status panel system switch
must be open to prevent the compressor from starting. If a
disconnect switch is installed outside the unit, turn it to “ON”.
The nonfused disconnect (optional) located in the unit’s main
supply panel must also be turned “ON”.

CAUTION: Do not attempt to start the compressors without at

least 8 hours of crankcase heat or compressor
damage will occur.

SAFETY AND SERVICE FEATURES

The control circuit includes the following safety features:

1. The supply air blower motor is protected with manual reset

starter overload protectors.

2. The condenser fan motors have inherent protection with

automatic reset.

3. The primary winding of transformer 1T is protected by fuse

12FU. The secondary winding and the 115 volt control
circuit are protected by fuse 13FU.

4. All safety controls in the 115 volt circuit have the “return” or

“common” side of the 1T transformer grounded. Fuse 13FU
will “BLOW” whenever a dangerous condition occurs. The
unit casing is also grounded.

5. The wiring to each compressor motor, each condenser fan

motor and the supply air blower motor are individually fused
according to the National Electrical Standards.

6. The compressor(s) are protected by a 100 watt immersion

type crankcase heater(s). Heater(s) are energized when-
ever power is supplied to the unit. When the compressor(s)
are energized, the heater(s) are turned off.

CAUTION: Do not attempt to start the compressors without at

least 8 hours of crankcase heat or compressor
damage will occur.

7. Each refrigeration system has a low pressure cutout (1LP

for system No. 1 and 2LP for system No. 2) to shut down
the compressor due to loss of refrigerant charge or a build
up of frozen condensate on the compressor before the
suction valve and are set to open when the suction pressure
drops to 7 psig. These controls will automatically reset when
the suction pressures rise to 22 psig. The opening of the
low pressure cutouts will activate the lockout circuit.

8. High pressure cutouts (1HP for system No. 1 and 2HP for

system No. 2) are located in each system on the compres-
sor before the discharge valve. Should a system discharge
pressure exceed 398 psig, the control will open and de-en-
ergize the compressor. The pressure cutout will close when
the discharge pressure drops to 310 psig. The opening of
the high pressure cutout will activate the lockout circuit. The
high pressure cutouts may open due to a dirty or restricted
condenser coil, loss of air flow or too high an ambient air
temperature.

9. The lockout circuits mentioned above will not be energized

during normal operation because they have a high resis-

tance. The flow of electricity will normally follow the path of
least resistance through the compressor contactors 1M and
2M. If, however, a low or high pressure cutout opens, the
lockout relay 10R or 11R will be energized. Since the
voltage across 10R or 11R will exceed 100V, the voltage
across 1M or 2M will be too low to pull in the contactors.
The normally closed contacts of 10R or 11R will open the
circuit in series with the low or high pressure cutout. When
these contacts automatically close, the lockout circuit can
be reset by interrupting the control circuit at the room
thermostat. Two advantages are gained by this circuit:

a. Prevents rapid cycling of the compressors which can be

damaging.

b. The alternate use of manual reset cutoffs avoids the

problem above but may require an expensive service
call to reset these controls.

10. Freezestat 3TH senses the suction temperature of the No.

1 system and will shut down compressor(s) when this
temperature drops to 32ÉF. It will reset automatically at
37ÉF

11. The supply air flow must be proven by vacuum switch 5LP.

In the event the belts on the supply air motor break or the
supply air motor should be de-energized by its oveload
protectors, 5 LP will open and interrupt the cooling, heating
and economizer control circuits. This assures that the
various modes of operation do not continue without proper
air flow.

12. The compressor motor protector(s), 1MP, 2MP will interrupt

the compressor control circuit when sensing an overload
condition. Also an anti-recycle timer is part of this device to
prevent the compressor from rapid cycling. The compressor
will stay off for five minutes. It also monitors the voltage of
the 120 volt control circuit and will shut down the
compressor if the voltage drops below 85 æ4.5 volts.

13. Oil pressure control switches are installed in the compres-

sor circuits. These assure that adequate oil pressure is
present to lubricate the moving parts of the compressor. If
pressure is not adequate, the switch opens shutting down
the compressor. It is manually reset.

14. When the pumpdown accessory, Model 2PD04700101, is

installed, the compressor will continue to operate through
contact 12TR-2 after the room thermostat or controller is
satisfied.

Solenoid 3SOL in the liquid line is now closed and the
compressor pumps most of the refrigerant out of the evapo-
rator to the high side of the system. The system suction
pressure drops until the low pressure cutoff (1LP) opens.
This will shut down the compressor and de-energizes the
12TR relay which opens 12TR-2 to put the operation of the
compressor under the control of the 1R relay. Also present
is a 12TR-1 contact which is closed when the system is off
and provides a bypass circuit to allow contactors 1M and
2M to be activated in the event the low pressure cutout has
not reset. Without this pumpdown circuit, it is possible to
have the oil pressure switch (OP/PS) open on light load and
short cycle of the compressor. Refrigerant floods back to
the compressor on each start-up, foams the oil in the
compressor crankcase and pumps the oil to the conden-
sate coil. The run times are too short to bring the oil back

START-UP

530.25-N3Y

Unitary Products Group

23

Summary of Contents for D*SC360

Page 1: ...te request for inspection by the carrier s agent should be made in writing Refer to Form 50 15 NM for additional information REFERENCE Additional information on the design installation operation and service of this equipment is available in the following reference forms 55 70 N1 General Installation 55 70 N2 Pre start Post start Check List Renewal Parts Refer to the Renewal Parts Manual for comple...

Page 2: ...ta 21 10 Resistances Unit Options Accessories 21 11 Supply Air Blower Performance 22 FIGURES No Description Page 1 Unit Less Panels 3 2 Typical Rigging 3 3 Center of Gravity 3 4 Recommended Drain Piping 4 5 Bottom Power Wiring Entrance 5 6 Side Power Wiring Entrance 5 7 Control Wiring Entrance DSC360 6 8 Control Wiring Entrance DSC480 6 9 Control Wiring Conns w o Status Panel 7 10 Control Wiring C...

Page 3: ... mounting curbs capable of supporting the unit s weight may also be field fabricated CLEARANCES These units must be installed with the minimum clearances listed below A 2 clearance within 3 feet of the unit must be maintained between any combustible material and the supply air duct work No objects should be left near the combustion air inlet to obstruct the openings If the unit is slab mounted shr...

Page 4: ... 90 degrees clockwise to facilitate entrance of the power wiring from the side of the box To do this remove the 1 4 bolt holding the power lug Next remove the slotted spring pin which keeps the lug from rotating Turn the power lug 90 degrees clockwise and replace both the slotted spring pin and the 1 4 bolt MODEL DSC 360 480 Voltage Variation Min Max1 200 Volts 187 218 230 Volts 216 252 460 Volts ...

Page 5: ...s the power wiring is already above the finished roof 2 Units that are mounted on structural steel above the finished roof unless the steel is blocking the 4 1 2 diameter sleeve in the base of the unit This applies to units with or without a factory installed disconnect switch CAUTION The 4 1 2 sleeve must be sealed after the power wiring has been routed to prevent pos sible condensation problems ...

Page 6: ...ugh the side entry must be sealed to prevent the entrance of water CONTROL WIRING MODEL DSC480 For bottom entry Figure 8 the control wiring should be routed 1 Up through the 2 1 4 O D tubing behind the control box 2 Through the positioned ty wrap on the outside of the control box 3 Through the 1 3 8 snap bushing in the control box 4 Through the 2 ty wraps positioned in the control box 5 Connect th...

Page 7: ...FIG 9 CONTROL WIRING CONNECTIONS WITHOUT STATUS PANEL 530 25 N3Y Unitary Products Group 7 ...

Page 8: ...FIG 10 CONTROL WIRING CONNECTIONS WITH STATUS PANEL 530 25 N3Y 8 Unitary Products Group ...

Page 9: ...FIG 11 CONTROL WIRING CONNECTIONS SOLID STATE CONTROL WITH STATUS PANEL FIG 12 CONTROL WIRING CONNECTIONS SOLID STATE CONTROL WITH STATUS PANEL 530 25 N3Y Unitary Products Group 9 ...

Page 10: ...air fans 4 Based on three 75ÉC insulated copper conductors in steel conduit 2 Rated at a 45ÉET and a 130ÉCT 5 Based on a 3 voltage drop 3 Dual element time delay type 6 A 575 to 460 volt transformer is provided for these motors ELECTRICAL DATA UNITS WITHOUT EXHAUST AIR FANS 1 DSC Model Supply Air Blower Motor HP Exhaust Air Fan Motors 1 Phase Unit Ampacity Amps Max Fuse Size 2 Amps Min Wire Size 3...

Page 11: ...g FF 1 1 2 Pipe 360 480 Drain Conn GG 2 5 8 KO 360 480 Gas Heat Piping1 HH 2 3 8 KO 360 Gas Heat Piping2 JJ 1 1 8 KO 360 480 Control Wiring KK 3 5 8 KO 480 Power Wiring LL 3 5 8 KO 360 Power Wiring 1 Heating Option G560 G800 2 Heating Option G400 DIM MODEL DSC 360 480 A 164 184 B 32 32 C 100 120 D 100 120 E 4 5 8 F 5 G 5 5 8 H 11 1 4 J 42 K 55 1 2 L 65 M 73 N 57 3 8 77 1 2 FRONT Control Box Side 3...

Page 12: ... by the unit is absorbed in the chamber and not transmitted to the condi tioned space The chamber may be constructed of fiberglass duct or metal duct lined with sound absorption material Ceiling return grilles should be located a minimum of 12 feet from the end of the sound chamber In every installation a return air duct must be installed to the unit FILTERS All filters being used in these units a...

Page 13: ...tside and return air dampers should be checked to make sure they operate freely and close tightly It may be necessary to readjust the linkage between the damper motor and the blades due to loosening in shipment Readjust linkage as follows 1 Turn the minimum outside air adjuster to the 100 outside air position All return air damper blades should be fully closed Be sure that the spring return damper...

Page 14: ...oses in the compressor control circuit NOTE The above operation is for intermittent fan operation For continuous operation the fan switch on the room thermostat or the status panel should be manually closed to energize 7R 6 Relay contact 1R closes and energizes 1M coil which starts the No 1 compressor At the same time 4M coil is energized to start the condenser fans 7 If the room temperature conti...

Page 15: ...ll not allow outdoor air to enter the unit during high humidity conditions except at a lower outdoor temperature During dry conditions air is introduced at a higher ambient The outdoor and return air dampers are controlled by the logic panel The discharge sensor acts as a modulating low limit which senses the temperature of the air leaving the evaporator coil If at any time during the cooling cycl...

Page 16: ...he compressor un loading solenoid which loads the compressor 9 The compressor short cycle time and low voltage protection is part of the solid state compressor protection module It prevents a compressor from starting unless it has been off for five minutes It also monitors the voltage of the 120 volt control circuit and will shut down the compressor if the 120 volt control voltage drops below 85 æ...

Page 17: ...erence line The recommended deflection force is as follows e Tension new belts at the maximum deflection force recommended for the belt section Check the belt ten sion at lease two times during the first 24 hours of operation Any retensioning should fall between the minimum and maximum deflection force values f After adjusting retighten nuts A 5 All pulleys are factory aligned 6 All supply air mot...

Page 18: ...f operation check all belts and pulleys for tightness and align ment WARNING Failure to properly adjust the total system CFM can result in extensive blower damage FIG 17 HOLE LOCATIONS FOR SUPPLY AIR CFM CHECK FIG 18 PRESSURE DROP ACROSS A DRY EVAPORATOR COIL VS SUPPLY AIR CFM MODEL OF NOMINAL CFM 80 90 100 110 120 CFM DSC360 9600 10800 12000 13200 14400 DSC480 12800 14400 16000 17600 19200 MASTER...

Page 19: ...Off On On Fan Compr 1 On O S A dampers operate to setting of mixed air control Compr 1st Stage Cool Off St 1 Cpr Auto On Off Off Off On Off Off On Fan Compr 1 On with O S A dampers open to min position Compr 2nd Stage Cool Off St 1 St 2 Cpr Auto On Off Off Off On On Off On Fan Compr 1 2 run with O S A dampers open to min position Heat 1st Stage Heat St 1 Off Auto On Off On Off Off Off Off On Heat ...

Page 20: ...FIG 19 FIXED OUTDOOR AIR ADJUSTMENT FIG 20 EXHAUST AIR PERFORMANCE 530 25 N3Y 20 Unitary Products Group ...

Page 21: ...haust Air 022 028 035 042 050 Return Air Damper for Economizer End Duct Connection 179 226 279 338 402 Return Air Damper for Economizer Side by Side Btm Duct 077 097 120 145 173 2 30 Efficient Filters1 007 009 011 014 016 Bag Type Filters1 056 071 089 107 127 End Duct Connections2 143 181 224 271 323 480 12800 14400 16000 17600 19200 G560 Gas Heat 038 049 06 073 086 G800 Gas Heat 051 065 08 097 11...

Page 22: ...W SP BHP KW SP BHP KW SP BHP KW 900 1 12 8 84 7 55 0 75 10 11 8 76 0 30 11 59 10 03 950 1 42 9 73 8 44 1 05 11 17 9 66 0 60 12 73 11 02 1000 1 72 10 59 9 16 1 36 12 19 10 55 0 92 13 78 11 96 0 42 15 45 13 49 1050 2 00 11 50 9 95 1 66 13 16 11 40 1 23 14 78 12 86 0 76 16 56 14 53 0 21 18 45 16 23 1100 2 30 12 27 10 62 1 98 14 10 12 24 1 58 15 83 13 84 1 10 17 61 15 49 0 55 19 54 17 28 1150 2 62 13 ...

Page 23: ... 1Mand 2M If however a low or high pressure cutout opens the lockout relay 10R or 11R will be energized Since the voltage across 10R or 11R will exceed 100V the voltage across 1M or 2M will be too low to pull in the contactors The normally closed contacts of 10R or 11R will open the circuit in series with the low or high pressure cutout When these contacts automatically close the lockout circuit c...

Page 24: ... Check the compressor amps with the unit data plate 8 After approximately 15 minutes of operation check the liquid line sight glasses for a proper liquid refrigerant seal in each of the refrigerant circuit s 9 Next increase the setting of the room thermostat until the heating contacts are energized 10 Refer to the proper heating installation and operation instruction for the correct heating sequen...

Page 25: ...After the unit is functioning properly instruct the owner and operator on how to operate the unit Replace all panels before leaving the job site 530 25 N3Y Unitary Products Group 25 ...

Reviews: