GROUND INSTALLATION

The unit may be installed at ground level on a solid base that will not
shift or settle, causing strain on the refrigerant lines and possible leaks.
Maintain the clearances shown in Figure 1 and install the unit in a level
position.

Normal operating sound levels may be objectionable if the unit is placed
directly under windows of certain rooms (bedrooms, study, etc.).

Isolate the unit from rain gutters to avoid any possible wash out of the
foundation.

ROOF INSTALLATION

When installing units on a roof, the structure must be capable of sup-
porting the total weight of the unit, including a pad, lintels, rails, etc.,
which should be used to minimize the transmission of sound or vibra-
tion into the conditioned space.

UNIT PLACEMENT

1.

Provide a base in the pre-determined location.

2.

Remove the shipping carton and inspect for possible damage.

3.

Compressor tie-down bolts should remain tightened.

4.

Position the unit on the base provided.

LIQUID LINE FILTER-DRIER

The air conditioning unit’s copper spun bi-flow filter/dryer is located on
the liquid line.

NOTE: Replacements for the liquid line drier must be exactly the same

as marked on the original factory drier. See 

Source 1 for O.E.M.

replacement driers.

PIPING CONNECTIONS

The outdoor condensing unit must be connected to the indoor evapora-
tor coil using field supplied refrigerant grade copper tubing that is inter-
nally clean and dry. Units should be installed only with the tubing sizes
for approved system combinations as specified in tabular data sheet.
The charge given is applicable for total tubing lengths up to 15 feet. See
Application Data Part Number 036-61920-000 for installing tubing of
longer lengths and elevation differences.

NOTE: 

Using a larger than specified line size could result in oil return

problems. Using too small a line will result in loss of capacity
and other problems caused by insufficient refrigerant flow. Slope
horizontal vapor lines at least 1" every 20 feet toward the out-
door unit to facilitate proper oil return.

PRECAUTIONS DURING LINE INSTALLATION

1.

Install the lines with as few bends as possible. Care must be taken
not to damage the couplings or kink the tubing. Use clean hard
drawn copper tubing where no appreciable amount of bending
around obstruction is necessary. If soft copper must be used, care
must be taken to avoid sharp bends which may cause a restriction.

2.

The lines should be installed so that they will not obstruct service
access to the coil, air handling system, or filter.

3.

Care must also be taken to isolate the refrigerant lines to minimize
noise transmission from the equipment to the structure.

4.

The vapor line must be insulated with a minimum of 1/2" foam rub-
ber insulation (Armaflex or equivalent). Liquid lines that will be
exposed to direct sunlight and/or high temperatures must also be
insulated.

Tape and suspend the refrigerant lines as shown. DO NOT allow tube
metal-to-metal contact. See Figure 2.

5.

Use PVC piping as a conduit for all underground installations as
shown in Figure 3. Buried lines should be kept as short as possible
to minimize the build up of liquid refrigerant in the vapor line during
long periods of shutdown

6.

Pack fiberglass insulation and a sealing material such as perma-
gum around refrigerant lines where they penetrate a wall to reduce
vibration and to retain some flexibility.

7.

See application part number 036-61920-000 for additional piping
information.

PRECAUTIONS DURING BRAZING OF LINES

All outdoor unit and evaporator coil connections are copper-to-copper
and should be brazed with a phosphorous-copper alloy material such
as Silfos-5 or equivalent. DO NOT use soft solder. The outdoor units
have reusable service valves on both the liquid and vapor connections.
The total system refrigerant charge is retained within the outdoor unit
during shipping and installation. The reusable service valves are pro-
vided to evacuate and charge per this instruction.

Serious service problems can be avoided by taking adequate precau-
tions to ensure an internally clean and dry system.

Failure to do so or using a substitute drier or a granular type may
result in damage to the equipment.

Filter-Drier

Source 1 Part No.

Apply with Models

CZE

029-22195-000

All

This system uses R-410A refrigerant which operates at higher pres-
sures than R-22. No other refrigerant may be used in this system.
Gauge sets, hoses, refrigerant containers, and recovery systems
must be designed to handle R-410A. If you are unsure, consult the
equipment manufacturer.

Never install a suction-line filter drier in the liquid line of an R-410A
system. Failure to follow this warning can cause a fire, injury or
death.

 FIGURE 2:  

Tubing Hanger

 FIGURE 3:  

Underground Installation

Liquid
Line

Incorrect

Correct

Tape

Sheet Metal Hanger

Insulated Vapor Line

TO INDOOR COIL

TO O UTDOOR UNIT

LIQUID LINE

CAP

PVC

CONDUIT

INSULATED

VAPOR LINE

Summary of Contents for CZE03811 Series

Page 1: ...hazardous situation which if not avoided may result in minor or moderate injury It is also used to alert against unsafe practices and hazards involving only property dam age INSPECTION As soon as a un...

Page 2: ...coil face to coil face If the unit is to be installed on a hot sun exposed roof or a black topped ground area the unit should be raised sufficiently above the roof or ground to avoid taking the accum...

Page 3: ...care must be taken to avoid sharp bends which may cause a restriction 2 The lines should be installed so that they will not obstruct service access to the coil air handling system or filter 3 Care mus...

Page 4: ...wrench back out counter clockwise until valve stem just touches the chamfered retaining wall See Page 4 PRECAU TIONS DURING BRAZING SERVICE VALVE 13 Replace plunger cap finger tight then tighten an ad...

Page 5: ...ply connections FIELD CONNECTIONS CONTROL WIRING 1 Route low voltage wiring into bottom of control box Make low volt age wiring connections inside the junction box per Figures 7 9 2 The complete conne...

Page 6: ...oil match up Some indoor coil matches may require additional charge See tabular data sheet provided in unit literature packet for charge requirements The TOTAL SYSTEM CHARGE must be permanently stampe...

Page 7: ...Owner Assist owner with processing warranty cards and or online registration Review Owners Manual provide a copy to the owner and provide guid ance on proper operation and maintenance Instruct the ow...

Page 8: ...ort AlertTM module marked R C and S 24 VAC Power Wiring The Comfort AlertTM module requires a con stant nominal 24 VAC power supply The wiring to the module s R and C terminals must be directly from t...

Page 9: ...ermittent Yellow ALERT Flash Code 4 Locked Rotor 1 Run capacitor has failed 2 Low line voltage contact utility if voltage at disconnect is low 3 Excessive liquid refrigerant in compressor 4 Compressor...

Page 10: ...103142 YIM A 1204 10 Unitary Products Group SECTION IX WIRING DIAGRAM FIGURE 10 Wiring Diagram...

Page 11: ...103142 YIM A 1204 Unitary Products Group 11 NOTES...

Page 12: ...ubject to change without notice Printed in U S A 103142 YIM A 1204 Copyright by York International Corp 2004 All rights reserved Supersedes Nothing Unitary 5005 Norman Product York OK Group Drive 7306...

Reviews: