TABLE 11 - SUPPLY AIR BLOWER PERFORMANCE
Blower
RPM
CFM
9600
10800
12000
13200
14400
SP
BHP
KW
SP
BHP
KW
SP
BHP
KW
SP
BHP
KW
SP
BHP
KW
800
0.97
4.71
4.09
0.76
5.46
4.71
0.48
6.16
5.30
-
-
-
-
-
-
850
1.18
5.31
4.59
1.00
6.12
5.26
0.74
6.87
5.89
0.30
7.67
6.57
-
-
-
900
1.40
5.88
5.06
1.24
6.79
5.83
1.00
7.50
6.43
0.57
8.42
7.17
0.35
9.31
7.92
950
1.67
6.60
5.67
1.53
7.73
6.62
1.29
8.36
7.13
0.86
9.25
7.87
0.65
10.43
8.96
1000
1.96
7.38
6.33
1.82
8.29
7.07
1.58
9.14
7.77
1.16
10.00
8.53
0.95
11.15
9.69
1050
2.23
8.04
6.87
2.09
9.00
7.66
1.88
9.92
8.46
1.46
11.00
9.54
1.26
12.12
10.59
1100
2.50
8.63
7.35
2.38
9.65
8.22
2.17
10.80
9.34
1.78
12.05
10.53
1.58
13.20
11.71
15 HP Motor and Drive
maximum 17.25 HP
10 HP Motor and Drive
maximum 11.5 HP
MODEL DSC360
Blower
RPM
CFM
12800
14400
16000
17600
19200
SP
BHP
KW
SP
BHP
KW
SP
BHP
KW
SP
BHP
KW
SP
BHP
KW
900
1.12
8.84
7.55
0.75
10.11
8.76
0.30
11.59
10.03
-
-
-
-
-
-
950
1.42
9.73
8.44
1.05
11.17
9.66
0.60
12.73
11.02
-
-
-
-
-
-
1000
1.72
10.59
9.16
1.36
12.19
10.55
0.92
13.78
11.96
0.42
15.45
13.49
-
-
-
1050
2.00
11.50
9.95
1.66
13.16
11.40
1.23
14.78
12.86
0.76
16.56
14.53
0.21
18.45
16.23
1100
2.30
12.27
10.62
1.98
14.10
12.24
1.58
15.83
13.84
1.10
17.61
15.49
0.55
19.54
17.28
1150
2.62
13.16
11.38
2.33
15.00
13.06
1.93
16.93
14.87
1.47
18.74
16.50
0.92
20.60
18.38
1190
2.89
13.79
11.97
2.60
15.73
13.75
2.22
17.70
15.57
1.76
19.58
17.32
1.25
21.52
19.36
NOTE: SP - Available Static Pressure in IWG to overcome the resistance of additional unit options and accessories and anything external to the unit.
*Unit resistance is based on a “Cooling Only” unit with wet evaporator coil, 2" throwaway or cleanable filters, no and/or fixed outside air, and bottom side x side duct connections.
20 HP Motor and Drive
maximum 23 HP
15 HP Motor and Drive
maximum 17.25 HP
MODEL DSC480
530.25-N3Y
22
Unitary Products Group