background image

103142-YIM-A-1204

Unitary Products Group

7

Measurement Method

If a calibrated charging cylinder or accurate weighing device is avail-
able, add refrigerant accordingly.

Check flare caps on service ports to be sure they are leak tight. DO
NOT OVERTIGHTEN (between 40 and 60 inch - lbs. maximum).

Subcooling Charging Method

This condensing unit must only be used with the matching thermostatic
expansion valve kit listed in the Tabular Data Sheet. This unit 

must

 be

charged during 

second-stage (Y1  & Y2) 

operation only

See Table 2

for unit specific subcooling charts.

For mix matched systems, the recommended subcooling is 10°F

1.

Set the system running in the 

Second-Stage (Y1 + Y2) 

cooling

mode by setting the thermostat at least 6°F below the room tem-
perature.

2.

Operate the system for a minimum of 15-20 minutes.

3.

Refer to the tabular data sheet for the recommended airflow and
verify this indoor airflow (it should be about 400 SCFM per ton).

4.

Measure the liquid refrigerant pressure P and temperature T at the
service valve.

5.

Calculate the saturated liquid temperature ST from Table 1.

6.

Subcooling temperature TC = Saturated Temperature (ST) - Liquid
Temp (T).

Add charge if the calculated subcooling temperature TC in Step 6 is
lower than the recommended level. Remove and recover the refrigerant
if the subcooling TC is higher than the recommended level. See Table 1
for R-410A saturation temperatures. 

SECTION VIII: SYSTEM START-UP

INDICATIONS OF PROPER OPERATION

Cooling

1.

The outdoor fan should be running, with warm air being dis-
charged from the top of the unit.

2.

The indoor blower (furnace or air handler) will be operating, dis-
charging cool air from the ducts. Coils or other parts in the air cir-
cuit should be cleaned as often as necessary to keep the unit
clean. Use a brush, vacuum cleaner attachment, or other suitable
means.

3.

The vapor line at the outdoor unit will feel cool to the touch.

4.

The liquid line at the outdoor unit will feel warm to the touch.

Instructing the Owner

Assist owner with processing warranty cards and/or online registration.
Review Owners Manual, provide a copy to the owner, and provide guid-
ance on proper operation and maintenance. Instruct the owner or the
operator how to start, stop, and adjust temperature setting.

The installer should also instruct the owner on proper operation and
maintenance of all other system components.

Maintenance

1.

Dirt should not be allowed to accumulate on the outdoor coils or
other parts in the air circuit. Clean as often as necessary to keep
the unit clean. Use a brush, vacuum cleaner attachment, or other
suitable means.

2.

The outdoor fan motor is permanently lubricated and does not
require periodic oiling.

NOTE: 

The outdoor fan motor is a permanent magnet DC brushless

type. The motor requires a separate Electronic Control to oper-
ate. Do not attempt to replace this motor with a typical PSC
type. Damage to Electronic Control may result.

3.

If the coil needs to be cleaned, it should be washed with Calgon
Coilclean (mix one part Coilclean to seven parts water). Allow
solution to remain on coil for 30 minutes before rinsing with clean
water. Solution should not be permitted to come in contact with
painted surfaces.

4.

Refer to the furnace or air handler instructions for filter and blower
motor maintenance.

5.

The indoor coil and drain pan should be inspected and cleaned
regularly to prevent odors and assure proper drainage.

Refrigerant charging should only be carried out by a qualified air
conditioning contractor.

Compressor damage will occur if system is improperly charged. On
new system installations, charge system per tabular data sheet for
the matched coil and follow guidelines in this instruction.

Example: The pressure P and temperature T measured at the liquid 
service port is 360 Psig and 93°F. From Table 1, the saturated tem-
perature for 360 Psig is 109°. The subcooling temperature TC = 
109°-93°=16°F

IT IS UNLAWFUL TO KNOWINGLY VENT, RELEASE OR DIS-
CHARGE REFRIGERANT INTO THE OPEN AIR DURING
REPAIR, SERVICE, MAINTENANCE OR THE FINAL DIS-
POSAL OF THIS UNIT.
WHEN THE SYSTEM IS FUNCTIONING PROPERLY AND
THE OWNER HAS BEEN FULLY INSTRUCTED, SECURE
THE OWNER’S APPROVAL.

Summary of Contents for CZE03811 Series

Page 1: ...hazardous situation which if not avoided may result in minor or moderate injury It is also used to alert against unsafe practices and hazards involving only property dam age INSPECTION As soon as a un...

Page 2: ...coil face to coil face If the unit is to be installed on a hot sun exposed roof or a black topped ground area the unit should be raised sufficiently above the roof or ground to avoid taking the accum...

Page 3: ...care must be taken to avoid sharp bends which may cause a restriction 2 The lines should be installed so that they will not obstruct service access to the coil air handling system or filter 3 Care mus...

Page 4: ...wrench back out counter clockwise until valve stem just touches the chamfered retaining wall See Page 4 PRECAU TIONS DURING BRAZING SERVICE VALVE 13 Replace plunger cap finger tight then tighten an ad...

Page 5: ...ply connections FIELD CONNECTIONS CONTROL WIRING 1 Route low voltage wiring into bottom of control box Make low volt age wiring connections inside the junction box per Figures 7 9 2 The complete conne...

Page 6: ...oil match up Some indoor coil matches may require additional charge See tabular data sheet provided in unit literature packet for charge requirements The TOTAL SYSTEM CHARGE must be permanently stampe...

Page 7: ...Owner Assist owner with processing warranty cards and or online registration Review Owners Manual provide a copy to the owner and provide guid ance on proper operation and maintenance Instruct the ow...

Page 8: ...ort AlertTM module marked R C and S 24 VAC Power Wiring The Comfort AlertTM module requires a con stant nominal 24 VAC power supply The wiring to the module s R and C terminals must be directly from t...

Page 9: ...ermittent Yellow ALERT Flash Code 4 Locked Rotor 1 Run capacitor has failed 2 Low line voltage contact utility if voltage at disconnect is low 3 Excessive liquid refrigerant in compressor 4 Compressor...

Page 10: ...103142 YIM A 1204 10 Unitary Products Group SECTION IX WIRING DIAGRAM FIGURE 10 Wiring Diagram...

Page 11: ...103142 YIM A 1204 Unitary Products Group 11 NOTES...

Page 12: ...ubject to change without notice Printed in U S A 103142 YIM A 1204 Copyright by York International Corp 2004 All rights reserved Supersedes Nothing Unitary 5005 Norman Product York OK Group Drive 7306...

Reviews: