background image

103142-YIM-A-1204

6

Unitary Products Group

DEHUMIDIFICATION CONTROL

A dehumidification control accessory 2HU06700124 may be used with
variable speed air handlers or furnaces in high humidity areas. This
control works with the variable speed indoor unit to provide cooling at a
reduced air flow, lowering evaporator temperature and increasing latent
capacity. The humidistat in this control opens the humidistat contacts on
humidity rise. To install, refer to instructions packaged with the acces-
sory and Figures 7-9. Prior to the installation of the dehumidification
control, the jumper across the HUMIDISTAT terminals on the indoor
variable speed air handler or furnace CFM selection board must be
removed.

During cooling, if the relative humidity in the space is higher than the
desired set point of the dehumidification control, the variable speed
blower motor will operate at lower speed until the dehumidification con-
trol is satisfied. A 40-60% relative humidity level is recommended to
achieve optimum comfort.

If a dehumidification control is installed, it is recommended that a mini-
mum air flow of 325 cfm/ton be supplied at all times.

SECTION VI: EVACUATION

It will be necessary to evacuate the system to 500 microns or less. If a
leak is suspected, leak test with dry nitrogen to locate the leak. Repair
the leak and test again. 

To verify that the system has no leaks, simply close the valve to the vac-
uum pump suction to isolate the pump and hold the system under vac-
uum. Watch the micron gauge for a few minutes. If the micron gauge
indicates a steady and continuous rise, it’s an indication of a leak. If the
gauge shows a rise, then levels off after a few minutes and remains
fairly constant, it’s an indication that the system is leak free but still con-
tains moisture and may require further evacuation if the reading is
above 500 microns.

SECTION VII: SYSTEM CHARGE

The factory charge in the outdoor unit includes enough charge for the
unit, a 15 ft. line set and the smallest rated indoor coil match-up. Some
indoor coil matches may require additional charge. See tabular data
sheet provided in unit literature packet for charge requirements.

The “TOTAL SYSTEM CHARGE” must be permanently stamped on the
unit data plate.

Total system charge is determined as follows:

1.

Determine outdoor unit charge from tabular data sheet.

2.

Determine indoor coil adjustment from tabular data sheet.

3.

Calculate the line charge using the tabular data sheet if line length
is greater than 15 feet.

4.

Total system charge = item 1 + item 2 + item 3.

5.

Permanently stamp the unit data plate with the total amount of
refrigerant in the system.

Use the following subcooling charging method whenever additional
refrigerant is required for the system charge. A superheat charging
method is not suitable for TXV equipped systems.

 FIGURE 7:  

Typical Variable Speed Air Handler Thermostat Wiring

 FIGURE 8:  

Typical Variable Speed Furnace Thermostat Wiring

 FIGURE 9:  

Typical Previous Generation Variable Speed Furnace  

Thermostat Wiring

VARIABLE

SPEED

AIR HANDLER

2 -STAGE

AIR CONDITIONER

C

Y1

R

W

O

G

C

Y1

R

O

Y

W2

W1

G

X/L

X/L

1

2

1

HUMIDISTAT CONTACTS OPEN ON HUMIDITY RISE.

JUMPER ON CFM SELECTION BOARD MUST BE

.

HUMIDISTAT

REMOVED

2

Y1, Y2, AND HUM LOCATED ON CFM SELECTION BOARD.

THERMOSTAT

E

Y2

Y2

HUM

BLU/YEL

YEL

BLK

RED

1

VARIABLE

SPEED

FURNACE

2-STAGE

AIR CONDITIONER

C

Y1

R

W

O

HUMIDISTAT CONTACTS OPEN ON HUMIDITY RISE.

JUMPER MUST BE IN

POSITION.

HUMIDISTAT INSTALLED?

YES

G

C

Y1

R

O

Y2/Y

W2

W1/W

G

HUM

X/L

X/L

1

2

THERMOSTAT

Y2

BLK

YEL

BLU/YEL

RED

2

HUM LOCATED ON CFM SELECTION BOARD.

E

1

VARIABLE

SPEED

FURNACE

2-STAGE

AIR CONDITONER

C

Y1

R

W

O

HUMIDISTAT CONTACTS OPEN ON HUMIDITY RISE.

JUMPER ON CFM SELECTION BOARD MUST BE

.

HUMIDISTAT

REMOVED

G

C

Y1

R

O

Y

W2

W1

G

HUM

X/L

X/L

1

THERMOSTAT

Y2

BLK

YEL

BLU/YEL

RED

E

Y2

R-410A refrigerant cylinders are rose colored, and have a dip tube
which allows liquid to flow out of the cylinder in the Upright Posi-
tion.
 Always charge the system slowly with the tank in the upright
position.

Do not leave the system open to the atmosphere.  Unit damage
could occur due to moisture being absorbed by the POE oil in the
system.  This type of oil is highly susceptible to moisture absorp-
tion.

Summary of Contents for CZE03811 Series

Page 1: ...hazardous situation which if not avoided may result in minor or moderate injury It is also used to alert against unsafe practices and hazards involving only property dam age INSPECTION As soon as a un...

Page 2: ...coil face to coil face If the unit is to be installed on a hot sun exposed roof or a black topped ground area the unit should be raised sufficiently above the roof or ground to avoid taking the accum...

Page 3: ...care must be taken to avoid sharp bends which may cause a restriction 2 The lines should be installed so that they will not obstruct service access to the coil air handling system or filter 3 Care mus...

Page 4: ...wrench back out counter clockwise until valve stem just touches the chamfered retaining wall See Page 4 PRECAU TIONS DURING BRAZING SERVICE VALVE 13 Replace plunger cap finger tight then tighten an ad...

Page 5: ...ply connections FIELD CONNECTIONS CONTROL WIRING 1 Route low voltage wiring into bottom of control box Make low volt age wiring connections inside the junction box per Figures 7 9 2 The complete conne...

Page 6: ...oil match up Some indoor coil matches may require additional charge See tabular data sheet provided in unit literature packet for charge requirements The TOTAL SYSTEM CHARGE must be permanently stampe...

Page 7: ...Owner Assist owner with processing warranty cards and or online registration Review Owners Manual provide a copy to the owner and provide guid ance on proper operation and maintenance Instruct the ow...

Page 8: ...ort AlertTM module marked R C and S 24 VAC Power Wiring The Comfort AlertTM module requires a con stant nominal 24 VAC power supply The wiring to the module s R and C terminals must be directly from t...

Page 9: ...ermittent Yellow ALERT Flash Code 4 Locked Rotor 1 Run capacitor has failed 2 Low line voltage contact utility if voltage at disconnect is low 3 Excessive liquid refrigerant in compressor 4 Compressor...

Page 10: ...103142 YIM A 1204 10 Unitary Products Group SECTION IX WIRING DIAGRAM FIGURE 10 Wiring Diagram...

Page 11: ...103142 YIM A 1204 Unitary Products Group 11 NOTES...

Page 12: ...ubject to change without notice Printed in U S A 103142 YIM A 1204 Copyright by York International Corp 2004 All rights reserved Supersedes Nothing Unitary 5005 Norman Product York OK Group Drive 7306...

Reviews: