Requirements For Installing/Servicing R-410A Equipment

Gauge sets, hoses, refrigerant containers, and recovery systems
must be designed to handle POE oils and the higher pressures of
R-410A.

Manifold sets should be 800 PSIG high side and 250 PSIG low
side with 550 PSIG low side retard.

All hoses must have a 700 PSIG service pressure rating.

Leak detectors should be designed to detect HFC refrigerant.

Recovery equipment (including refrigerant recovery containers)
must be specifically designed to handle R-410A.

Do not use an R-22 TXV.

A liquid-line filter drier is required on every unit.

LIMITATIONS

The unit should be installed in accordance with all National, State, and
Local Safety Codes and the limitations listed below:

1.

Limitations for the indoor unit, coil, and appropriate accessories
must also be observed.

2.

Only variable speed air handlers or variable speed furnaces
should be used with these models.

3.

The outdoor unit must not be installed with any duct work in the air
stream. The outdoor fan is the propeller type and is not designed
to operate against any additional external static pressure.

4.

The maximum and minimum conditions for operation must be
observed to ensure a system that will give maximum performance
with minimum service.

5.

The unit should not be operated at outdoor temperatures below
60° F without an approved low ambient operation accessory kit
installed.

6.

The maximum allowable line length for this product is 75 feet.

7.

Indoor evaporator coil orifice 

must

 be removed prior to the 

instal-

lation 

of a factory supplied balanced port TXV kit.

SECTION III: UNIT INSTALLATION

LOCATION

Before starting the installation, select and check the suitability of the
location for both the indoor and outdoor unit. Observe all limitations and
clearance requirements.

The outdoor unit must have sufficient clearance for air entrance to the
condenser coil, for air discharge, and for service access. See Figure 1.

NOTE: 

For multiple unit installations, units must be spaced a minimum

of 18 inches apart (coil face to coil face.).

If the unit is to be installed on a hot sun exposed roof or a black-topped
ground area, the unit should be raised sufficiently above the roof or
ground to avoid taking the accumulated layer of hot air into the outdoor
unit.

Provide an adequate structural support.

ADD-ON REPLACEMENT/RETROFIT

When this unit is being used as a replacement for an R-22 unit, it is
required that the outdoor unit, indoor coil, and metering device all be
replaced. Line-set change out is also recommended. The following
steps should be performed in order to insure proper system operation
and performance. 

1.

Change-out of the indoor coil to an approved R-410A coil with the
appropriate metering device.

2.

Change-out of the line-set when replacing an R-22 unit with an 
R-410A unit is highly recommended to reduce cross-contamina-
tion of oils and refrigerants. 

3.

If change-out of the line set is not practical, then the following pre-
cautions should be taken.

Inspect the line set for kinks, sharp bends, or other restrictions,
and for corrosion.

Determine if there are any low spots which might be serving as oil
traps. 

Flush the line set with a commercially available flush kit to
remove as much of the existing oil and contaminants as possible. 

Install a suction line filter-drier to trap any remaining contami-
nants, and remove after 50 hours of operation. 

4.

If the outdoor unit is being replaced due to a compressor burnout,
then installation of a 100% activated alumina suction-line filter
drier is required, in addition to the factory installed liquid-line drier.
Operate the system for 10 hours. Monitor the suction drier pres-
sure drop. If the pressure drop exceeds 3 psig, replace both the
suction-line and liquid-line driers. After a total of 10 hours run time
where the suction-line pressure drop has not exceeded 3 psig,
replace the liquid line drier, and remove the suction-line drier.
Never leave a suction-line drier in the system longer than 50 hours
of run time.

 FIGURE 1:  

Typical Installation

THERMOSTAT

NEC CLASS 1

WIRING

TO INDOOR
BLOWER

NEC CLASS 2
WIRING

TO COIL

WEATHERPROOF

DISCONNECT SWITCH

48” OVERHEAD
CLEARANCE

24” SERVICE
ACCESS
CLEARANCE

18” FRONT

& SIDES

NOTE:

ALL OUTDOOR WIRING MUST BE WEATHERPROOF

SEAL OPENINGS WITH
PERMAGUM OR EQUIVALENT

Summary of Contents for CZE03811 Series

Page 1: ...hazardous situation which if not avoided may result in minor or moderate injury It is also used to alert against unsafe practices and hazards involving only property dam age INSPECTION As soon as a un...

Page 2: ...coil face to coil face If the unit is to be installed on a hot sun exposed roof or a black topped ground area the unit should be raised sufficiently above the roof or ground to avoid taking the accum...

Page 3: ...care must be taken to avoid sharp bends which may cause a restriction 2 The lines should be installed so that they will not obstruct service access to the coil air handling system or filter 3 Care mus...

Page 4: ...wrench back out counter clockwise until valve stem just touches the chamfered retaining wall See Page 4 PRECAU TIONS DURING BRAZING SERVICE VALVE 13 Replace plunger cap finger tight then tighten an ad...

Page 5: ...ply connections FIELD CONNECTIONS CONTROL WIRING 1 Route low voltage wiring into bottom of control box Make low volt age wiring connections inside the junction box per Figures 7 9 2 The complete conne...

Page 6: ...oil match up Some indoor coil matches may require additional charge See tabular data sheet provided in unit literature packet for charge requirements The TOTAL SYSTEM CHARGE must be permanently stampe...

Page 7: ...Owner Assist owner with processing warranty cards and or online registration Review Owners Manual provide a copy to the owner and provide guid ance on proper operation and maintenance Instruct the ow...

Page 8: ...ort AlertTM module marked R C and S 24 VAC Power Wiring The Comfort AlertTM module requires a con stant nominal 24 VAC power supply The wiring to the module s R and C terminals must be directly from t...

Page 9: ...ermittent Yellow ALERT Flash Code 4 Locked Rotor 1 Run capacitor has failed 2 Low line voltage contact utility if voltage at disconnect is low 3 Excessive liquid refrigerant in compressor 4 Compressor...

Page 10: ...103142 YIM A 1204 10 Unitary Products Group SECTION IX WIRING DIAGRAM FIGURE 10 Wiring Diagram...

Page 11: ...103142 YIM A 1204 Unitary Products Group 11 NOTES...

Page 12: ...ubject to change without notice Printed in U S A 103142 YIM A 1204 Copyright by York International Corp 2004 All rights reserved Supersedes Nothing Unitary 5005 Norman Product York OK Group Drive 7306...

Reviews: